The text of a manual · part 20 of 30
Variable speed drives Altivar 61 Catalogue: Safety requirements
Pages 114 to 127 of 211, from Variable speed drives Altivar 61 Catalogue
The original document is the PDF (4.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Telemecanique Altivar 61 ATV61, Schneider Altivar 61 ATV61 and Square D Altivar 61 ATV61
Page 114
Schemes
0
Variable speed drives for asynchronous motors
0
Altivar 61 Safety requirements
“Power Removal” safety function The Altivar 61 drive integrates the “Power Removal” safety function which prohibits unintended equipment operation. The motor no longer produces torque. This safety function: b conforms to machine safety standard EN 954-1, category 3 b conforms to operational safety standard IEC/EN 61508, capacity SIL2 (safety control-signalling applied to processes and systems) The SIL (Safety Integrity Level) capacity depends on the connection diagram for the drive and for the safety function. Failure to follow the setup recommendations could inhibit the SIL capacity of the “Power Removal” safety function. b conforms to draft product standard IEC/EN 61800-5-2 for both stop functions: v Safe Torque Off (“STO”) v Safe Stop 1 (“SS1”) The “Power Removal” safety function has a redundant electronic architecture (1) which is monitored continuously by a diagnostics function. This SIL2 and category 3 level of safety function is certified as conforming to these standards by the INERIS certification body under a program of voluntary certification.
Categories relating to safety according to EN 954-1 Categories Main safety basis B
1
Selecting components which conform to the relevant standards Selecting components and safety principles
2
Selecting components and safety principles
3
Structure of the safety circuits
4
Structure of the safety circuits
Control system Behaviour in the requirements event of a fault Monitoring in accordance with Possible loss of safety established practice function Use of tested components and Possible loss of safety tested safety principles function with a lower probability than in B Test per cycle. The intervals Fault detected on each test between tests must be appropriate to both the machine and its application A single fault should not result Safety function assured in loss of the safety function. except in the event of The fault must be detected if an accumulation of faults this is reasonably possible A single fault should not result Safety function always in loss of the safety function. assured The fault must be detected when or before the safety function is next invoked. An accumulation of faults should not result in loss of the safety function.
The machine manufacturer is responsible for selecting the safety category. The category depends on the level of risk factors given in standard EN 954-1.
Safety Integrity Levels (SIL) according to standard IEC/EN 61508 SIL1 according to standard IEC/EN 61508 is comparable with category 1 according to EN 954-1 (SIL1: mean probability of undetected dangerous failure per hour between 10-5 and 10-6). SIL2 according to standard IEC/EN 61508 is comparable with category 3 according to EN 954-1 (SIL 2: mean probability of undetected dangerous failure per hour between 10-6 and 10-7). (1) Redundant: consists of mitigating the effects of failure of one component by means of the correct operation of another, assuming that faults do not occur simultaneously on both.
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Functions: pages 148 to 175
112 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 115
Schemes (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61 Safety requirements
“Power Removal” safety function considerations The “Power Removal” safety function cannot be considered as a means of electrical disconnection of the motor (no electrical isolation); if necessary, a Vario switch disconnector must be used. The “Power Removal” safety function is not designed to overcome any malfunction in the drive process control or application functions. The output signals available on the drive must not be considered as safety signals (example: “Power Removal” active); these are Preventa-type safety module outputs which must be integrated into a safety control-signalling circuit. The schemes on the following pages take into account conformity with standard IEC/EN 60204-1 that defines 3 stop categories: b Category 0: stopping by immediate removal of the power from the actuators (example: uncontrolled stop) b Category 1: controlled stop maintaining the power on the actuators until the machine stops, then cutting off the power when the actuators stop as a result of the machine stopping b Category 2: controlled stop maintaining the power on the actuators
Connection schemes and applications Conformity with category 1 of standard EN 954-1 and level SIL1 according to standard IEC/EN 61508 Use of the connection schemes on pages 114 and 115 which use a line contactor or a Vario switch disconnector between the drive and the motor. In this case, the “Power Removal” safety function is not used and the motor stops in accordance with category 0 of standard IEC/EN 60204-1. Conformity with category 3 of standard EN 954-1 and level SIL2 according to standard IEC/EN 61508 The connection diagrams use the “Power Removal” safety function of the Altivar 61 drive combined with a Preventa safety module to monitor the Emergency stop circuits. Machines with short freewheel stopping times (low inertia, see page 116). When the activation command is given on the PWR input with the controlled motor, the motor power supply is immediately switched off and the motor stops according to category 0 of standard IEC/EN 60204-1. Restarting is not permitted (“STO”) if the activation command is given after the motor has come to a complete stop. This safe stop is maintained while the PWR input remains activated. Machines with long freewheel stopping times (high inertia, see page 117). When the activation command is given, deceleration of the motor controlled by the drive is first requested, then, following a time delay controlled by a Preventa-type fault relay which corresponds to the deceleration time, the “Power Removal” safety function is activated by the PWR input. The motor stops according to category 1 of standard IEC/EN 60204-1 (“SS1”). Periodic test The “Power Removal” safety input must be activated at least once a year for preventive maintenance purposes. The drive power supply must be switched off and then on again before carrying out this preventive maintenance. If during testing the power supply to the motor is not switched off, safety integrity is no longer assured for the “Power Removal” safety function. The drive must therefore be replaced to ensure the operational safety of the machine or of the system process.
