Page 134

Variable speed drives for asynchronous motors

Combinations for customer assembly (continued)

0

0

Altivar 61 Motor starters: supply voltage 380…415 V

DF534573

Motor starters for UL Type 12/IP 54 drives Motor Power (1) kW

Drive

Circuit-breaker

Reference

Reference (2)

HP

Rating Im A A

Line contactor Reference (3) (4)

3-phase supply voltage: 380…415 V 50/60 Hz Type 2 coordination

DF534634

DF534574

0.75

NS160pMA150 + LC1 D115pp + ATV 61WD55N4

1

ATV 61W075N4 GV2 L07 2.5 – LC1 D09pp ATV 61W075N4C 1.5 2 ATV 61WU15N4 GV2 L08 4 – LC1 D09pp ATV 61WU15N4C 2.2 3 ATV 61WU22N4 GV2 L10 6.3 – LC1 D09pp ATV 61WU22N4C 3 – ATV 61WU30N4 GV2 L14 10 – LC1 D09pp ATV 61WU30N4C 4 5 ATV 61WU40N4 GV2 L14 10 – LC1 D09pp ATV 61WU40N4C 5.5 7.5 ATV 61WU55N4 GV2 L16 14 – LC1 D18pp ATV 61WU55N4C 7.5 10 ATV 61WU75N4 GV2 L20 18 – LC1 D18pp ATV 61WU75N4C 11 15 ATV 61WD11N4 GV2 L22 25 – LC1 D25pp ATV 61WD11N4C 15 20 ATV 61WD15N4 GV2 L32 32 – LC1 D40pp ATV 61WD15N4C 18.5 25 ATV 61WD18N4 NS80HMA50 50 300 LC1 D40pp ATV 61WD18N4C 22 30 ATV 61WD22N4 NS80HMA50 50 300 LC1 D50pp ATV 61WD22N4C 30 40 ATV 61WD30N4 NS80HMA80 80 480 LC1 D65pp ATV 61WD30N4C 37 50 ATV 61WD37N4 NS80HMA80 80 480 LC1 D80pp ATV 61WD37N4C 45 60 ATV 61WD45N4 NS100pMA100 100 600 LC1 D80pp ATV 61WD45N4C 55 75 ATV 61WD55N4 NS160pMA150 150 1350 LC1 D115pp ATV 61WD55N4C 75 100 ATV 61WD75N4 NS160pMA150 150 1350 LC1 D115pp ATV 61WD75N4C 90 125 ATV 61WD90N4 NS250pMA220 220 1980 LC1 F185pp ATV 61WD90N4C (1) Standard power ratings for 4-pole motors 400 V 50/60 Hz. The values expressed in HP comply with the NEC (National Electrical Code). (2) NS80HMApp, NSpppp: products sold under the Merlin Gerin brand. For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance (N, H, L). Breaking capacity of circuit-breakers according to standard IEC 60947-2: Circuit-breaker Icu (kA) for 400 V N H L GV2 L07…L14 100 – – – GV2 L16…L32 50 – – – NS80HMA 70 – – – NS100pMA – 25 70 150 NS160pMA, NS250pMA – 36 70 150 (3) Composition of contactors: LC1 D09 to LC1 D115: 3 poles + 1 “N/O” auxiliary contact and 1 “N/C” auxiliary contact. LC1 F185: 3 poles. To add auxiliary contacts or other accessories, please consult our specialist catalogue “Motor-starter solutions. Control and protection components”. (4) Replace pp with the control circuit voltage reference indicated in the table below. Volts a 24 48 110 220 230 240 LC1 D09…D115 50 Hz B5 E5 F5 M5 P5 U5 60 Hz B6 E6 F6 M6 – U6 50/60 Hz B7 E7 F7 M7 P7 U7 LC1 F185 50 Hz (LX1 coil) B5 E5 F5 M5 P5 U5 60 Hz (LX1 coil) – E6 F6 M6 – U6 40…400 Hz (LX9 coil) – E7 F7 M7 P7 U7 For other voltages available between 24 V and 660 V, or a DC control circuit, please consult your Regional Sales Office.

