Page 150
Functions
0
Variable speed drives for asynchronous motors
0
Altivar 61
Summary of functions Remote graphic display terminal functions Description Navigation Password page 150 page 151 page 151
Integrated 7-segment display terminal Presentation page 152
Start-up Simply Start menu Programming using macro-configurations MONITORING menu page 152 page 153 page 154
Configuration and settings Presentation page 154
Operation Presentation page 154
Maintenance, diagnostics Response to faults or alarms Fault history and help IDENTIFICATION menu Test functions Oscilloscope function page 155 page 155 page 155 page 155 page 155
Controlling the drive Via the drive I/O Via the remote graphic display terminal Via a communication network - I/O profile - CiA DSP 402 profile - ODVA profile page 156 page 156 page 157 page 157 page 157
Functions suitable for pumping and ventilation applications Motor control profiles - Energy saving ratio - Quadratic ratio (Kn 2) PID regulator - Internal references - Preset PID references - PID feedback - PI feedback supervision - Sleep/wake-up - Activate sleep mode by flow detection - Alarms - Predictive speed reference - Auto/Man. Forced operation Flow limit page 158 page 158 page 158 page 158 page 159 page 159 page 159 page 159 page 159 page 159 page 159 page 159 page 159
Other application functions 2-wire control - State detection - Transition detection - Forward operation as priority page 160 page 160 page 160 page 160 page 160
- Time - Profile (linear, S, U or customized) - Switching - Automatic adaptation page 160 page 161 page 161 page 161 page 162 page 162 page 162
3-wire control Phase rotation Ramps
Preset speeds JOG operation Limiting low speed operating time
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
148 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 151
Functions
0
Variable speed drives for asynchronous motors
0
Altivar 61
Summary of functions (continued) Other application functions (continued) Motor control types - Flux Vector Control with sensor (FVC) - Sensorless Flux Vector Control - 2-point Vector Control - Voltage/frequency ratio - Synchronous motor Limiting motor overvoltage Auto-tuning Switching frequency, noise reduction Motor fluxing Output contactor command Stop on thermal alarm Uncontrolled output cut +/- speed - Single action buttons - Double action buttons - Reference saving - Around a reference Automatic catching of a spinning load with speed detection Undervoltage management Braking balance Braking resistor thermal protection Parameter set switching Motor or configuration switching Reference switching Operations on the references - Summing inputs - Subtraction inputs - Multiplication inputs Torque limit Torque or current limit detection Current limit Reference saving Stop types - Freewheel stop - Fast stop - Fastest possible stop - DC injection stop Motor thermal protection Drive thermal protection IGBT thermal protection Machine protection Configuring the drive’s fault response Resetting resettable faults General reset (disables all faults) Automatic restart PTC probe protection IGBT testing Resetting operating time to zero External fault Line contactor control Forced local mode
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111 page 163 page 163 page 163 page 163 page 163 page 163 page 163 page 163 page 164 page 164 page 164 page 165 page 165 page 165 page 166 page 166 page 166 page 167 page 167 page 167 page 168 page 168 page 168 page 169 page 169 page 169 page 170 page 170 page 170 page 171 page 171 page 171 page 171 page 171 page 172 page 172 page 172 page 172 page 173 page 173 page 173 page 174 page 174 page 174 page 174 page 174 page 175 page 175
Schemes: pages 112 to 127
149 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 152
Functions (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61
Remote graphic display terminal functions DF534487
This display terminal is attached to the front of the drive. It includes the integrated 7-segment display terminal for drives supplied without a graphic display terminal. b Description v Description of graphic display terminal 1 Graphic display unit: - 8 lines, 240 x 160 pixels - large digit display that can be read from 5 m away - bar chart display 2 Assignable functions keys F1, F2, F3, F4: - dialogue functions: direct access, help screens, navigation - application functions: Local/Remote, preset speed. 3 STOP/RESET key: local control of motor stopping/fault clearing 4 RUN key: local control of motor operation 5 Navigation button: - Press to save the current value (ENT) - Turn ± to increase or decrease the value, or go to the next or previous line 6 FWD/REV key: reverses the direction of rotation of the motor 7 ESC key: aborts a value, parameter or menu to return to the previous option.
1
2 3
7
4
6
5
534786
Note: Keys 3, 4 and 6 can be used to control the drive directly.