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Functions: pages 148 to 175
113 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 116
Schemes (continued)
Variable speed drives for asynchronous motors
0
0
Altivar 61
Schemes conforming to standards EN 954-1 category 1, IEC/EN 61508 capacity SIL1, in stopping category 0 according to IEC/EN 60204-1
1
3
5
2
4
6
Q1
5
Power section for single phase power supply
3
ATV 61H075M3…HU75M3
3-phase power supply with upstream breaking via contactor 1
ATV 61ppppM3, ATV 61ppppM3X, ATV 61ppppN4, ATV 61WpppN4C
6
4
2
Q1
1 Q2 2
T1
1 Q3 2
S2
S1
A1
KM1 A2
To 1/Q2
3
4
5
6
KM1 2
(1)
(1)
(4)
Reference potentiometer
X-Y mA or 0…10 V
W/T3
S/L2
R/L1
W1
V/T2
U/T1
COM
(6)
(5) M 3
U1
L1
AI2
AI1–
AI1+
+ 10
PA/+
PO
PC/–
W/T3
V/T2 W1
V1
U1
U/T1
ATV 61pppppp
A1
V1
PWR COM
LI6
+ 24 AO1
LI5
LI4
LI3
LI2
LI1
R2C
R2A
R1C
R1A
T/L3
S/L2
R/L1
R1B
(3)
(2) (2) (2) A1
3
KM1 13 14
6
4
2
R1C
4
R1A
KM1
1
5
3
1
To 3/Q2
A1
M 3
Note: All terminals are located at the bottom of the drive. Install interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc. Components for use with the Altivar (for a complete list of references, see our “Motor starter solutions. Power control and protection components” specialist catalogue). Reference Description A1 ATV 61 drive, see pages 18 to 21 KM1 Contactor, see motor starters pages 128 to 137 L1 DC choke, see page 65 Q1 Circuit-breaker, see motor starters pages 128 to 137 Q2 GV2 L rated at twice the nominal primary current of T1 Q3 GB2 CB05 S1, S2 XB4 B or XB5 A pushbuttons T1 100 VA transformer 220 V secondary (1) Line choke (single phase or 3-phase), see page 68. (2) For ATV 61HC50N4 and ATV 61HC63N4 drives, see page 118. (3) Fault relay contacts for remote signalling of the drive status (4) Connection of the common for the logic inputs depends on the positioning of the SW1 switch: see schemes on page 118. (5) DC choke as an option for ATV 61HpppM3, ATV 61HD11M3X…HD45M3X, ATV 61H075N4…HD75N4. Connected in place of the strap between the PO and PA/+ terminals. For ATV 61HD55M3X, HD75M3X, ATV 61HD90N4…HC50N4 drives, the choke is supplied with the drive; the customer is responsible for connecting it. On drives ATV 61WpppN4 and ATV 61WpppN4C, the DC choke is integrated. (6) Software-configurable current (0…20 mA) or voltage (0…10 V) analog input.
