Page 128

Installation recommendations

0

Variable speed drives for asynchronous motors

0

Altivar 61 Electromagnetic compatibility

Connections to meet the requirements of EMC standards Principle b Earths between drive, motor and cable shielding must have “high frequency” equipotentiality. b Use shielded cables with shielding connected to earth over 360° at both ends for the motor cable, the braking resistor cable and the control-signalling cables. Conduit or metal ducting can be used for part of the shielding length provided that there is no break in the continuity of the earth connections. b Ensure maximum separation between the power supply cable (line supply) and the motor cable.

2

9 9 1

9 5 3

87 6

Installation plan for ATV 61HpppM3, ATV 61HpppM3X, ATV 61HpppN4 drives

4

ATV 61H pppM3, ATV 61HD11M3X, HD15M3X, ATV 61H075N4…HD18N4

2

9

9 1

5

3

8

6 7 4

1 Steel plate (1), to be mounted on the drive (machine earth). 2 Altivar 61 UL Type 1/IP 20 drive. 3 Unshielded power supply wires or cable. 4 Unshielded wires for the output of the fault relay contacts. 5 Attach and earth the shielding of cables 6, 7 and 8 as close as possible to the drive: - strip the shielding, - attach the cable to the plate 1 by attaching the clamp to the stripped part of the shielding. The shielding must be clamped tightly enough to the metal plate to ensure good contact. 6 Shielded cable for connecting the motor 7 Shielded cable for connecting the control/signalling wiring. For applications requiring several conductors, use cables with a small crosssection (0.5 mm2). 8 Shielded cable for connecting the braking resistor 6, 7, 8, the shielding must be earthed at both ends. The shielding must be continuous and intermediate terminals must be placed in EMC shielded metal boxes. 9 Earth screw. Note: The HF equipotential ground connection between the drive, motor and cable shielding does not remove the need to connect the PE protective conductors (green-yellow) to the appropriate terminals on each unit. If using an additional EMC input filter, it should be mounted beneath the drive and connected directly to the line supply via an unshielded cable. Link 3 on the drive is then via the filter output cable.

ATV 61HD18M3X…HD45M3X, ATV 61HD22N4…HD75N4

(1) Plate supplied for ATV 61HpppM3, ATV 61HD11M3X, HD45M3X and ATV 61H075N4…HD75N4 drives. For ATV 61HD55M3X... HD90M3X and ATV 61HD90N4…HC31N4 drives, the plate is supplied with the UL Type 1 conformity kit or the IP 21 or IP 31 conformity kit, to be ordered separately, see pages 24 and 25. For ATV 61HC40N4...HC63N4 drives the plate is supplied with the IP 31 conformity kit, to be ordered separately, see page 25.

2

5

1

5

3

8

6

7

4

ATV 61HD55M3X…HD90M3X, ATV 61HD90N4…HC63N4

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 and 19

Dimensions: pages 90 to 111

Functions: pages 148 to 175

126 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 129

Variable speed drives for asynchronous motors

Installation recommendations (continued)

0

0

Altivar 61 Electromagnetic compatibility

Connections to meet the requirements of EMC standards (continued) Installation plan for ATV 61WpppN4, ATV 61WpppN4C drives 1 Steel plate (machine earth) 2 Altivar 61 UL Type 12/IP 54 drive. 3 Unshielded power supply wires or cable. 4 Unshielded wires for the output of the fault relay contacts. 5 Attach and earth the shielding of cables 6, 7 and 8 as close as possible to the drive: - strip the shielding, - Attach the shielded cable to the cable gland 9 ensuring it is fully in contact 360°, - fold back the shielding and clamp it between the ring and the body of the cable gland. According to the rating, the cable shielding 7 can be earthed by using a cable gland 5, a clamp 5 or a cable clip 5. The shielding must be clamped tightly enough to the metal plate to ensure good contact. 6 Shielded cable for connecting the motor 7 Shielded cable for connecting the control/signalling wiring. For applications requiring several conductors, use cables with a small cross-section (0.5 mm2). 8 Shielded cable for connecting the braking resistor 6, 7, 8, the shielding must be earthed at both ends. The shielding must be continuous and intermediate terminals must be placed in EMC shielded metal boxes. 9 Metal cable gland (not supplied) for cables 6, 7 and 8. Standard cable gland (not supplied) for cables 3 and 4.