RUN
1
Term
REM
+50.00Hz
6
1. DRIVE MENU
2
1.1 SIMPLY START 1.2 MONITORING 1.3 SETTINGS
3
1.4 MOTOR CONTROL 1.5 INPUTS / OUTPUTS CFG 4
Code
<<
F1
F2
Presentation: pages 4 to 7
>> F3
T/K F4
Characteristics: pages 8 to 15
5 v Description of graphic display unit 1 Display line. Its content can be configured; the factory settings show: - the drive status (example: RUN) - the active control channel (example: “Term”: Terminals), - the frequency reference - Type of control (example: “LOC/REM”). 2 Menu line. Indicates the current menu or submenu. 3 Area displaying menus, submenus, parameters, values, bar charts, in the form of a scrolling window, with a maximum of 5 lines. The line or value selected using the navigation button is displayed in reverse video (see opposite). 4 Section displaying the functions assigned to the keys F1 to F4 and aligned with them, for example: - >> : Horizontal scrolling to the right, or proceeding to the next menu or submenu, or, in the case of a value, decreasing the value, displayed in reverse video (see example opposite) - << : Horizontal scrolling to the left, or proceeding to the next menu or submenu, or, in the case of a value, increasing the value, displayed in reverse video - “T/K” : Local Remote function assigned to key F4, - HELP: Contextual help - Code: Displays the selected parameter code - Other functions (application functions) can be assigned to these keys via the 1.6 COMMAND menu. 5 : Means that this display window does not scroll further down. : Means that this display window can scroll further down. 6 : Means that this display window can scroll further up. : Means that this display window does not scroll further up.
References: pages 18 to 21
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
150 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 153
Functions (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61
Remote graphic display terminal functions (continued) 534884 b Navigation: accessing menus and parameters Structure of main menus: 1 Drive menu:
ATV71HU22N4
Menu type
Function
1.1 SIMPLY START 1.2 MONITORING
Simplified menu for fast startup Displays current values for motor, inputs/outputs and communication (command words, status words, etc.) Accesses the adjustment parameters, which can be modified during operation Accesses the motor parameters, including adjustment of motor control profiles Configures the I/O and transforms signals Configures the command and reference channels Configures the application functions (preset speeds, PID regulator, etc.) Configures the fault management process Configures the communication networks Provides diagnostics for motor and drive, integrated test procedures, fault history Identifies the drive and internal options Restores factory settings (completely or by parameter group) Accesses the parameters selected by the user Accesses the parameters for the multipump card or the Controller Inside programmable card
2.2kW/3HP 380/480V Config n˚1
1.3 SETTINGS 1.4 MOTOR CONTROL
RUN
Term
+50.00Hz
5.4A
1.5 INPUTS/OUTPUTS CFG 1.6 COMMAND 1.7 APPLICATION FUNCT.
1. DRIVE MENU
1.1 SIMPLY START 1.2 MONITORING
1
1.3 SETTINGS
1.8 FAULT MANAGEMENT 1.9 COMMUNICATION 1.10 DIAGNOSTICS
1.4 MOTOR CONTROL 1.5 INPUTS / OUTPUTS CFG
Code
RUN
<<
Term
>>
Quick
+43.33Hz 5.4A
2
1.11 IDENTIFICATION 1.12 FACTORY SETTINGS
Motor speed
1300 rpm Min=0
3
1.13 USER MENU 1.14 PROGRAMMABLE CARD
2 Display line
Max=1500 Quick
3 Display screen: Displays values in the form of bar charts or digital values, depending on the extent of customization. RUN
Term
+0.00Hz
4 Main menu:
0A
MAIN MENU 1. DRIVE MENU 2. LEVEL ACCESS
4
3. OPEN / SAVE AS
Menu type
Function
1. DRIVE MENU 2. ACCESS LEVEL 3. OPEN / SAVE AS
See above (1 Drive menu) 4 access levels: basic, limited, advanced, expert Transfers files between the graphic display terminal and the drive Provides password protection for the configuration Choice of 6 languages available (English, German, Spanish, French, Italian and Chinese) Customizes the display line 2 and the display screen 3 (bar charts, digital values) Configures how parameters are displayed: customization, selection for User menu, visibility, accessibility
4. PASSWORD 5. LANGUAGE
<<
4. PASSWORD >>
Quick
5. LANGUAGE 6. MONITORING CONFIG. 7. DISPLAY CONFIG.
b Password Altivar 61 drives allow individual parameters to be selected for password protection. Rights can be set for save operations and for loading the configuration.