132 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 135

Variable speed drives for asynchronous motors

Combinations for customer assembly (continued)

0

0

Altivar 61 Motor starters: supply voltage 380…415 V

DF534573

Motor starters for UL Type 12/IP 54 drives Motor Power (1) kW

Drive

Circuit-breaker

Reference

Reference (2)

HP

Rating Im A A

Line contactor Reference (3) (4)

3-phase supply voltage: 380…415 V 50/60 Hz Type 1 coordination

DF534635

DF534574

0.75

NS160pMA150 + LC1 D115pp + ATV 61WD75N4

1

ATV 61W075N4 GV2 LE07 2.5 – LC1 K06pp ATV 61W075N4C 1.5 2 ATV 61WU15N4 GV2 LE08 4 – LC1 K06pp ATV 61WU15N4C 2.2 3 ATV 61WU22N4 GV2 LE10 6.3 – LC1 K06pp ATV 61WU22N4C 3 – ATV 61WU30N4 GV2 LE14 10 – LC1 K06pp ATV 61WU30N4C 4 5 ATV 61WU40N4 GV2 LE14 10 – LC1 K06pp ATV 61WU40N4C 5.5 7.5 ATV 61WU55N4 GV2 LE16 14 – LC1 K06pp ATV 61WU55N4C 7.5 10 ATV 61WU75N4 GV2 LE20 18 – LC1 K06pp ATV 61WU75N4C 11 15 ATV 61WD11N4 GV2 LE22 25 – LC1 D09pp ATV 61WD11N4C 15 20 ATV 61WD15N4 GV2 LE32 32 – LC1 D18pp ATV 61WD15N4C 18.5 25 ATV 61WD18N4 NS80HMA50 50 300 LC1 D25pp ATV 61WD18N4C 22 30 ATV 61WD22N4 NS80HMA50 50 300 LC1 D32pp ATV 61WD22N4C 30 40 ATV 61WD30N4 NS80HMA80 80 480 LC1 D40pp ATV 61WD30N4C 37 50 ATV 61WD37N4 NS80HMA80 80 480 LC1 D50pp ATV 61WD37N4C 45 60 ATV 61WD45N4 NS100pMA100 100 600 LC1 D80pp ATV 61WD45N4C 55 75 ATV 61WD55N4 NS160pMA150 150 1350 LC1 D80pp ATV 61WD55N4C 75 100 ATV 61WD75N4 NS160pMA150 150 1350 LC1 D115pp ATV 61WD75N4C 90 125 ATV 61WD90N4 NS250pMA220 220 1980 LC1 D115pp ATV 61WD90N4C (1) Standard power ratings for 4-pole motors 400 V 50/60 Hz. The values expressed in HP comply with the NEC (National Electrical Code). (2) NS80HMApp, NSpppp: products sold under the Merlin Gerin brand. For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance (N, H, L). Breaking capacity of circuit-breakers according to standard IEC 60947-2: Circuit-breaker Icu (kA) for 400 V N H L GV2 LE07…LE14 100 – – – GV2 LE16…LE22 15 – – – GV2 LE32 10 NS80HMA 70 – – – NS100pMA – 25 70 150 NS160pMA, NS250pMA – 36 70 150 (3) Composition of contactors: LC1 K06: 3 poles + 1 “N/O” auxiliary contact and 1 “N/C” auxiliary contact. LC1 D09 to LC1 D115: 3 poles + 1 “N/O” auxiliary contact and 1 “N/C” auxiliary contact. Replace pp with the control circuit voltage reference indicated in the table below. Volts a 24 48 110 220 230 240 LC1 K06 50/60 Hz B7 E7 F7 M7 P7 U7 LC1 D09…D115 50 Hz B5 E5 F5 M5 P5 U5 60 Hz B6 E6 F6 M6 – U6 50/60 Hz B7 E7 F7 M7 P7 U7 For other voltages available between 24 V and 660 V, or a DC control circuit, please consult your Regional Sales Office.

133 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 136

Variable speed drives for asynchronous motors

Combinations for customer assembly (continued)

0

0

Altivar 61 Motor starters: supply voltage 440…480 V

DF534573

Motor starters for UL Type 1/IP 20 drives Motor Power (1) kW

Drive

Circuit-breaker

Reference

Reference (2)

HP

Rating Im A A

Line contactor Reference (3) (4)

