Variable speed drives Altivar 61 Catalogue: Mounting and installation recommendations
Pages 140 to 149 of 211, from Variable speed drives Altivar 61 Catalogue
The original document is the PDF (4.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Telemecanique Altivar 61 ATV61, Schneider Altivar 61 ATV61 and Square D Altivar 61 ATV61
Page 140
Mounting and installation recommendations
0
Variable speed drives for asynchronous motors
0
Altivar 61 UL Type 1/IP 20 drives
Mounting recommendations Depending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate accessories. Install the unit vertically: b Do not place it close to heating elements. b Leave sufficient free space to ensure that the air required for cooling purposes can circulate from the bottom to the top of the unit.
u 100
ATV 61HpppM3, ATV 61HD11M3X…HD45M3X, ATV 61H075N4…HD75N4
522085 u 100
10
Mounting types b Type A mounting
50
50
Removing the protective blanking cover for: ATV 61Hppp M3, ATV 61HD11M3X, HD15M3X, ATV 61HD075N4…HD18N4
564510 b Type B mounting b Type C mounting Removing the protective blanking cover for: ATV 61HD18M3X…HD45M3X, ATV 61HD22N4…HD75N4 u 50 u 50
By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP 20. The protective blanking cover may vary according to the drive model, see opposite.
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
138 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 141
Mounting and installation Variable speed drives recommendations (continued) for asynchronous motors 0
0
Altivar 61 UL Type 1/IP 20 drives
Mounting recommendations (continued) Derating curves The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type. For intermediate temperatures (55°C for example) interpolate between 2 curves. ATV 61HpppM3, ATV 61HD11M3X, HD15M3X and ATV 61H075N4…HD18N4 I/In % In = 100 40oC mounting types B and C
90 80
40oC mounting type A 50oC mounting types B and C
70
50oC mounting type A
60
60oC mounting types A, B and C
50
0
4
8
12 16 kHz Switching frequency
ATV 61HD22N4 and ATV 61HD30N4 (1) I/In % In = 100
90
40oC mounting types A, B and C
80 50oC mounting types A, B and C
70 60 50
60oC mounting types A, B and C
0
4
8
12 16 kHz Switching frequency
ATV 61HD18M3X…HD45M3X and ATV 61HD37N4…HD75N4 (1) I/In % In = 100 40 oC mounting types A, B and C
90 80
50 oC mounting types A, B and C
70 60
60 oC mounting types A, B and C
50
0
2,5
4
8
12 16 kHz Switching frequency
(1) Above 50°C, ATV 61HD18M3X…HD45M3X, ATV 61HD22N4…HD75N4 drives should be equipped with a control card fan kit. See page 22.
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
139 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 142
Mounting and installation Variable speed drives recommendations (continued) for asynchronous motors 0
0
Altivar 61 UL Type 1/IP 20 drives
Mounting recommendations (continued)
X2
ATV 61HD55M3X…HD90M3X, ATV 61HD90N4…HC63N4
X1
1000
ATV 61H D55M3X…D90M3X, D90N4, C11N4 C13N4…C22N4 C25N4, C31N4 C40N4, C50N4 C63N4
X1 100
X2 100
150 150 250 250
150 200 300 400
250
These drives can be mounted side by side, observing the following mounting recommendations:
250
1000
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
140 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 143
Mounting and installation Variable speed drives recommendations (continued) for asynchronous motors 0
0
Altivar 61 UL Type 1/IP 20 drives
Mounting recommendations (continued) Derating curves The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type. For intermediate temperatures (55°C for example), interpolate between 2 curves. ATV 61HD55M3X
ATV 61HD75M3X
I/In % 120
I/In % 120