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Functions: pages 148 to 175
114 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 117
Schemes (continued)
Variable speed drives for asynchronous motors
0
0
Altivar 61
Schemes conforming to standards EN 954-1 category 1, IEC/EN 61508 capacity SIL1, in stopping category 0 according to IEC/EN 60204-1 (continued)
5 5/L3 W1 6/T3
W/T3
S/L2
R/L1 V/T2 3/L2
U/T1 1/L1
W1 6/T3
V1 4/T2
COM
AI2
AI1–
AI1+
+ 10
PA/+
PO
PC/–
W/T3
V/T2 3/L2
L1
(6)
(5) V1 4/T2
A1
5/L3
U/T1 1/L1
ATV 61pppppp
U1 2/T1
PWR COM
LI6
+ 24 AO1
LI5
LI4
LI3
LI2
LI1
R2C
R2A
R1C
R1A
T/L3
S/L2
R/L1
R1B
(3)
(2) (2) (2)
U1 2/T1
6
(1)
(4)
Q2
4
2
6
4
2
Q1
(1)
A1
3
1
Q1
5
Power section for single phase power supply
3
ATV 61H075M3…HU75M3
3-phase power supply with downstream breaking via switch disconnector 1
ATV 61ppppM3, ATV 61ppppM3X, ATV 61ppppN4, ATV 61WpppN4C
Reference potentiometer
Q2
X-Y mA or 0…10 V
M 3
M 3
Note: All terminals are located at the bottom of the drive. Install interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc. Components for use with the Altivar (for a complete list of references, see our “Motor starter solutions. Power control and protection components” specialist catalogue). Reference Description A1 ATV 61 drive, see pages 18 to 21 L1 DC choke, see page 65 Q1 Circuit-breaker, see motor starters pages 128 to 137 Q2 Switch disconnector (Vario) (1) Line choke (single phase or 3-phase), see page 68. (2) For ATV 61HC50N4 and ATV 61HC63N4 drives, see page 118. (3) Fault relay contacts for remote signalling of the drive status (4) Connection of the common for the logic inputs depends on the positioning of the SW1 switch: see schemes on page 118. (5) DC choke as an option for ATV 61H pppM3, ATV 61HD11M3X…HD45M3X, ATV 61H075N4…HD75N4. Connected in place of the strap between the PO and PA/+ terminals. For ATV 61HD55M3X, HD75M3X, ATV 61HD90N4…HC50N4 drives, the choke is supplied with the drive; the customer is responsible for connecting it. On drives ATV 61WpppN4 and ATV 61Wppp N4C, the DC choke is integrated. (6) Software-configurable current (0…20 mA) or voltage (0…10 V) analog input.
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Functions: pages 148 to 175
115 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 118
Schemes (continued)
Variable speed drives for asynchronous motors
0
0
Altivar 61
Schemes conforming to standards EN 954-1 category 3, IEC/EN 61508 capacity SIL2, in stopping category 0 according to IEC/EN 60204-1
(2)
N (–) S1 Y1
XPS AC
Logic
–
T
13
23
33
Y43
14
24
34
Y44
2
+
Y2
6
A1
4
(2) A2
6
4
Q1
ESC
(3) 2
1
S2
(1)
5
F1
L1 (+)
5
Q1
3
Power section for single phase power supply
3
ATV 61H075M3…HU75M3
3-phase power supply, low inertia machine
1
ATV 61HpppM3, ATV 61HpppM3X, ATV 61ppppN4, ATV 61WpppN4C
K1 K2
(4) K1
48 V, 115 V, 230 V A2
K2
PE
(4)
LI6
PWR
AO1
COM
Reference potentiometer
W/T3
S/L2
R/L1
W1
(11) X-Y mA or 0…10 V
V/T2
U/T1 U1
COM
AI2
AI1–
AI1+
L1
A1
V1
LI5
LI4
LI3
LI2
LI1
R2C
R2A
+ 10
R1B
R1C PO
PA/+
R1A PC/–
W/T3
T/L3
S/L2 V/T2 W1
U/T1
R/L1 V1
U1
ATV 61pppppp
(10) M 3
(9)
(7)
(6) (6) (6) A1
(8)
+ 24
(5)
M 3
Note: All terminals are located at the bottom of the drive. Install interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc. Components for use with the Altivar (for a complete list of references, see our “Motor starter solutions. Power control and protection components” and “Preventa safety solutions” specialist catalogues). Reference Description A1 ATV 61 drive, see pages 18 to 21 A2 Preventa XPS AC safety module for monitoring Emergency stops and switches. One safety module can manage the “Power Removal” function for several drives on the same machine. F1 Fuse L1 DC choke, see page 65 Q1 Circuit-breaker, see motor starters pages 128 to 137 S1 Emergency stop button with 2 contacts S2 XB4 B or XB5 A pushbutton (1) Power supply: c or 24 V a, 48 V a, 115 V a, 230 V a. (2) S2: resets XPS AC module on power-up or after an Emergency stop. ESC can be used to set external starting conditions. (3) Requests freewheel stopping of the movement and activates the “Power Removal” safety function. (4) Line choke (single phase or 3-phase), see page 68. (5) The logic output can be used to signal that the machine is in a safe stop state. (6) For ATV 61HC50N4 and ATV 61HC63N4 drives, see page 118. (7) Fault relay contacts for remote signalling of the drive status (8) Connection of the common for the logic inputs depends on the positioning of the SW1 switch: see schemes on page 118. (9) Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B according to NF C 93-550, external diameter 2.54 mm, maximum length 2m. The cable shielding must be earthed. (10)DC choke as an option for ATV 61HppppM3, ATV 61HD11M3X…HD45M3X, ATV 61H075N4…HD75N4. Connected in place of the strap between the PO and PA/+ terminals. For ATV 61HD55M3X, HD75M3X, ATV 61HD90N4…HC50N4 drives, the choke is supplied with the drive; the customer is responsible for connecting it. On drives ATV 61WpppN4 and ATV 61WpppN4C, the DC choke is integrated. (11)Software-configurable current (0…20 mA) or voltage (0…10 V) analog input.