5

2 1

5

9

3

8 4 7 6

ATV 61W075N4…WD30N4, ATV 61W075N4C…WD30N4C

Note: The HF equipotential ground connection between the drive, motor and cable shielding does not remove the need to connect the PE protective conductors (green-yellow) to the appropriate terminals on each unit. If using an additional EMC input filter, it should be mounted beneath the drive and connected directly to the line supply via an unshielded cable. Link 3 on the drive is then via the filter output cable.

5 2 5

1 9

3

8 4 7 6

ATV 61WD37N4…WD90N4, ATV 61WD37N4C…WD90N4C

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 20 and 21

Dimensions: pages 90 to 111

Functions: pages 148 to 175

127 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 130

Combinations for customer assembly

0

Variable speed drives for asynchronous motors

0

Altivar 61 Motor starters: supply voltage 200…240 V

Applications DF534567

Circuit-breaker/contactor/drive combinations can be used to ensure continuous service of the installation with optimum safety. The type of circuit-breaker/contactor coordination selected can reduce maintenance costs in the event of a motor short-circuit by minimizing the time required to make the necessary repairs and the cost of replacement equipment. The suggested combinations provide type 1 or type 2 coordination depending on the drive rating.

DF534568

Type 2 coordination: A motor short-circuit will not damage the device or affect its settings. The motor starter should be able to operate once the electrical fault has been removed. The electrical isolation provided by the circuit-breaker will not be affected by the short-circuit. Welding of the contactor contacts is permissible if they can be separated easily. Type 1 coordination: The electrical isolation provided by the circuit-breaker will not be affected by the incident and no other elements apart from the contactor are damaged as a result of the motor short-circuit. The drive controls the motor, provides protection against short-circuits between the drive and the motor and protects the motor cable against overloads. The overload protection is provided by the drive's motor thermal protection. If this protection is removed, external thermal protection should be provided. Before restarting the installation, the cause of the trip must be removed. DF534636

Motor starters for UL Type 1/IP 20 drives Motor Power (1) kW

Drive Reference

Circuit-breaker Reference (2)

HP

Rating Im

Line contactor Reference (3) (4)

A

A

GV2 L14 GV2 L16 GV2 L20 GV2 L32 NS80HMA50 GV2 L32 NS80HMA50 NS80HMA50

10 14 18 32 50 32 50 50

– – – – 300 – 300 300

LC1 D09pp LC1 D18pp LC1 D25pp LC1 D32pp LC1 D32pp LC1 D32pp LC1 D32pp LC1 D40pp

NS80HMA50

50

300

LC1 D50pp

Single phase supply voltage: 200…240 V 50/60 Hz. Type 2 coordination

GV2 L20 + LC1 D25pp + ATV 61HU22M3

0.37 0.75 1.5 2.2

0.5 1 2 3

ATV 61H075M3 ATV 61HU15M3 ATV 61HU22M3 ATV 61HU30M3

3

–

4

5

5.5

7.5

ATV 61HU40M3 (5) ATV 61HU55M3 (5) ATV 61HU75M3 (5)

Single phase supply voltage: 200…240 V 50/60 Hz. Type 1 coordination 0.37 0.75 1.5 2.2 3

0.5 1 2 3 –

ATV 61H075M3 GV2 LE14 10 – LC1 K06pp ATV 61HU15M3 GV2 LE16 14 – LC1 K06pp ATV 61HU22M3 GV2 LE20 18 – LC1 K06pp ATV 61HU30M3 GV2 LE32 32 – LC1 D18pp ATV 61HU40M3 GV2 LE32 32 – LC1 D18pp (5) 4 5 ATV 61HU55M3 NS80HMA50 50 300 LC1 D40pp (5) 5.5 7.5 ATV 61HU75M3 NS80HMA50 50 300 LC1 D40pp (5) (1) Standard power ratings for 4-pole motors 230 V 50/60 Hz. The values expressed in HP comply with the NEC (National Electrical Code). (2) NS80HMA: product sold under the Merlin Gerin brand. Breaking capacity of circuit-breakers according to standard IEC 60947-2: Circuit-breaker Icu (kA) for 240 V GV2 L14, GV2 L16, 100 GV2 LE14…GV2 LE20 GV2 L20, GV2 L32, 50 GV2 LE32 NS80HMA 100 (3) Composition of contactors: LC1 K06: 3 poles + 1 “N/O” auxiliary contact and 1 “N/C” auxiliary contact. LC1 D09 to LC1 D50: 3 poles + 1 “N/O” auxiliary contact and 1 “N/C” auxiliary contact. (4) Replace pp with the control circuit voltage reference indicated in the table below. Volts a 24 48 110 220 230 240 LC1 K06 50/60 Hz B7 E7 F7 M7 P7 U7 LC1 Dpp 50 Hz B5 E5 F5 M5 P5 U5 60 Hz B6 E6 F6 M6 – U6 50/60 Hz B7 E7 F7 M7 P7 U7 For other voltages available between 24 V and 660 V, or a DC control circuit, please consult your Regional Sales Office. (5) A line choke must be added (see page 68).