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
151 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 154
Functions (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61
Integrated 7-segment display terminal ATV 61pppppM3, ATV 61HD11M3X…HD45M3X and ATV 61H075N4…HD75N4 drives can be supplied without a graphic display terminal. In this case, they are equipped with an integrated 7-segment display terminal. This can be used to: v Display status and faults v Access and modify parameters
Start-up
DF534783
The Altivar 61 drive is supplied ready for use for most applications. When the drive is switched on, the menus for setting the language and access level appear automatically. RUN
Term
+50.00Hz
5.4A
1.1 SIMPLY START 2/3 wire control
:
2 wire
Macro-configuration :
Pumps.Fans
Standard mot. Freq. :
50Hz IEC
Rated motor power :
2.2kW
Rated motor volt.
Code
:
<<
400V
>>
Quick b Simply Start menu By accessing the Simply Start menu directly, it is possible to: v Pre-program the drive for an application: - Select the relevant macro-configuration - 2-wire/3-wire control v Benefit from optimum motor performance: - Enter data from the motor rating plate - Auto-tuning. v Protect the motor by setting the drive’s integrated electronic thermal overload relay
Simply Start menu
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
152 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 155
Functions (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61
Start-up (continued) b Programming using macro-configurations Programming using macro-configurations offers the choice of five options corresponding to the various business areas and applications: v Start/stop v General use v PID regulation v Communication network connectivity v Ventilation pump. Choosing one of these macro-configurations automatically assigns the functions, parameters and I/O, even in the case of option cards. Although the configuration is preset, it can still be modified, if necessary. The Ventilation pump macro-configuration is set as the factory configuration. The preset functions for each macro-configuration are given in the table below. Type of macro-configuration
Start/stop
General use
PID regulation
Communication Ventilation pump. network connectivity
AI1
Ref. 1 channel
Ref. 1 channel
PID reference
AI2 AO1 2-wire
LI1 LI2 LI3
Not assigned Motor freq. Forward Fault reset Not assigned
Sum ref. 2 Motor freq. Forward Reverse JOG
LI4
Not assigned
Fault reset
Ref. 1B channel Motor freq. Forward Freewheel Ref. 1B switching Fault reset
LI5
Not assigned
Torque limit
Not assigned
Not assigned
LI6 LI1 LI2 LI3 LI4
Not assigned Stop Forward Reverse Not assigned
Not assigned Stop Forward Reverse JOG
LI5
Not assigned
Fault reset
Not assigned Stop Forward Reverse Ref. 2 switching Forced local
Not assigned Stop Forward Freewheel Ref. 1B switching Fault reset
LI6
Not assigned
Torque limit
Not assigned
Not assigned
Faulty Not assigned
Faulty Not assigned
PID feedback Motor freq. Forward Fault reset PID integral reset PID 2 preset ref. PID 4 preset ref. Not assigned Stop Forward Reverse PID integral reset PID 2 preset ref. PID 4 preset ref. Faulty Not assigned
Ref. 2 channel Ref. 1 channel by bus Not assigned Motor freq. Forward Fault reset Ref. 2 switching Fault reset
Faulty Not assigned
Faulty Drive operation
Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Motor current Not assigned
Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Motor current Not assigned
Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Motor current PID error
Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Motor current Not assigned
Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Motor current Not assigned
F1 key
Not assigned
Not assigned
Not assigned
Not assigned
F2, F3, F4 keys
Not assigned
Not assigned
Not assigned
Control via graphic display terminal Not assigned
Altivar 61 drive I/O
3-wire
R1 R2
Ref. 1 channel
I/O extension card I/O 2-wire LI7 3-wire LI7 LI8 to LI14 LO1 to LO4 R3/R4 AI3, AI4 RP AO2 AO3
Graphic display terminal keys
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
T/K (control via graphic display terminal)
Schemes: pages 112 to 127
153 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 156
Functions (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61
522169
Start-up (continued) b MONITORING menu The MONITORING menu can be used to display commands, the operation of the motor and application through the drive of its I/O or of the communication network connections. Term
RUN
+43.33Hz
5.4A
:
43.3 Hz
Motor current
:
5.4 A
Motor speed
:
1300 rpm
Motor thermal state :
80 %
Code
:
<<
80A
+50.00Hz
1 0 1 0
PR
LI7
LI1
LI8
LI2
LI9
LI3
LI4
LI5
LI6
LI10 LI11 LI12 LI13 LI14
<<
Displaying physical values
>>
5.4A
+50.00Hz
COMMUNICATION MAP
85 %
Quick
>>
Mod.