110
110
In = 100
In = 100
90
90
80
80
70
70 60
60 40 ˚C 50 50 ˚C
40
40 ˚C 50 50 ˚C
40
60 ˚C
60 ˚C 30
30 2
2,5 3
4
5
2
6 7 8 kHz Switching frequency
ATV 61HD90M3X
2,5 3
4
5
6 7 8 kHz Switching frequency
ATV 61HD90N4
I/In % 120
I/In % 120
110
110
In = 100
In = 100
90
90
80
80
70
70 67 60
60
40 ˚C
50 ˚C
40 ˚C 50
50 50 ˚C
40
40
60 ˚C
60 ˚C 30
30 2
2,5 3
4
5
6 7 8 kHz Switching frequency
ATV 61HC11N4
2
2,5 3
4
5
6 7 8 kHz Switching frequency
ATV 61HC13N4
I/In % 120
I/In % 120
110 106 In = 100
110 104 In = 100
90 88
91 80
80 40 ˚C
70
40 ˚C
71 50 ˚C
60
61 50 ˚C
50
50
60 ˚C 40
40 60 ˚C
30
30 2
2,5 3
Presentation: pages 4 to 7
4
5
6 7 8 kHz Switching frequency
Characteristics: pages 8 to 15
2
2,5 3
References: pages 18 to 21
4
5
6 7 8 kHz Switching frequency
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
141 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 144
Mounting and installation Variable speed drives recommendations (continued) for asynchronous motors 0
0
Altivar 61 UL Type 1/IP 20 drives
Derating curves (continued) ATV 61HC16N4
ATV 61HC22N4 combined with a 200 kW motor
I/In % 120
I/In % 120
110 104 In = 100
110 105 In = 100
92
90 80
80 75 70
40 ˚C
60
50 ˚C
40 ˚C
70 67 60
50 ˚C 50
60 ˚C
50
40
40
30
30 2
2,5 3
4
5
2
6 7 8 kHz Switching frequency
ATV 61HC22N4 combined with a 220 kW motor
60 ˚C
2,5 3
4
5
6 7 8 kHz Switching frequency
ATV 61HC25N4
I/In % 120
I/In % 120
110 105 In = 100
110 105 In = 100
91
90
80
80
72
40 ˚C
60
50 ˚C
40 ˚C 69
50
60
50 ˚C
50 60 ˚C
40 30
60 ˚C
40 30
2
2,5 3
4
5
6 7 8 kHz Switching frequency
ATV 61HC31N4 combined with a 280 kW motor
2
I/In % 120
110 105 In = 100
110 104 In = 100
91
92
80 40 ˚C
60
4
5
6 7 8 kHz Switching frequency
ATV 61HC31N4 combined with a 315 kW motor
I/In % 120
71
2,5 3
50 ˚C
50
80 76 70
40 ˚C
60
50 ˚C
50 60 ˚C
40 30
60 ˚C
40 30
2
2,5 3
Presentation: pages 4 to 7
4
5
6 7 8 kHz Switching frequency
Characteristics: pages 8 to 15
2
2,5 3
References: pages 18 to 21
4
5
6 7 8 kHz Switching frequency
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
142 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 145
Mounting and installation Variable speed drives recommendations (continued) for asynchronous motors 0
0
Altivar 61 UL Type 1/IP 20 drives
Derating curves (continued) ATV 61HC40N4 combined with a 355 kW motor
ATV 61HC40N4 combined with a 400 kW motor
I/In % 120
I/In % 120
110 106 In = 100
110 105 In = 100
90 88
90 80
80 40 ˚C
70 62
40 ˚C
69 60
50 ˚C
50
50 ˚C
50 40
40
60 ˚C
60 ˚C 30
30 2
2,5 3
4
5
2
6 7 8 kHz Switching frequency
ATV 61HC50N4
2,5 3
4
5
6 7 8 kHz Switching frequency
ATV 61HC63N4 combined with a 560 kW motor
I/In % 120
I/In % 120
110 104 In = 100
110 105 In = 100
93
92 80
78 70
40 ˚C
73 70
60
50 ˚C
60
50
60 ˚C
50
40
40 ˚C 50 ˚C 60 ˚C
40
30
30 2
2,5 3
4
5
6 7 8 kHz Switching frequency
2
2,5 3
4
5
6 7 8 kHz Switching frequency
ATV 61HC63N4 combined with a 630 kW motor I/In % 120
110 104 In = 100 93 80 77
40 ˚C
70 60
50 ˚C
50
60 ˚C
40 30 2
2,5 3
Presentation: pages 4 to 7
4
5
6 7 8 kHz Switching frequency
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
143 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 146
Mounting and installation Variable speed drives recommendations (continued) for asynchronous motors 0
0
Altivar 61 UL Type 12/IP 54 drives
Mounting recommendations (continued) Depending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate accessories. Install the unit vertically: b Do not place it close to heating elements. b Leave sufficient free space to ensure that the air required for cooling purposes can circulate from the bottom to the top of the unit.