DF534637

DF534574

3-phase supply voltage: 440…480 V 50/60 Hz. Type 2 coordination

NS160pMA150 + LC1 D115pp + ATV 61HD75N4

0.75 1.5 2.2 3 4 5.5 7.5 11

1 2 3 – 5 7.5 10 15

ATV 61H075N4 ATV 61HU15N4 ATV 61HU22N4 ATV 61HU30N4 ATV 61HU40N4 ATV 61HU55N4 ATV 61HU75N4 ATV 61HD11N4 ATV 61HD15N4 ATV 61HD18N4 ATV 61HD22N4 ATV 61HD30N4 ATV 61HD37N4 ATV 61HD45N4 ATV 61HD55N4 ATV 61HD75N4 ATV 61HD90N4 ATV 61HC11N4 ATV 61HC13N4 ATV 61HC16N4 ATV 61HC22N4 ATV 61HC22N4 ATV 61HC25N4 ATV 61HC31N4 ATV 61HC31N4 ATV 61HC40N4 ATV 61HC40N4

GV2 L08 GV2 L10 GV2 L14 GV2 L14 GV2 L16 GV2 L20 GV2 L22 GV2 L32 NS80HMA50 NS80HMA50 NS80HMA50 NS80HMA50 NS80HMA80 NS80HMA80 NS100HMA100 NS100HMA100 NS160pMA150 NS160pMA150 NS250pMA220 NS250pMA220 NS400pMA320 NS630pMA500 NS630pMA500 NS630pMA500 NS630pMA500 NS800L Micrologic 2 or 5 (LR OFF) NS800L Micrologic 2 or 5 (LR OFF) NS800L Micrologic 2 or 5 (LR OFF)

4 6.3 10 10 14 18 25 32 50 50 50 50 80 80 100 100 150 150 220 220 320 500 500 500 500 800 800 800

– – – – – – – – 300 300 300 300 480 480 600 600 1350 1350 1980 1980 1920 3000 3000 3000 3000 1600 1600 1600

LC1 D09pp LC1 D09pp LC1 D09pp LC1 D09pp LC1 D18pp LC1 D18pp LC1 D25pp LC1 D32pp LC1 D40pp LC1 D40pp LC1 D40pp LC1 D50pp LC1 D65pp LC1 D80pp LC1 D115pp LC1 D115pp LC1 D115pp LC1 D115pp LC1 F185pp LC1 F265pp LC1 F330pp LC1 F330pp LC1 F400pp LC1 F500pp LC1 F500pp LC1 F630pp LC1 F630pp LC1 F630pp

15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 250 280 315 355 400

20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450 500 – 600

500

700

ATV 61HC50N4

NS1000L Micrologic 2 or 5 (LR OFF) 1000

2000

LC1 F630pp

560 800 ATV 61HC63N4 NS1000L Micrologic 2 or 5 (LR OFF) 1000 2000 LC1 F630pp 630 900 ATV 61HC63N4 NS1000L Micrologic 2 or 5 (LR OFF) 1000 2000 LC1 F630pp (1) Standard power ratings for 4-pole motors 400 V 50/60 Hz. The values expressed in HP comply with the NEC (National Electrical Code). (2) NS80HMApp, NSpppp: products sold under the Merlin Gerin brand. For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance (N, H, L). Breaking capacity of circuit-breakers according to standard IEC 60947-2: Circuit-breaker Icu (kA) for 440 V N H L GV2 L08, GV2 L10 100 – – – GV2 L14…L32 20 – – – NS80HMA 65 – – – NS100pMA – 25 65 130 NS160pMA, NS250pMA – 35 65 130 NS400pMA, NS600pMA – 42 65 130 NS800L Micrologic 2 or 5, – – – 130 NS1000L Micrologic 2 or 5 (3) Composition of contactors: LC1 D09 to LC1 D115: 3 poles + 1 “N/O” auxiliary contact and 1 “N/C” auxiliary contact. LC1 Fppp: 3 poles. To add auxiliary contacts or other accessories, please consult our specialist catalogue “Motor-starter solutions. Control and protection components”. (4) Replace pp with the control circuit voltage reference indicated in the table below. Volts a 24 48 110 220 230 240 LC1 D09…D115 50 Hz B5 E5 F5 M5 P5 U5 60 Hz B6 E6 F6 M6 – U6 50/60 Hz B7 E7 F7 M7 P7 U7 LC1 F185 50 Hz (LX1 coil) B5 E5 F5 M5 P5 U5 60 Hz (LX1 coil) – E6 F6 M6 – U6 40…400 Hz (LX9 coil) – E7 F7 M7 P7 U7 LC1 F265, LC1 F330 40…400 Hz (LX1 coil) B7 E7 F7 M7 P7 U7 LC1 F400…F630 40…400 Hz (LX1 coil) – E7 F7 M7 P7 U7 For other voltages available between 24 V and 660 V, or a DC control circuit, please consult your Regional Sales Office.

