Page 150

Functions

0

Variable speed drives for asynchronous motors

0

Altivar 61

Summary of functions Remote graphic display terminal functions Description Navigation Password page 150 page 151 page 151

Integrated 7-segment display terminal Presentation page 152

Start-up Simply Start menu Programming using macro-configurations MONITORING menu page 152 page 153 page 154

Configuration and settings Presentation page 154

Operation Presentation page 154

Maintenance, diagnostics Response to faults or alarms Fault history and help IDENTIFICATION menu Test functions Oscilloscope function page 155 page 155 page 155 page 155 page 155

Controlling the drive Via the drive I/O Via the remote graphic display terminal Via a communication network - I/O profile - CiA DSP 402 profile - ODVA profile page 156 page 156 page 157 page 157 page 157

Functions suitable for pumping and ventilation applications Motor control profiles - Energy saving ratio - Quadratic ratio (Kn 2) PID regulator - Internal references - Preset PID references - PID feedback - PI feedback supervision - Sleep/wake-up - Activate sleep mode by flow detection - Alarms - Predictive speed reference - Auto/Man. Forced operation Flow limit page 158 page 158 page 158 page 158 page 159 page 159 page 159 page 159 page 159 page 159 page 159 page 159 page 159

Other application functions 2-wire control - State detection - Transition detection - Forward operation as priority page 160 page 160 page 160 page 160 page 160

- Time - Profile (linear, S, U or customized) - Switching - Automatic adaptation page 160 page 161 page 161 page 161 page 162 page 162 page 162

3-wire control Phase rotation Ramps

Preset speeds JOG operation Limiting low speed operating time

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

148 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 151

Functions

0

Variable speed drives for asynchronous motors

0

Altivar 61

Summary of functions (continued) Other application functions (continued) Motor control types - Flux Vector Control with sensor (FVC) - Sensorless Flux Vector Control - 2-point Vector Control - Voltage/frequency ratio - Synchronous motor Limiting motor overvoltage Auto-tuning Switching frequency, noise reduction Motor fluxing Output contactor command Stop on thermal alarm Uncontrolled output cut +/- speed - Single action buttons - Double action buttons - Reference saving - Around a reference Automatic catching of a spinning load with speed detection Undervoltage management Braking balance Braking resistor thermal protection Parameter set switching Motor or configuration switching Reference switching Operations on the references - Summing inputs - Subtraction inputs - Multiplication inputs Torque limit Torque or current limit detection Current limit Reference saving Stop types - Freewheel stop - Fast stop - Fastest possible stop - DC injection stop Motor thermal protection Drive thermal protection IGBT thermal protection Machine protection Configuring the drive’s fault response Resetting resettable faults General reset (disables all faults) Automatic restart PTC probe protection IGBT testing Resetting operating time to zero External fault Line contactor control Forced local mode

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111 page 163 page 163 page 163 page 163 page 163 page 163 page 163 page 163 page 164 page 164 page 164 page 165 page 165 page 165 page 166 page 166 page 166 page 167 page 167 page 167 page 168 page 168 page 168 page 169 page 169 page 169 page 170 page 170 page 170 page 171 page 171 page 171 page 171 page 171 page 172 page 172 page 172 page 172 page 173 page 173 page 173 page 174 page 174 page 174 page 174 page 174 page 175 page 175

Schemes: pages 112 to 127

149 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 152

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61

Remote graphic display terminal functions DF534487

This display terminal is attached to the front of the drive. It includes the integrated 7-segment display terminal for drives supplied without a graphic display terminal. b Description v Description of graphic display terminal 1 Graphic display unit: - 8 lines, 240 x 160 pixels - large digit display that can be read from 5 m away - bar chart display 2 Assignable functions keys F1, F2, F3, F4: - dialogue functions: direct access, help screens, navigation - application functions: Local/Remote, preset speed. 3 STOP/RESET key: local control of motor stopping/fault clearing 4 RUN key: local control of motor operation 5 Navigation button: - Press to save the current value (ENT) - Turn ± to increase or decrease the value, or go to the next or previous line 6 FWD/REV key: reverses the direction of rotation of the motor 7 ESC key: aborts a value, parameter or menu to return to the previous option.