u 100
ATV 61WpppN4, ATV 61WpppN4C
50 u 100
50
Derating curves ATV 61W075N4…WU55N4, ATV 61W075N4C…WU55N4C
ATV 61WU75N4, WD11N4, ATV 61WU75N4C, WD11N4C
I/In % In = 100
I/In % In = 100 40°C
90
90
80
80
70
70
60
60
50
50
0
Presentation: pages 4 to 7
2
4
8
16 kHz 12 Switching frequency
Characteristics: pages 8 to 15
40°C
0
2
References: pages 18 to 21
4
8
16 kHz 12 Switching frequency
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
144 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 147
Mounting and installation Variable speed drives recommendations (continued) for asynchronous motors 0
0
Altivar 61 UL Type 12/IP 54 drives
Derating curves (continued) ATV 61WD15N4, ATV 61WD15N4C
ATV 61WD18N4, WD22N4, ATV 61WD18N4C, WD22N4C
I/In % In = 100
I/In % In = 100
90
90
80
40°C
80
70
70
60
60
50
50
0
2
4
8
16 kHz 12 Switching frequency
40°C
0
2
4
8
16 kHz 12 Switching frequency
ATV 61WD30N4, ATV 61WD30N4C
ATV 61WD37N4, WD45N4, ATV 61WD37N4C, WD45N4C
I/In % In = 100
I/In % In = 100
90
90
80
80
40°C 40°C
70
70
60
60
50
50
0
2
4
8
12 16 kHz Switching frequency
0
2
4
8
12 16 kHz Switching frequency
ATV 61WD55N4…WD90N4, ATV 61WD55NC4…WD90N4C I/In % In = 100
90 80 40°C
70 60 50
0
Presentation: pages 4 to 7
2
4
8
12 16 kHz Switching frequency
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
145 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 148
Mounting and installation Variable speed drives recommendations (continued) for asynchronous motors 0
0
Altivar 61 UL Type 1/IP 20 drives
Specific recommendations for mounting in an enclosure (1) Follow the mounting recommendations described on pages 138 to 143. To ensure proper air circulation in the drive: b Fit ventilation grilles. b Ensure that there is sufficient ventilation. If there is not, install forced ventilation with a filter. The openings and/or fans must provide a flow rate at least equal to that of the drive fans (see page 147) b Use special filters with IP 54 protection. b Remove the blanking cover from the top of the drive, see page 138. Power dissipated inside the enclosure (1) For drives
Dissipated power (2) Mounted in the enclosure (power section inside the enclosure) W
Dust and damp proof flushmounting (power section outside the enclosure) W
3-phase supply voltage: 200…240 V 50/60 Hz ATV 61H075M3 ATV 61HU15M3 ATV 61HU22M3 ATV 61HU30M3 ATV 61HU40M3 ATV 61HU55M3 ATV 61HU75M3 ATV 61HD11M3X ATV 61HD15M3X ATV 61HD18M3X ATV 61HD22M3X ATV 61HD30M3X ATV 61HD37M3X ATV 61HD45M3X ATV 61HD55M3X ATV 61HD75M3X ATV 61HD90M3X
66 101 122 154 191 293 363 566 620 799 865 1134 1337 1567 1715 2233 2694
28 30 38 38 42 52 60 73 76 119 124 151 166 184 154 154 154