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Functions: pages 148 to 175
116 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 119
Schemes (continued)
Variable speed drives for asynchronous motors
0
0
Altivar 61
Schemes conforming to standards EN 954-1 category 3, IEC/EN 61508 capacity SIL2, in stopping category 1 according to IEC/EN 60204-1
L1 (+)
F1
(+)
(–)
(1)
Q1 S1(2) 13 23 33 41
K2
K3
1 2
+
K1 K3
K1
K2
K4
K4
K1
K2 K3
6
(3)
K2
K4
58 68
(5)
(6)
ESC
(4)
L1
(10)
COM
U1
+ 24
PWR
AO1
LI6
LI5
LI3
LI2
LI4 or
M 3
(13)
(12) M 3
ATV 61pppppp COM
AI1–
(11)
AI2
LI1
R2C AI1+
R2A
+ 10
R1C
R1B
PA/+
PO
R1A PC/–
W/T3
V/T2
T/L3
S/L2 W1
V1
U1
U/T1
R/L1
A1
U/T1
(9) (8)
(7) (7) (7)
R/L1
A1
S/L2
S2 (4)
Y1 Y2 Y3 Y4 Y5 14 24 34 42
W/T3
(3)
S33
W1
PE
V/T2
A2 N (–)
V1
4
2
115 V 230 V
57 67 6
K1
5
3
1
T -
S12 S22
4
S21 S11 B1
XPS AT
2
A1
Q1
5
Power section for single phase power supply
3
ATV 61H075M3…HU75M3
3-phase power supply, high inertia machine
1
ATV 61HpppM3, ATV 61HpppM3X, ATV 61ppppN4, ATV 61WpppN4C
X-Y mA Reference potentiometer
0…10 V
Note: All terminals are located at the bottom of the drive. Install interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc. Components for use with the Altivar (for a complete list of references, see our “Motor starter solutions. Power control and protection components” and “Preventa safety solutions” specialist catalogues). Reference Description A1 ATV 61 drive, see pages 18 to 21 A2 (6) Preventa XPS AT safety module for monitoring Emergency stops and switches. One safety module can manage the “Power Removal” safety function for several drives on the same machine, but the time delay must be adjusted on the drive controlling the motor that requires the longest stopping time. F1 Fuse L1 DC choke, see page 65 Q1 Circuit-breaker, see motor starters pages 128 to 137 S1 Emergency stop button with 2 contacts S2 XB4 B or XB5 A pushbutton (1) Power supply: c or 24 V a, 115 V a, 230 V a. (2) Requests controlled stopping of the movement and activates the “Power Removal” safety function. (3) Line choke (single phase or 3-phase), see page 68. (4) S2: resets XPS AT module on power-up or after an Emergency stop. ESC can be used to set external starting conditions. (5) The “O” contact can be used to signal that the machine is in a safe stop state. (6) For stopping times requiring more than 30 seconds in category 1, use a Preventa XPS AV safety module which can provide a maximum time delay of 300 seconds. (7) For ATV 61HC50N4 and ATV 61HC63N4 drives, see page 118. (8) Fault relay contacts for remote signalling of the drive status (9) Connection of the common for the logic inputs depends on the positioning of the SW1 switch: see schemes on page 118. (10)Standardized coaxial cable, type RG174/U according to MIL-C17 or KX3B according to NF C 93-550, external diameter 2.54 mm, maximum length 2m. The cable shielding must be earthed. (11)Logic inputs LI1 and LI2 must be assigned to the direction of rotation: LI1 in the forward direction and LI2 in the reverse direction. (12)DC choke as an option for ATV 61HppppM3, ATV 61HD11M3X…HD45M3X, ATV 61H075N4…HD75N4. Connected in place of the strap between the PO and PA/+ terminals. For ATV 61HD55M3X, HD75M3X, ATV 61HD90N4…HC50N4 drives, the choke is supplied with the drive; the customer is responsible for connecting it. On drives ATV 61WpppN4 and ATV 61WpppN4C, the DC choke is integrated. (13)Software-configurable current (0…20 mA) or voltage (0…10 V) analog input.