134 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 137

Variable speed drives for asynchronous motors

Combinations for customer assembly (continued)

0

0

Altivar 61 Motor starters: supply voltage 440…480 V

DF534573

Motor starters for UL Type 1/IP 20 drives Motor Power (1) kW

Drive

Circuit-breaker

Reference

Reference (2)

HP

Rating Im A A

Line contactor Reference (3) (4)

DF534637

DF534574

3-phase supply voltage: 440…480 V 50/60 Hz. Type 1 coordination

NS160pMA150 + LC1 D115pp + ATV 61HD75N4

0.75 1 ATV 61H075N4 GV2 LE08 4 – LC1 K06pp 1.5 2 ATV 61HU15N4 GV2 LE10 6.3 – LC1 K06pp 2.2 3 ATV 61HU22N4 GV2 LE14 10 – LC1 K06pp 3 – ATV 61HU30N4 GV2 LE14 10 – LC1 K06pp 4 5 ATV 61HU40N4 GV2 LE16 14 – LC1 D09pp 5.5 7.5 ATV 61HU55N4 GV2 LE20 18 – LC1 D09pp 7.5 10 ATV 61HU75N4 GV2 LE22 25 – LC1 D18pp 11 15 ATV 61HD11N4 GV2 LE32 32 – LC1 D25pp 15 20 ATV 61HD15N4 NS80HMA50 50 300 LC1 D40pp 18.5 25 ATV 61HD18N4 NS80HMA50 50 300 LC1 D40pp 22 30 ATV 61HD22N4 NS80HMA50 50 300 LC1 D40pp 30 40 ATV 61HD30N4 NS80HMA80 80 300 LC1 D50pp 37 50 ATV 61HD37N4 NS80HMA80 80 300 LC1 D65pp 45 60 ATV 61HD45N4 NS100HMA100 100 600 LC1 D80pp 55 75 ATV 61HD55N4 NS100HMA100 100 600 LC1 D80pp 75 100 ATV 61HD75N4 NS160pMA150 150 1350 LC1 D115pp 90 125 ATV 61HD90N4 NS160pMA150 150 1350 LC1 D115pp 110 150 ATV 61HC11N4 NS250pMA220 220 1980 LC1 D115pp 132 200 ATV 61HC13N4 NS250pMA220 220 1980 LC1 F265pp 160 250 ATV 61HC16N4 NS400pMA320 320 1920 LC1 F330pp 200 300 ATV 61HC22N4 NS630pMA500 500 3000 LC1 F330pp 220 350 ATV 61HC22N4 NS630pMA500 500 3000 LC1 F400pp 250 400 ATV 61HC25N4 NS630pMA500 500 3000 LC1 F500pp 280 450 ATV 61HC31N4 NS630pMA500 500 3000 LC1 F500pp 315 500 ATV 61HC31N4 NS800 Micrologic 2 or 5 (LR OFF) 800 1600 LC1 F630pp 355 – ATV 61HC40N4 NS800 Micrologic 2 or 5 (LR OFF) 800 1600 LC1 F630pp 400 600 ATV 61HC40N4 NS800 Micrologic 2 or 5 (LR OFF) 800 1600 LC1 F630pp 500 700 ATV 61HC50N4 NS800 Micrologic 2 or 5 (LR OFF) 800 1600 LC1 F630pp 560 800 ATV 61HC63N4 NS1000 Micrologic 2 or 5 (LR OFF) 1000 2000 LC1 F630pp 630 900 ATV 61HC63N4 NS1000 Micrologic 2 or 5 (LR OFF) 1000 2000 LC1 F630pp (1) Standard power ratings for 4-pole motors 400 V 50/60 Hz. The values expressed in HP comply with the NEC (National Electrical Code). (2) NS80HMApp, NSpppp: products sold under the Merlin Gerin brand. For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance (N, H, L). Breaking capacity of circuit-breakers according to standard IEC 60947-2: Circuit-breaker Icu (kA) for 440 V N H L GV2 LE08 100 – – – GV2 LE10 50 – – – GV2 LE14 15 – – – GV2 LE16, GV2 LE20 8 – – – GV2 LE22, GV2 LE32 6 – – – NS80HMA 65 – – – NS100pMA – 25 65 130 NS160pMA, NS250pMA – 35 65 130 NS400pMA, NS600pMA – 42 65 130 NS800 Micrologic 2 or 5, – 50 65 – NS1000 Micrologic 2 or 5 (3) Composition of contactors: LC1 K06, LC1 D09 to LC1 D115: 3 poles + 1 “N/O” auxiliary contact and 1 “N/C” auxiliary contact. LC1 Fppp: 3 poles. To add auxiliary contacts or other accessories, please consult our specialist catalogue “Motor-starter solutions. Control and protection components”. (4) Replace pp with the control circuit voltage reference indicated in the table below. Volts a 24 48 110 220 230 240 LC1 K06 50/60 Hz B7 E7 F7 M7 P7 U7 LC1 D09…D115 50 Hz B5 E5 F5 M5 P5 U5 60 Hz B6 E6 F6 M6 – U6 50/60 Hz B7 E7 F7 M7 P7 U7 LC1 F265, LC1 F330 40…400 Hz (LX1 coil) B7 E7 F7 M7 P7 U7 LC1 F400…F630 40…400 Hz (LX1 coil) – E7 F7 M7 P7 U7 For other voltages available between 24 V and 660 V, or a DC control circuit, please consult your Regional Sales Office.