1

2 3

7

4

6

5

534786

Note: Keys 3, 4 and 6 can be used to control the drive directly.

RUN

1

Term

REM

+50.00Hz

6

1. DRIVE MENU

2

1.1 SIMPLY START 1.2 MONITORING 1.3 SETTINGS

3

1.4 MOTOR CONTROL 1.5 INPUTS / OUTPUTS CFG 4

Code

<<

F1

F2

Presentation: pages 4 to 7

>> F3

T/K F4

Characteristics: pages 8 to 15

5 v Description of graphic display unit 1 Display line. Its content can be configured; the factory settings show: - the drive status (example: RUN) - the active control channel (example: “Term”: Terminals), - the frequency reference - Type of control (example: “LOC/REM”). 2 Menu line. Indicates the current menu or submenu. 3 Area displaying menus, submenus, parameters, values, bar charts, in the form of a scrolling window, with a maximum of 5 lines. The line or value selected using the navigation button is displayed in reverse video (see opposite). 4 Section displaying the functions assigned to the keys F1 to F4 and aligned with them, for example: - >> : Horizontal scrolling to the right, or proceeding to the next menu or submenu, or, in the case of a value, decreasing the value, displayed in reverse video (see example opposite) - << : Horizontal scrolling to the left, or proceeding to the next menu or submenu, or, in the case of a value, increasing the value, displayed in reverse video - “T/K” : Local Remote function assigned to key F4, - HELP: Contextual help - Code: Displays the selected parameter code - Other functions (application functions) can be assigned to these keys via the 1.6 COMMAND menu. 5 : Means that this display window does not scroll further down. : Means that this display window can scroll further down. 6 : Means that this display window can scroll further up. : Means that this display window does not scroll further up.

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

150 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 153

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61

Remote graphic display terminal functions (continued) 534884 b Navigation: accessing menus and parameters Structure of main menus: 1 Drive menu:

ATV71HU22N4

Menu type

Function

1.1 SIMPLY START 1.2 MONITORING

Simplified menu for fast startup Displays current values for motor, inputs/outputs and communication (command words, status words, etc.) Accesses the adjustment parameters, which can be modified during operation Accesses the motor parameters, including adjustment of motor control profiles Configures the I/O and transforms signals Configures the command and reference channels Configures the application functions (preset speeds, PID regulator, etc.) Configures the fault management process Configures the communication networks Provides diagnostics for motor and drive, integrated test procedures, fault history Identifies the drive and internal options Restores factory settings (completely or by parameter group) Accesses the parameters selected by the user Accesses the parameters for the multipump card or the Controller Inside programmable card

2.2kW/3HP 380/480V Config n˚1

1.3 SETTINGS 1.4 MOTOR CONTROL

RUN

Term

+50.00Hz

5.4A

1.5 INPUTS/OUTPUTS CFG 1.6 COMMAND 1.7 APPLICATION FUNCT.

1. DRIVE MENU

1.1 SIMPLY START 1.2 MONITORING

1

1.3 SETTINGS

1.8 FAULT MANAGEMENT 1.9 COMMUNICATION 1.10 DIAGNOSTICS

1.4 MOTOR CONTROL 1.5 INPUTS / OUTPUTS CFG

Code

RUN

<<

Term

>>

Quick

+43.33Hz 5.4A

2

1.11 IDENTIFICATION 1.12 FACTORY SETTINGS

Motor speed

1300 rpm Min=0

3

1.13 USER MENU 1.14 PROGRAMMABLE CARD

2 Display line

Max=1500 Quick

3 Display screen: Displays values in the form of bar charts or digital values, depending on the extent of customization. RUN

Term

+0.00Hz

4 Main menu:

0A

MAIN MENU 1. DRIVE MENU 2. LEVEL ACCESS

4

3. OPEN / SAVE AS

Menu type

Function

1. DRIVE MENU 2. ACCESS LEVEL 3. OPEN / SAVE AS

See above (1 Drive menu) 4 access levels: basic, limited, advanced, expert Transfers files between the graphic display terminal and the drive Provides password protection for the configuration Choice of 6 languages available (English, German, Spanish, French, Italian and Chinese) Customizes the display line 2 and the display screen 3 (bar charts, digital values) Configures how parameters are displayed: customization, selection for User menu, visibility, accessibility

4. PASSWORD 5. LANGUAGE

<<

4. PASSWORD >>

Quick

5. LANGUAGE 6. MONITORING CONFIG. 7. DISPLAY CONFIG.

b Password Altivar 61 drives allow individual parameters to be selected for password protection. Rights can be set for save operations and for loading the configuration.