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Functions: pages 148 to 175
117 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 120
Schemes (continued)
Variable speed drives for asynchronous motors
0
0
Altivar 61
Power terminal connections For ATV 61HC50N4 and ATV 61HC63N4 To circuit-breaker (1)
To - DC bus
To + DC bus
(3)
(3)
(3)
(3) PO/2
PA/+
PA/+
PA/+
PA/+
PC/–
PO/1
PC/–
T/L3.2
S/L2.2
R/L1.2
T/L3.1
S/L2.1
R/L1.1
(2)
ATV 61HC50N4, HC63N4 (1) For control section connections, see pages 114 to 117. (2) Line choke, see page 68. (3) DC chokes provided as standard with the drive
VW3 A7 7pp braking resistors or VW3 A7 1pp braking units
A1
A1
A1 BU/–
PB
PA
BU/+
ATV 61HC25N4…HC63N4
PB
ATV 61HD55M3X…HD90M3X, ATV 61HD90N4…HC22N4
PA/+
ATV 61HpppM3, ATV 61HD11M3X…HD45M3X, ATV 61H075N4 …HD75N4, ATV 61WpppN4, ATV 61WpppN4C
BU/–
Braking resistor
BU/+
TH Braking resistor
Braking resistor
PA
PB Braking unit
(1)
A2
Components for use with the Altivar Reference A1 A2 Braking resistor
Description ATV 61 drive, see pages 18 to 21 Braking unit, if using a braking resistor for ATV 61HC25N4…HC63N4, see page 55 See page 57
(1) Option of using a thermal overload relay.
Examples of recommended schemes Logic inputs The SW1 switch is used to adapt operation of the logic inputs (LI) to the PLC output technology: b Set the switch to Source (factory setting) if using PLC outputs with PNP transistors, b Set the switch to Sink Int or Sink Ext if using PLC outputs with NPN transistors Internal power supply Switch in “Source” position
SW1 Source Sink Ext. Int.
LI6
0V 0V
LI4
SW1
SW2
LI4
LI3
LI2
+24
LI1
ATV 61pppppp
Sink Ext. Int.
0V
LI6
LI5
Source
LI4
LI3
LI2
+24
LI1
ATV 61pppppp
Sink Ext. Int.
SW2 PTC LI
+ 24 V 0V
+ 24 V 0V
24 V c supply
Presentation: pages 4 to 7
LI3
Switch in “Sink Ext” position
SW1
PTC LI
LI6
External power supply Switch in “Source” position
LI5
PTC LI
LI5
SW2
PTC LI
LI2
+24
SW2
Source
ATV 61pppppp
0V
LI6
LI5
LI4
LI3
LI2
LI1
ATV 61pppppp
Sink Ext. Int.
+24
Source
Switch in “Sink Int” position
LI1
SW1
24 V c supply
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Functions: pages 148 to 175
118 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 121
Schemes (continued)
Variable speed drives for asynchronous motors
0
0
Altivar 61
Examples of recommended schemes (continued) Input for PTC probes The SW2 switch is used to operate the LI6 input: b As a logic input by setting the SW2 switch to LI (factory setting) b Or for protecting the motor via PTC probes by setting the SW2 switch to PTC A1
ATV 61pppppp LI6
PTC LI
0V
SW2
Motor
2-wire control and jog operation (JOG)
3-wire control and jog operation (JOG)
Forward
Reverse
JOG Forward
+ 24
LI4
LI3
LI1
+ 24
LIp
LIp
LIp
Stop
LI2
ATV 61pppppp
ATV 61pppppp
JOG forward
Reverse
JOG reverse
Unipolar speed reference
Bipolar speed reference Requires a VW3 A3 201 or VW3 A3 202 I/O extension card
VW3 A3 20p – 10
COM
AI1+
+10
COM
AI1 –
AI1+
+10
Reference potentiometer
AI1 –
ATV 61pppppp
ATV 61pppppp
Reference potentiometer
Separate control power supply The separate control card can be powered by an external 24 V c supply
P 24
0V
ATV 61pppppp
0V
+ 24 V 24 V c supply
ATV 61pppppp
ATV 61pppppp
ATV 61pppppp
0…10 V
AI2
AI2 Supply 0-20 mA 4-20 mA X-Y mA
Speed
+ 10 V reference potentiometer 2.2 to 10 kΩ
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
COM
0-20 mA, 4-20 mA, X-Y mA
COM
External + 10 V
COM
Analog input configured for current
External 0…10 V
AI2
Analog input configured for voltage
References: pages 18 to 21
Dimensions: pages 90 to 111
Functions: pages 148 to 175
119 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 122
Schemes (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61
VW3 A3 201 and VW3 A3 202 I/O extension cards Logic I/O The SW3 or SW4 switch is used to adapt operation of the logic inputs (LI) to the PLC output technology: b Set the switch to Source (factory setting) if using PLC outputs with PNP transistors, b Set the switch to Sink Int or Sink Ext if using PLC outputs with NPN transistors Internal power supply Switch in “Source” position
R B
VW3 A3 20
SW3/SW4
VW3 A3 20
TH –
TH
CLO
LO
LI
LO
0V
Sink Ext. Int.