128 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 131

Variable speed drives for asynchronous motors

Combinations for customer assembly (continued)

0

0

Altivar 61 Motor starters: supply voltage 200…240 V

Motor starters for UL Type 1/IP 20 drives DF534570

Motor Power (1) kW

Drive Reference

Circuit-breaker Reference (2)

HP

Rating Im A

A

6.3 14 18 25 32 50 50 80 80 80 100 150 150 220 220 320 500

– – – – – 300 300 480 480 480 600 1350 1350 1980 1980 1920 3000

Line contactor Reference (3) (4)

3-phase supply voltage: 200…240 V 50/60 Hz. Type 2 coordination

DF534629

DF534571

0.75 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90

1 2 3 – 5 7.5 10 15 20 25 30 40 50 60 75 100 125

ATV 61H075M3 ATV 61HU15M3 ATV 61HU22M3 ATV 61HU30M3 ATV 61HU40M3 ATV 61HU55M3 ATV 61HU75M3 ATV 61HD11M3X ATV 61HD15M3X ATV 61HD18M3X ATV 61HD22M3X ATV 61HD30M3X ATV 61HD37M3X ATV 61HD45M3X ATV 61HD55M3X ATV 61HD75M3X ATV 61HD90M3X

GV2 L10 GV2 L16 GV2 L20 GV2 L22 GV2 L32 NS80HMA50 NS80HMA50 NS80HMA80 NS80HMA80 NS80HMA80 NS100pMA100 NS160pMA150 NS160pMA150 NS250pMA220 NS250pMA220 NS400pMA320 NS630pMA500

LC1 D09pp LC1 D18pp LC1 D18pp LC1 D25pp LC1 D40pp LC1 D40pp LC1 D50pp LC1 D65pp LC1 D80pp LC1 D80pp LC1 D115pp LC1 D115pp LC1 D150pp LC1 F185pp LC1 F225pp LC1 F265pp LC1 F330pp