135 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 138

Variable speed drives for asynchronous motors

Combinations for customer assembly (continued)

0

0

Altivar 61 Motor starters: supply voltage 440…480 V

DF534573

Motor starters for UL Type 12/IP 54 drives Motor Power (1) kW

Drive

Circuit-breaker

Reference

Reference (2)

HP

Rating Im A A

Line contactor Reference (3) (4)

3-phase supply voltage: 440…480 V 50/60 Hz. Type 2 coordination

DF534635

DF534574

0.75

NS100pMA100 + LC1 D115pp + ATV 61WD55N4

1

ATV 61W075N4 GV2 L07 2.5 – LC1 D09pp ATV 61W075N4C 1.5 2 ATV 61WU15N4 GV2 L08 4 – LC1 D09pp ATV 61WU15N4C 2.2 3 ATV 61WU22N4 GV2 L10 6.3 – LC1 D09pp ATV 61WU22N4C 3 – ATV 61WU30N4 GV2 L10 6.3 – LC1 D09pp ATV 61WU30N4C 4 5 ATV 61WU40N4 GV2 L14 10 – LC1 D09pp ATV 61WU40N4C 5.5 7.5 ATV 61WU55N4 GV2 L14 10 – LC1 D18pp ATV 61WU55N4C 7.5 10 ATV 61WU75N4 GV2 L20 18 – LC1 D18pp ATV 61WU75N4C 11 15 ATV 61WD11N4 GV2 L22 25 – LC1 D25pp ATV 61WD11N4C 15 20 ATV 61WD15N4 GV2 L32 32 – LC1 D40pp ATV 61WD15N4C 18.5 25 ATV 61WD18N4 NS80HMA50 50 300 LC1 D40pp ATV 61WD18N4C 22 30 ATV 61WD22N4 NS80HMA50 50 300 LC1 D40pp ATV 61WD22N4C 30 40 ATV 61WD30N4 NS80HMA50 50 300 LC1 D50pp ATV 61WD30N4C 37 50 ATV 61WD37N4 NS80HMA80 80 480 LC1 D80pp ATV 61WD37N4C 45 60 ATV 61WD45N4 NS80HMA80 80 480 LC1 D80pp ATV 61WD45N4C 55 75 ATV 61WD55N4 NS100pMA100 100 600 LC1 D115pp ATV 61WD55N4C 75 100 ATV 61WD75N4 NS160pMA150 150 1350 LC1 D115pp ATV 61WD75N4C 90 125 ATV 61WD90N4 NS250pMA220 220 1980 LC1 F185pp ATV 61WD90N4C (1) Standard power ratings for 4-pole motors 400 V 50/60 Hz. The values expressed in HP comply with the NEC (National Electrical Code). (2) NS80HMApp, NSpppp: products sold under the Merlin Gerin brand. For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance (N, H, L). Breaking capacity of circuit-breakers according to standard IEC 60947-2: Circuit-breaker Icu (kA) for 440 V N H L GV2 L07…GV2 L10 100 – – – GV2 L14…L32 20 – – – NS80HMA 65 – – – NS100pMA – 25 65 130 NS160pMA, NS250pMA – 35 65 130 (3) Composition of contactors: LC1 D09 to LC1 D115: 3 poles + 1 “N/O” auxiliary contact and 1 “N/C” auxiliary contact. LC1 F185: 3 poles. To add auxiliary contacts or other accessories, please consult our specialist catalogue “Motor-starter solutions. Control and protection components”. (4) Replace pp with the control circuit voltage reference indicated in the table below. Volts a 24 48 110 220 230 240 LC1 D09…D115 50 Hz B5 E5 F5 M5 P5 U5 60 Hz B6 E6 F6 M6 – U6 50/60 Hz B7 E7 F7 M7 P7 U7 LC1 F185 50 Hz (LX1 coil) B5 E5 F5 M5 P5 U5 60 Hz (LX1 coil) – E6 F6 M6 – U6 40…400 Hz (LX9 coil) – E7 F7 M7 P7 U7 For other voltages available between 24 V and 660 V, or a DC control circuit, please consult your Regional Sales Office.