+24
TH –
+ TH
CLO
LO
LI
LO
0V
Source
+
SW3/SW4
Sink Ext. Int.
+24
Source
R C
R A
R B
R A
R C
Switch in “Sink Int” position
Motor
External power supply Switch in “Source” position
VW3 A3 20
R B
R C
R A
R B
R A
R C
Switch in “Sink Ext” position
VW3 A3 20
Motor
+ 24 V
TH –
TH
CLO
LO
LI
LO
0V
Sink Ext. Int.
+24
Source
TH –
TH
CLO
LO
LI
LO
0V
+24
+
Sink Ext. Int.
+
SW3/SW4
SW3/SW4 Source
Motor
Motor
+ 24 V
0V
0V
24 V c supply
24 V c supply
Analog I/O (only on VW3 A3 202 extended I/O card)
0V
RP
COM
AO3 (1)
AO2 (1)
COM
AI4
AI3 –
AI3 +
VW3 A3 202
(2) Supply 0-20 mA 4-20 mA X-Y mA
R (3)
X-Y mA or 0…10 V
(1)
(1) Software-configurable current (0-20 mA) or voltage (0…10 V) analog input. (2) Software-configurable current (0-20 mA) or voltage (± 10 V or 0…10 V) analog outputs, independent selection possible for each output via switch. (3) R: add a resistor if the input voltage of the pulse train is greater than 5 V. Recommended values: Input voltage Resistance V Ω 12 510 15 910 24 1300
Presentation: page 30
Characteristics: pages 30 and 31
References: page 19
Functions: pages 148 to 175
120 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 123
Schemes (continued)
Variable speed drives for asynchronous motors
0
0
Altivar 61
VW3 A3 502 and VW3 A3 503 multi-pump cards, VW3 A3 501 “Controller Inside” programmable card Card powered by the drive (1) ATV 61pppppp
VW3 A3 50p
COM
AI52
AI51
24 V
LO5p
LO5p
Sink Ext. Int.
LI5p
Source
+ 24 V
SW1
0-20 mA 0-20 mA
Card powered by external power supply
COM
AO52
AO51
COM
AI52
AI51
24 V
LO5p
LO5p
LI5p
COM
VW3 A3 50p
+ 24 V 0V
0-20 mA 0-20 mA
0-20 mA 0-20 mA
24 V c supply
(1) Only if the power consumption is less than 200 mA; otherwise use an external power supply.
Presentation: pages 32 and 36
Characteristics: pages 35 to 38
References: pages 35 to 43
Functions: pages 148 to 175
121 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 124
Schemes (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61
VW3 A4 6pp passive filters Standard scheme
Scheme for filter control by drive depending on load
ATV 61H
N4
X4.3 X3.3
X4.2 X3.2
X4.1 X3.1
KM1
R2C
B
X2.3 X1.3 L3
(1) A
X2.2 X1.2 L2
ATV 61H
VW3 A4 6
R2A
X2.1 X1.1 L1
X4.3 X3.3
X4.2 X3.2
X4.1 X3.1
X2.3 X1.3 L3
B
X2.2 X1.2 L2
(1) A
X2.1 X1.1 L1
(2) (2) (2) VW3 A4 6
N4
(1) Contact making it possible to show the thermal state of the passive filter (2) Supplied wired.
VW3 A4 4pp additional EMC input filters 3-phase power supply, 3-phase filter
Single phase power supply, 3-phase filter
L3 L'3 L3
L2 L'2
L1 L'1
ATV 61Hppppp
L2
VW3 A3 4pp
L1
L'3 L3
L3
L'2 L2
L2
L'1 L1
L1
(1)
VW3 A3 4pp
ATV 61Hppppp
(1) Line choke compulsory for ATV 61HU40M3…HU75M3, see page 68.