3-phase supply voltage: 200…240 V 50/60 Hz. Type 1 coordination

NS80HMA50 + LC1 D40pp + ATV 61HU55M3

0.75 1 ATV 61H075M3 GV2 LE10 6.3 – LC1 K06pp 1.5 2 ATV 61HU15M3 GV2 LE16 14 – LC1 K06pp 2.2 3 ATV 61HU22M3 GV2 LE20 18 – LC1 K06pp 3 – ATV 61HU30M3 GV2 LE22 25 – LC1 K06pp 4 5 ATV 61HU40M3 GV2 LE32 32 – LC1 D18pp 5.5 7.5 ATV 61HU55M3 NS80HMA50 50 300 LC1 D25pp 7.5 10 ATV 61HU75M3 NS80HMA50 50 300 LC1 D32pp 11 15 ATV 61HD11M3X NS80HMA80 80 480 LC1 D40pp 15 20 ATV 61HD15M3X NS80HMA80 80 480 LC1 D50pp 18.5 25 ATV 61HD18M3X NS80HMA80 80 480 LC1 D50pp 22 30 ATV 61HD22M3X NS100pMA100 100 600 LC1 D80pp 30 40 ATV 61HD30M3X NS160pMA150 150 1350 LC1 D80pp 37 50 ATV 61HD37M3X NS160pMA150 150 1350 LC1 D115pp 45 60 ATV 61HD45M3X NS250pMA220 220 1320 LC1 D115pp 55 75 ATV 61HD55M3X NS250pMA220 220 1980 LC1 D115pp 75 100 ATV 61HD75M3X NS400pMA320 320 1920 LC1 F185pp 90 125 ATV 61HD90M3X NS630pMA500 500 3000 LC1 F265pp (1) Standard power ratings for 4-pole motors 230 V 50/60 Hz. The values expressed in HP comply with the NEC (National Electrical Code). (2) NS80HMApp, NSpppp MA : products sold under the Merlin Gerin brand. Breaking capacity of circuit-breakers according to standard IEC 60947-2: Circuit-breaker Icu (kA) for 240 V N H L GV2 L10, GV2 L16, GV2 L20, 100 – – – GV2 LE10, GV2 LE16, GV2 LE20 GV2 L22, GV2 L32, 50 – – – GV2 LE22, GV2 LE32 NS80HMA 100 – – – NSppppMA – 85 100 150 (3) Composition of contactors: LC1 K06: 3 poles + 1 “N/O” auxiliary contact and 1 “N/C” auxiliary contact. LC1 D09 to LC1 D150: 3 poles + 1 “N/O” auxiliary contact and 1 “N/C” auxiliary contact. LC1 Fppp: 3 poles. To add auxiliary contacts or other accessories, please consult our specialist catalogue “Motor-starter solutions. Control and protection components”. (4) Replace pp with the control circuit voltage reference indicated in the table below. Volts a 24 48 110 220 230 240 LC1 K06 50/60 Hz B7 E7 F7 M7 P7 U7 LC1 D09…D150 50 Hz B5 E5 F5 M5 P5 U5 60 Hz B6 E6 F6 M6 – U6 50/60 Hz B7 E7 F7 M7 P7 U7 LC1 F185, F225 50 Hz (LX1 coil) B5 E5 F5 M5 P5 U5 60 Hz (LX1 coil) – E6 F6 M6 – U6 40…400 Hz (LX9 coil) – E7 F7 M7 P7 U7 LC1 F265, LC1 F330 40…400 Hz (LX1 coil) B7 E7 F7 M7 P7 U7 For other voltages available between 24 V and 660 V, or a DC control circuit, please consult your Regional Sales Office.

129 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 132

Variable speed drives for asynchronous motors

Combinations for customer assembly (continued)

0

0

Altivar 61 Motor starters: supply voltage 380…415 V

DF534573

Motor starters for UL Type 1/IP 20 drives Motor Power (1) kW

Drive Reference

Circuit-breaker Reference (2)

HP

Rating Im A A

Line contactor Reference (3) (4)