RUN
Logic input map
Frequency Ref.
Drv thermal state
Term
RUN
1.2 MONITORING
Cmd channel
:
Modbus
Cmd Value
:
ABCD Hex
Active ref. channel :
CANopen
Frequency ref.
:
+50.00 Hz
ETA status word
:
Quick
Code
Logic input map
<<
2153 Hex
Quick
>>
Communication map
One of the uses of this menu is to display the alarm groups, thermal states and electrical values such as: v electrical power consumed by the drive v the drive’s cumulative electrical power, etc.
Configuration and settings
522154
The SETTINGS menu can be used to configure all the drive’s settings. Activating a function automatically provides access to the related settings on the same screen (the application functions are described on pages 158 to 175). RUN
Term
+50.00Hz 1250A
RDY
Term
+0.00Hz
0.0A
0,01
2 preset speeds
:
LI3
:
3,00 s
4 preset speeds
:
LI4
Deceleration
:
3,00 s
8 preset speeds
:
LI5
Acceleration 2
:
5,00 s
Preset speed 2
:
10.0 Hz
Deceleration 2
:
5,00 s
Preset speed 3
:
Code
<<
>>
Code
Quick
Settings screen
<<
9.51 s
15.0 Hz
>>
0A
+0.00Hz
ACCELERATION
Acceleration
Ramp increment :
Term
RDY
PRESET SPEEDS
1.3 SETTINGS
Min=0,01
Max=9999
Quick
<<
Setting a function
>>
Quick
Configuring a value
Operation
533525
The display screen appears automatically every time the drive is turned on. There are different possible scenarios: b One or two bar charts are displayed. b One, two or five digital values are displayed. Term
RUN
+43.33Hz 5.4A
Motor speed
+38.0Hz
RUN
10A
Max=1500 Quick
<<
References: pages 18 to 21
>>
+43.33Hz
5.4A
Frequency Ref.
:
Motor current
:
5.4 A
Motor speed
:
1300 rpm
Motor thermal state :
80 %
Drv thermal state
1 digital value
Characteristics: pages 8 to 15
Term
1.2 MONITORING
+45.1 Hz
1 bar chart
Presentation: pages 4 to 7
Term
Output frequency
1300 rpm Min=0
DEC
Code
Quick
<<
43.3 Hz
:
85 %
>>
Quick
5 digital values
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
154 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 157
Functions (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61
533523
Maintenance, diagnostics Term
SCF1
+50.00Hz
0.0A
FAULT HISTORY Short circuit b Response to faults or alarms It is possible to use the alarm management or drive operation configuration functions to take corrective measures before stopping the machine.
Overcurrent External FLT Overvoltage Undervoltage
Help
Quick
522162
Fault history
SCF1
Term
New functions have been added to the Altivar 61 drive to enable it to provide quick and simple maintenance, ultimately boosting productivity:
+50.00Hz
0.0A
MOTOR SHORT CIRCUIT b Fault history and help When a fault occurs, a help screen is available to quickly identify the cause of the fault. As soon as the fault occurs, values such as speed, current, thermal state, timer are saved and restored in the fault history. The last 8 faults are stored.
Check the connection cables and the motor insulation. Perform the diagnostic test.
Quick
534639
Troubleshooting screen
Term
RUN
+50.00Hz
5.4A
1.11 IDENTIFICATION ATV61HU22N4 2.2 kW / 3HP 380 / 480 V b IDENTIFICATION menu The IDENTIFICATION menu can be used to display the relevant serial numbers and software versions, thereby helping to manage the equipment base. This information, also available from the PowerSuite software workshop, can be exported to other database-type software applications.