Output filters VW3 A5 1pp motor chokes
VW3 A5 2pp sinus filters
ATV 61Hppppp
V
W W WT/3
W1
U UT/1
VT/2 V
U
U1
VW3 A5 2pp
M 3
M 3
Presentation: pages 69, 74 and 78
V1
PE
W W WT/3
PE
V
VW3 A5 1pp
W1
U UT/1
VT/2
U
V
V1
U1
PE
PE
ATV 61Hppppp
Characteristics: pages 69, 75 and 78
References: pages 70, 76 and 78
Dimensions: pages 104 to 111
Functions: pages 148 to 175
122 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 125
Schemes (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61
Drives combined with a braking unit and wired onto the same DC bus ATV 61HC25N4…HC63N4
PC/–
BU/+
PA/+ PC/–
M
M
TH BU/+
PA
BU/–
PB
L3
ATV 61 HC25N4…HC63N4 V
BU/–
L2 PO
W
PA/+
L2
L1
L1 PO
U
U
BU/+
W
ATV 61 HC25N4…HC63N4 V
BU/–
3a
L3
L1
L2
3a
TH
Braking resistor
(1)
Braking unit
BU/+
PA
BU/–
PB
Braking resistor
(1)
Braking unit
(1) Option of using a thermal overload relay.
Drive powered by external DC power supply ATV 61HD18M3X…HD45M3X, ATV 61HD22N4…HD75N4, ATV 61WD22N4…WD90N4, ATV 61WD22N4C…WD90N4C
+ – F2
(2) A1
F1
(2) A1
R2A
PC/–
P0 W/T3 W1
V1
U1
M 3
V/T2
U/T1
PA/+
R2C
R2A
P0
A2
W/T3 W1
PC/–
PA/+ V/T2 V1
U1
U/T1
A1
A2
R2 - KM2 A2
R1 - KM1
R2C
DC power supply (1)
M 3
For drives A1, A2
Braking resistors R1, R2 Value Ω 5 5 5 5 5 5 5 5 5 5 5 5
Reference
Contactors (3) KM1, KM2
ATV 61HD18M3X VW3 A7 707 LC1 D32pp ATV 61HD22M3X VW3 A7 707 LC1 D40pp ATV 61HD30M3X VW3 A7 707 LC1 D65pp ATV 61HD37M3X VW3 A7 707 LC1 D80pp ATV 61HD45M3X VW3 A7 707 LC1 D80pp ATV 61HD22N4, ATV 61WD22N4, WD22N4C VW3 A7 707 LC1 D25pp ATV 61HD30N4, ATV 61WD30N4, WD30N4C VW3 A7 707 LC1 D32pp ATV 61HD37N4, ATV 61WD37N4, WD37N4C VW3 A7 707 LC1 D38pp ATV 61HD45N4, ATV 61WD45N4, WD45N4C VW3 A7 707 LC1 D40pp ATV 61HD55N4, ATV 61WD55N4, WD55N4C VW3 A7 707 LC1 D50pp ATV 61HD75N4, ATV 61WD75N4, WD75N4C VW3 A7 707 LC1 D80pp ATV 61HD90N4, ATV 61WD90N4, WD90N4C VW3 A7 707 LC1 D80pp (1) DC power supply not included. (2) Fast-acting fuses, see page 125. The function of the fuses is to protect the DC bus wiring in the event of a drive short-circuit. (3) See our “Motor starter solutions. Power control and protection components” specialist catalogue. Note: ATV 61HpppM3, ATV 61HD11M3X, HD15M3X, ATV 61H075N4…HD18N4, ATV 61W075N4…WD18N4 and ATV 61W075N4C…WD18N4C have an integrated pre-charge circuit. This is used to connect the DC power supply directly to the drive without the need for an external pre-charge circuit. Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Functions: pages 148 to 175
123 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 126
Schemes (continued)
Variable speed drives for asynchronous motors
0
0
Altivar 61
Connection diagrams for several drives in parallel on the DC bus Drives with different ratings
Q1
Q2
KM1 F2
F3
F4
M1
PC/–
RO
W
TO
ATV 61
M3
V
U
W
U
W
M2
PA/+
PC/–
PA/+
A4
ATV 61
V
U
V
ATV 61
W
U
ATV 61
A3
V
A2
F1
PC/–
+
PA/+
L3
L1
A1
L2
IL
SO
(1) (1) (1)
M4
Reference A1
Description ATV 61 drive, see pages 18 to 21. Drive power = ∑ motor power ratings M1 + M2 + M3 + M4 +… A2, A3, A4 ATV 61 drives powered by the DC bus. They must be protected using fast-acting fuses. Contactors on the DC circuit are ineffective as the switching action may cause the fuses to blow owing to the high load current. F1 Fast-acting fuses, see page 125. Drive A1 powered by the AC supply with an output bus. The function of the fuse is to protect the internal diode bridge in the event of a short-circuit on the external DC bus. F2, F3, F4 Fast-acting fuses, see page 125. Drives A2 and A3 are powered by their DC bus and are not connected to the AC input. The function of the fuses is to protect the DC bus wiring in the event of a drive short-circuit. (1) With ATV 61HD90M3X and ATV 61HC11N4…HC63N4 drives, make provision for connection of the fans’ power supply.