3-phase supply voltage: 380…415 V 50/60 Hz. Type 2 coordination

DF534631

DF534574

0.75 1.5 2.2 3 4 5.5 7.5

NS160pMA150 + LC1 D115pp + ATV 61HD55N4

1 2 3 – 5 7.5 10

ATV 61H075N4 ATV 61HU15N4 ATV 61HU22N4 ATV 61HU30N4 ATV 61HU40N4 ATV 61HU55N4 ATV 61HU75N4

GV2 L08 4 – LC1 D09pp GV2 L10 6.3 – LC1 D09pp GV2 L14 10 – LC1 D09pp GV2 L16 14 – LC1 D18pp GV2 L16 14 – LC1 D18pp GV2 L22 25 – LC1 D25pp GV2 L32 32 – LC1 D32pp NS80HMA50 50 300 LC1 D32pp 11 15 ATV 61HD11N4 NS80HMA50 50 300 LC1 D40pp 15 20 ATV 61HD15N4 NS80HMA50 50 300 LC1 D50pp 18.5 25 ATV 61HD18N4 NS80HMA50 50 300 LC1 D50pp 22 30 ATV 61HD22N4 NS80HMA80 80 480 LC1 D50pp 30 40 ATV 61HD30N4 NS80HMA80 80 480 LC1 D65pp 37 50 ATV 61HD37N4 NS80HMA80 80 480 LC1 D80pp 45 60 ATV 61HD45N4 NS100pMA100 100 600 LC1 D115pp 55 75 ATV 61HD55N4 NS160pMA150 150 1350 LC1 D115pp 75 100 ATV 61HD75N4 NS250pMA220 220 1980 LC1 F185pp 90 125 ATV 61HD90N4 NS250pMA220 220 1980 LC1 F185pp 110 150 ATV 61HC11N4 NS250pMA220 220 1980 LC1 F225pp 132 200 ATV 61HC13N4 NS250pMA220 220 1980 LC1 F265pp 160 250 ATV 61HC16N4 NS400pMA320 320 1920 LC1 F330pp 200 300 ATV 61HC22N4 NS630pMA500 500 3000 LC1 F400pp 220 350 ATV 61HC22N4 NS630pMA500 500 3000 LC1 F400pp 250 400 ATV 61HC25N4 NS630pMA500 500 3000 LC1 F500pp 280 450 ATV 61HC31N4 NS630pMA500 500 3000 LC1 F500pp 315 500 ATV 61HC31N4 NS800L Micrologic 2 or 5 (LR OFF) 800 1600 LC1 F630pp 355 – ATV 61HC40N4 NS800L Micrologic 2 or 5 (LR OFF) 800 1600 LC1 F630pp 400 600 ATV 61HC40N4 NS800L Micrologic 2 or 5 (LR OFF) 800 1600 LC1 F630pp 500 700 ATV 61HC50N4 NS1000L Micrologic 2 or 5 (LR OFF) 1000 2000 LC1 F630pp 560 800 ATV 61HC63N4 NS1000L Micrologic 2 or 5 (LR OFF) 1000 2000 LC1 F780pp (1) Standard power ratings for 4-pole motors 400 V 50/60 Hz. The values expressed in HP comply with the NEC (National Electrical Code). (2) NS80HMApp, NSpppp: products sold under the Merlin Gerin brand. For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance (N, H, L). Breaking capacity of circuit-breakers according to standard IEC 60947-2: Circuit-breaker Icu (kA) for 400 V N H L GV2 L08…L14 100 – – – GV2 L16…L32 50 – – – NS80HMA 70 – – – NS100pMA – 25 70 150 NS160pMA, NS250pMA – 36 70 150 NS400pMA, NS630pMA – 45 70 150 NS800L Micrologic 2 or 5, – – – 150 NS1000L Micrologic 2 or 5 (3) Composition of contactors: LC1 D09 to LC1 D115: 3 poles + 1 “N/O” auxiliary contact and 1 “N/C” auxiliary contact. LC1 Fppp: 3 poles. To add auxiliary contacts or other accessories, please consult our specialist catalogue “Motor-starter solutions. Control and protection components”. (4) Replace pp with the control circuit voltage reference indicated in the table below. Volts a 24 48 110 220 230 240 LC1 D09…D115 50 Hz B5 E5 F5 M5 P5 U5 60 Hz B6 E6 F6 M6 – U6 50/60 Hz B7 E7 F7 M7 P7 U7 LC1 F185, F225 50 Hz (LX1 coil) B5 E5 F5 M5 P5 U5 60 Hz (LX1 coil) – E6 F6 M6 – U6 40…400 Hz (LX9 coil) – E7 F7 M7 P7 U7 LC1 F265, F330 40…400 Hz (LX1 coil) B7 E7 F7 M7 P7 U7 LC1 F400…F630 40…400 Hz (LX1 coil) – E7 F7 M7 P7 U7 LC1 F780 40…400 Hz (LX1 coil) – – F7 P7 P7 P7 For other voltages available between 24 V and 660 V, or a DC control circuit, please consult your Regional Sales Office.

130 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 133

Variable speed drives for asynchronous motors

Combinations for customer assembly (continued)

0

0

Altivar 61 Motor starters: supply voltage 380…415 V

DF534573

Motor starters for UL Type 1/IP 20 drives Motor Power (1) kW

Drive

Circuit-breaker

Reference

Reference (2)

HP

Rating Im A A

Line contactor Reference (3) (4)

3-phase supply voltage: 380…415 V 50/60 Hz. Type 1 coordination

DF534631

DF534632

0.75 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 250 280 315 355 400 500 560 630

NS160pMA150 + LC1 D80pp + ATV 61HD55N4

1 2 3 – 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450 500 – 600 700 800 900