3-phase supply voltage: 380…480 V 50/60 Hz ATV 61H075N4 44 26 ATV 61HU15N4 64 28 ATV 61HU22N4 87 30 ATV 61HU30N4 114 35 ATV 61HU40N4 144 40 ATV 61HU55N4 178 50 ATV 61HU75N4 217 55 ATV 61HD11N4 320 65 ATV 61HD15N4 392 86 ATV 61HD18N4 486 86 ATV 61HD22N4 717 110 ATV 61HD30N4 976 135 ATV 61HD37N4 1174 137 ATV 61HD45N4 1360 165 ATV 61HD55N4 1559 178 ATV 61HD75N4 2326 225 ATV 61HD90N4 2403 237 ATV 61HC11N4 3056 269 ATV 61HC13N4 3583 304 ATV 61HC16N4 4036 362 ATV 61HC22N4 5482 452 ATV 61HC25N4 6379 606 ATV 61HC31N4 7867 769 ATV 61HC40N4 9598 – ATV 61HC50N4 12055 – ATV 61HC63N4 15007 – (1) Only for ATV 61HpppM3, ATV 61HpppM3X and ATV 61Hppp N4 drives. (2) This value is given for operation at nominal load and for a switching frequency of 2.5 or 4 kHz depending on the rating. Add 7 W to this value for each additional option card.
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
146 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 149
Mounting and installation Variable speed drives recommendations (continued) for asynchronous motors 0
0
Altivar 61 UL Type 1/IP 20 drives
Fan flow rate depending on the drive rating For drive
Flow rate m3/hour
ATV 61H075M3…HU15M3, ATV 61H075N4…HU22N4 ATV 61HU22M3…HU40M3, ATV 61HU30N4, HU40N4 ATV 61HU55M3, ATV 61HU55N4, HU75N4 ATV 61HU75M3, ATV 61HD11N4 ATV 61HD11M3X, HD15M3X ATV 61HD15N4, HD18N4 ATV 61HD18M3X, HD22M3X, ATV 61HD22N4…HD37N4 ATV 61HD30M3X…HD45M3X, ATV 61HD45N4…HD75N4 ATV 61HD55M3X, HD75M3X, ATV 61HD90N4, HC11N4 ATV 61HD90M3X, ATV 61HC13N4 ATV 61HC16N4
17
ATV 61HC22N4
860
ATV 61HC25N4, HC31N4
1260
ATV 61HC40N4, HC50N4
2100
ATV 61HC63N4
2400
56 112 163 252 203 406 402 774 745
Sealed metal enclosure (IP 54 degree of protection) The drive must be mounted in a dust and damp proof enclosure in certain environmental conditions: dust, corrosive gases, high humidity with risk of condensation and dripping water, splashing liquid, etc. This enables the drive to be used in an enclosure where the maximum internal temperature reaches 50°C.
Calculating the enclosure dimensions (1) Maximum thermal resistance Rth (°C/W) θ = maximum temperature inside enclosure in °C θ – θe θe = maximum external temperature in °C Rth = --------------P P = total power dissipated in the enclosure in W Power dissipated by drive: see page 146 (mounting in an enclosure or flushmounting in an enclosure). Add the power dissipated by the other equipment components. Useful heat dissipation surface of enclosure S (m2) (sides + top + front panel if wall-mounted) K S = --------Rth
K = enclosure thermal resistance per m2
For a metal enclosure: b K = 0.12 with internal fan b K = 0.15 without fan Note: Do not use insulated enclosures, as they have a poor level of conductivity. (1) Only for ATV 61H pppM3, ATV 61H pppM3X and ATV 61HpppN4 drives.
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
147 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com