Appl. Software V1.0 IE 01 MC Software V1.0 IE 01
<<
>>
Quick
522157
Identification screen
RUN
Term
+50.00Hz
5.4A
SERVICE MESSAGE For technical support, dial 32 12 75
Quick Example of a customized message b Test functions The Altivar 61 drive includes the following test functions: v Identifying any motor short-circuit before start-up v Running, via the graphic display terminal or PowerSuite software workshop, automatic procedures during maintenance operations aimed at testing: - the motor - the drive power components The test results are shown on the graphic display terminal or using the PowerSuite software workshop. It is also possible to write and read messages in the drive using the graphic display terminal or the PowerSuite software workshop. b Oscilloscope function The Altivar 61 drive has an oscilloscope function, which produces traces that can be viewed using the PowerSuite software workshop. The PowerSuite software workshop can also be used to carry out remote diagnostics via modem.
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
155 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 158
Functions (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61
Controlling the drive b Via the drive I/O Control signals are transmitted via cable to the I/O. Functions are assigned to logic inputs, analog inputs, etc. A logic input can be assigned to more than one function. This means that two functions can be controlled using a single signal, thereby limiting the number of inputs required. The Altivar 61 drive I/O can be configured independently from each other. For instance, v A time delay can be applied when it comes to reading the logic inputs, so as to avoid any bounce-back from certain switches. v Transforming incoming signals on the analog inputs can help the drive fully adapt to the control devices and applications: - Minimum and maximum values for the input signal - Input filtering in order to eliminate unwanted interference from the signals received - Magnifying glass effect through delinearizing the input signal in order to increase the precision with small amplitude signals - “Pedestal” and “Deadband” functions for signals in order to prevent low speed operations which can have an adverse effect on the application - “Mid-point” function, which can be used from a unipolar input signal to obtain a bipolar output signal to control the speed and direction of rotation v Transforming analog outputs which transfer information sent by the drive to other devices (display units, drives, PLCs, etc.): - voltage or current output signal - minimum and maximum values for the output signal - output signal filtering Logic outputs can be delayed on activation and deactivation. The output state can also be configured when the signal is active. The frequency control signals are also transformed by the drive: v signal frequency minimum and maximum values (30 kHz on the extended I/O card’s RP input). b Via the remote graphic display terminal The rotation commands and references (speed or PID) can be controlled via the graphic display terminal. Some application functions can also be assigned to the function keys F1, F2, F3 and F4 on the graphic display terminal. It is possible to manage a change in command and/or reference source (bumpless function) in different ways. Example: two options are offered when switching control from via the terminals to via the graphic display terminal: v stop the Altivar 61 drive, or v continue operation with a copy of the direction of rotation and reference
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
156 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 159
Functions (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61
Controlling the drive (continued) b Via a communication network v I/O profile The I/O profile, which is easy and quick to use, can be used to control the Altivar 61 drive via the communication network, in the same way as via the I/O terminals. When commands are sent via a network they are written in a command word. This word behaves like virtual terminals containing logic inputs. Application functions can be assigned to the bits of this word. More than one function can be assigned to the same bit. The commands and references can come from different sources, such as the terminals, graphic display terminal or communication networks. Each source can be set or switched individually using logic inputs or command word bits. The I/O profile is supported by all integrated communication ports (Modbus, CANopen), as well as by all the communication cards available (Ethernet TCP/IP, Fipio, Profibus DP, etc.). v CiA DSP 402 profile ( “Device Profile Drives and Motion Control”) This profile from the organization CiA (CAN in Automation) describes standard functions, parameters and operation for variable speed drives. This standard is an extension of the Drivecom profile. The Altivar 61 drive complies with the CiA DSP 402 standard and it supports the following 2 modes in this profile: separate and not separate. Separate mode The Start/Stop commands and references can come from different sources. Example: the speed reference is transmitted by the Ethernet TCP/IP network and the Start/Stop commands by the logic signals wired on the terminals. Each source can be set or switched individually using logic inputs or command word bits. Not separate mode The Start/Stop commands and references (speed, torque, PID, etc.) come from the same source (example: CANopen bus). It is possible to replace this source by another one, using a logic input or command word bit. The CiA DSP 402 profile is supported by all integrated communication ports (Modbus, CANopen), as well as by all the communication cards available (Ethernet TCP/IP, Fipio, Profibus DP, etc.). v ODVA profile The ODVA profile is supported by the DeviceNet communication card.
Presentation: pages 4 to 7
Characteristics: pages 8 to 15
References: pages 18 to 21
Dimensions: pages 90 to 111
Schemes: pages 112 to 127
157 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com