ATV 61H075N4 ATV 61HU15N4 ATV 61HU22N4 ATV 61HU30N4 ATV 61HU40N4 ATV 61HU55N4 ATV 61HU75N4 ATV 61HD11N4 ATV 61HD15N4 ATV 61HD18N4 ATV 61HD22N4 ATV 61HD30N4 ATV 61HD37N4 ATV 61HD45N4 ATV 61HD55N4 ATV 61HD75N4 ATV 61HD90N4 ATV 61HC11N4 ATV 61HC13N4 ATV 61HC16N4 ATV 61HC22N4 ATV 61HC22N4 ATV 61HC25N4 ATV 61HC31N4 ATV 61HC31N4 ATV 61HC40N4 ATV 61HC40N4 ATV 61HC50N4 ATV 61HC63N4 ATV 61HC63N4

GV2 LE08 4 GV2 LE10 6.3 GV2 LE14 10 GV2 LE16 14 GV2 LE16 14 GV2 LE22 25 GV2 LE32 32 NS80HMA50 50 NS80HMA50 50 NS80HMA50 50 NS80HMA80 50 NS80HMA80 80 NS80HMA80 80 NS100pMA100 100 NS160pMA150 150 NS250pMA220 220 NS250pMA220 220 NS250pMA220 220 NS250pMA220 220 NS400pMA320 320 NS630pMA500 500 NS630pMA500 500 NS630pMA500 500 NS630pMA500 500 NS800 Micrologic 2 or 5 (LR OFF) 800 NS800 Micrologic 2 or 5 (LR OFF) 800 NS800 Micrologic 2 or 5 (LR OFF) 800 NS1000 Micrologic 2 or 5 (LR OFF) 1000 NS1000 Micrologic 2 or 5 (LR OFF) 1000 NS1250 Micrologic 2 or 5 (LR OFF) 1000

– – – – – – – 300 300 300 300 480 480 600 1350 1980 1980 1980 1980 1920 3000 3000 3000 3000 1600 1600 1600 2000 2000 2000

LC1 K06pp LC1 K06pp LC1 K06pp LC1 K06pp LC1 K06pp LC1 D09pp LC1 D18pp LC1 D25pp LC1 D32pp LC1 D32pp LC1 D32pp LC1 D50pp LC1 D80pp LC1 D80pp LC1 D80pp LC1 D115pp LC1 D115pp LC1 F150pp LC1 F150pp LC1 F225pp LC1 F330pp LC1 F330pp LC1 F400pp LC1 F400pp LC1 F500pp LC1 F500pp LC1 F630pp LC1 F630pp LC1 F630pp LC1 F630S011

(1) Standard power ratings for 4-pole motors 400 V 50/60 Hz. The values expressed in HP comply with the NEC (National Electrical Code). (2) NS80HMApp, NSpppp: products sold under the Merlin Gerin brand. For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance (N, H, L). Breaking capacity of circuit-breakers according to standard IEC 60947-2: Circuit-breaker Icu (kA) for 400 V N H L GV2 LE08…LE22 15 – – – GV2 LE32 10 – – – NS80HMA 70 – – – NS100pMA – 25 70 150 NS160pMA, NS250pMA – 36 70 150 NS400pMA, NS630pMA – 45 70 150 NS800 Micrologic 2 or 5, – 50 70 – NS1000 Micrologic 2 or 5, NS1250 Micrologic 2 or 5 (3) Composition of contactors: LC1 K06, LC1 D09 to LC1 D115: 3 poles + 1 “N/O” auxiliary contact and 1 “N/C” auxiliary contact. LC1 Fppp: 3 poles. To add auxiliary contacts or other accessories, please consult our specialist catalogue “Motor-starter solutions. Control and protection components”. (4) Replace pp with the control circuit voltage reference indicated in the table below. Volts a 24 48 110 220 230 240 LC1 K06 50/60 Hz B7 E7 F7 M7 P7 U7 LC1 D09…D115 50 Hz B5 E5 F5 M5 P5 U5 60 Hz B6 E6 F6 M6 – U6 50/60 Hz B7 E7 F7 M7 P7 U7 LC1 F150, F225 50 Hz (LX1 coil) B5 E5 F5 M5 P5 U5 60 Hz (LX1 coil) – E6 F6 M6 – U6 40…400 Hz (LX9 coil) – E7 F7 M7 P7 U7 LC1 F330 40…400 Hz (LX1 coil) B7 E7 F7 M7 P7 U7 LC1 F400…F630 40…400 Hz (LX1 coil) – E7 F7 M7 P7 U7 For other voltages available between 24 V and 660 V, or a DC control circuit, please consult your Regional Sales Office.