Drives with equivalent ratings
KM1
Q3
Q2
F2
F1, F2, F3 KM1 L1, L2, L3
PA/+ PC/–
M2
L3
L2
A3
ATV 61pppppp
V
PC/–
W
PA/+
PO
F3
L3 (1)
W
L3
L2
ATV 61pppppp
M1
Reference A1, A2, A3
L1
A2
PO
V
V
W
U
ATV 61pppppp
U
L3
L2
L1
A1
L2 (1)
L1
F1
L1 (1)
U
Q1
PO
PA/+ PC/–
M3
Description ATV 61 drives, see pages 18 to 21. The power difference between the drives connected in parallel must not exceed any rating. Fast-acting fuses, see page 125. Drives A1, A2 and A3 powered by the AC supply with an output bus. The function of the fuse is to protect the internal diode bridge in the event of a short-circuit on the external DC bus. When using a common line contactor, all the Altivar 61 drive load circuits operate in parallel and cannot therefore be overloaded. DC chokes, see page 65.
Q1, Q2, Q3
Circuit-breakers on the line supply side to protect drives against overloads. Use trip contacts on the “external fault” logic input or the line contactor. The line contactor must only be activated if all three circuit-breakers are closed, as otherwise there is a risk of damage to the drives. (1) DC chokes compulsory except for ATV 61HD55M3X…HD90M3X and ATV 61HD90N4…HC63N4 (these drives include a DC choke as standard).
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Functions: pages 148 to 175
124 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 127
Combinations
0
Variable speed drives for asynchronous motors
0
Altivar 61
Size of DC bus fuses (F1, F2, F3, F4) depending on the drive rating For drives ATV 61H075M3 ATV 61HU15M3, HU22M3 ATV 61HU30M3 ATV 61HU40M3, HU55M3 ATV 61HU75M3 ATV 61HD11M3X ATV 61HD15M3X ATV 61HD18M3X ATV 61HD22M3X ATV 61HD30M3X ATV 61HD37M3X ATV 61HD45M3X ATV 61HD55M3X ATV 61HD75M3X ATV 61HD90M3X ATV 61H075N4…HU22N4, ATV 61W075N4…WU22N4, ATV 61W075N4C…WU22N4C ATV 61HU30N4, HU40N4, ATV 61WU30N4, WU40N4, ATV 61WU30N4C, WU40N4C ATV 61HU55N4, ATV 61WU55N4, ATV 61WU55N4C ATV 61HU75N4, HD11N4, ATV 61WU75N4, WD11N4, ATV 61WU75N4C, WD11N4C ATV 61HD15N4…HD22N4, ATV 61WD15N4…WD22N4, ATV 61WD15N4C…WD22N4C ATV 61HD30N4, HD37N4, ATV 61WD30N4, WD37N4, ATV 61WD30N4C, WD37N4C ATV 61HD45N4, ATV 61WD45N4, ATV 61WD45N4C ATV 61HD55N4, ATV 61WD55N4, ATV 61WD55N4C ATV 61HD75N4, HD90N4 ATV 61WD75N4, WD90N4, ATV 61WD75N4C, WD90N4C ATV 61HC11N4 ATV 61HC13N4 ATV 61HC16N4 ATV 61HC22N4 ATV 61HC25N4 ATV 61HC31N4 ATV 61HC40N4 ATV 61HC50N4 ATV 61HC63N4 (1) Nominal voltage of fast-acting fuse: Line voltage aV 230 400 440 460 480
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Fast-acting fuses (1) A 10 16 25 40 50 80 100 125 160 200 250 315 350 500 630 10
16
25
40
80
125
160
200
315
400 500 550 800 900 1100 1400 1800 2250 Nominal voltage of fast-acting fuse V 690 690 800 800 800
Dimensions: pages 90 to 111
Functions: pages 148 to 175
125 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com