136 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 139

Combinations for customer Variable speed drives for assembly (continued) asynchronous motors 0

0

Altivar 61 Motor starters: supply voltage 440…480 V

DF534573

Motor starters for UL Type 12/IP 54 drives Motor Power (1) kW

Drive

Circuit-breaker

Reference

Reference (2)

HP

Rating Im A A

Line contactor Reference (3) (4)

3-phase supply voltage: 440…480 V 50/60 Hz. Type 1 coordination

DF534635

DF534632

0.75

NS100pMA100 + LC1 D80pp + ATV 61WD55N4

1

ATV 61W075N4 GV2 LE07 2.5 – LC1 K06pp ATV 61W075N4C 1.5 2 ATV 61WU15N4 GV2 LE08 4 – LC1 K06pp ATV 61WU15N4C 2.2 3 ATV 61WU22N4 GV2 LE10 6.3 – LC1 K06pp ATV 61WU22N4C 3 – ATV 61WU30N4 GV2 LE10 6.3 – LC1 K06pp ATV 61WU30N4C 4 5 ATV 61WU40N4 GV2 LE14 10 – LC1 K06pp ATV 61WU40N4C 5.5 7.5 ATV 61WU55N4 GV2 LE14 10 – LC1 K06pp ATV 61WU55N4C 7.5 10 ATV 61WU75N4 GV2 LE20 18 – LC1 D09pp ATV 61WU75N4C 11 15 ATV 61WD11N4 GV2 LE22 25 – LC1 D09pp ATV 61WD11N4C 15 20 ATV 61WD15N4 GV2 LE32 32 – LC1 D18pp ATV 61WD15N4C 18.5 25 ATV 61WD18N4 NS80HMA50 50 300 LC1 D32pp ATV 61WD18N4C 22 30 ATV 61WD22N4 NS80HMA50 50 300 LC1 D32pp ATV 61WD22N4C 30 40 ATV 61WD30N4 NS80HMA50 50 300 LC1 D40pp ATV 61WD30N4C 37 50 ATV 61WD37N4 NS80HMA80 80 480 LC1 D50pp ATV 61WD37N4C 45 60 ATV 61WD45N4 NS80HMA80 80 480 LC1 D65pp ATV 61WD45N4C 55 75 ATV 61WD55N4 NS100pMA100 100 600 LC1 D80pp ATV 61WD55N4C 75 100 ATV 61WD75N4 NS160pMA150 150 1350 LC1 D115pp ATV 61WD75N4C 90 125 ATV 61WD90N4 NS250pMA220 220 1980 LC1 D115pp ATV 61WD90N4C (1) Standard power ratings for 4-pole motors 400 V 50/60 Hz. The values expressed in HP comply with the NEC (National Electrical Code). (2) NS80HMApp, NSpppp: products sold under the Merlin Gerin brand. For references to be completed, replace the dot with the letter corresponding to the circuit-breaker breaking performance (N, H, L). Breaking capacity of circuit-breakers according to standard IEC 60947-2: Circuit-breaker Icu (kA) for 440 V N H L GV2 LE07…LE10 100 – – – GV2 LE14…LE32 20 – – – NS80HMA 65 – – – NS100pMA – 25 65 130 NS160pMA, NS250pMA – 35 65 130 (3) Composition of contactors: LC1 K06, LC1 D09 to LC1 D115: 3 poles + 1 “N/O” auxiliary contact and 1 “N/C” auxiliary contact. (4) Replace pp with the control circuit voltage reference indicated in the table below. Volts a 24 48 110 220 230 240 LC1 D09…D115 50 Hz B5 E5 F5 M5 P5 U5 60 Hz B6 E6 F6 M6 – U6 50/60 Hz B7 E7 F7 M7 P7 U7 For other voltages available between 24 V and 660 V, or a DC control circuit, please consult your Regional Sales Office.

137 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com