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

151 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 154

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61

Integrated 7-segment display terminal ATV 61pppppM3, ATV 61HD11M3X…HD45M3X and ATV 61H075N4…HD75N4 drives can be supplied without a graphic display terminal. In this case, they are equipped with an integrated 7-segment display terminal. This can be used to: v Display status and faults v Access and modify parameters

Start-up

DF534783

The Altivar 61 drive is supplied ready for use for most applications. When the drive is switched on, the menus for setting the language and access level appear automatically. RUN

Term

+50.00Hz

5.4A

1.1 SIMPLY START 2/3 wire control

:

2 wire

Macro-configuration :

Pumps.Fans

Standard mot. Freq. :

50Hz IEC

Rated motor power :

2.2kW

Rated motor volt.

Code

:

<<

400V

>>

Quick b Simply Start menu By accessing the Simply Start menu directly, it is possible to: v Pre-program the drive for an application: - Select the relevant macro-configuration - 2-wire/3-wire control v Benefit from optimum motor performance: - Enter data from the motor rating plate - Auto-tuning. v Protect the motor by setting the drive’s integrated electronic thermal overload relay

Simply Start menu

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

152 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 155

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61

Start-up (continued) b Programming using macro-configurations Programming using macro-configurations offers the choice of five options corresponding to the various business areas and applications: v Start/stop v General use v PID regulation v Communication network connectivity v Ventilation pump. Choosing one of these macro-configurations automatically assigns the functions, parameters and I/O, even in the case of option cards. Although the configuration is preset, it can still be modified, if necessary. The Ventilation pump macro-configuration is set as the factory configuration. The preset functions for each macro-configuration are given in the table below. Type of macro-configuration

Start/stop

General use

PID regulation

Communication Ventilation pump. network connectivity

AI1

Ref. 1 channel

Ref. 1 channel

PID reference

AI2 AO1 2-wire

LI1 LI2 LI3

Not assigned Motor freq. Forward Fault reset Not assigned

Sum ref. 2 Motor freq. Forward Reverse JOG

LI4

Not assigned

Fault reset

Ref. 1B channel Motor freq. Forward Freewheel Ref. 1B switching Fault reset

LI5

Not assigned

Torque limit

Not assigned

Not assigned

LI6 LI1 LI2 LI3 LI4

Not assigned Stop Forward Reverse Not assigned

Not assigned Stop Forward Reverse JOG

LI5

Not assigned

Fault reset

Not assigned Stop Forward Reverse Ref. 2 switching Forced local

Not assigned Stop Forward Freewheel Ref. 1B switching Fault reset

LI6

Not assigned

Torque limit

Not assigned

Not assigned

Faulty Not assigned

Faulty Not assigned

PID feedback Motor freq. Forward Fault reset PID integral reset PID 2 preset ref. PID 4 preset ref. Not assigned Stop Forward Reverse PID integral reset PID 2 preset ref. PID 4 preset ref. Faulty Not assigned

Ref. 2 channel Ref. 1 channel by bus Not assigned Motor freq. Forward Fault reset Ref. 2 switching Fault reset

Faulty Not assigned

Faulty Drive operation

Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Motor current Not assigned

Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Motor current Not assigned

Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Motor current PID error

Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Motor current Not assigned

Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Not assigned Motor current Not assigned

F1 key

Not assigned

Not assigned

Not assigned

Not assigned

F2, F3, F4 keys

Not assigned

Not assigned

Not assigned

Control via graphic display terminal Not assigned

Altivar 61 drive I/O

3-wire

R1 R2

Ref. 1 channel

I/O extension card I/O 2-wire LI7 3-wire LI7 LI8 to LI14 LO1 to LO4 R3/R4 AI3, AI4 RP AO2 AO3

Graphic display terminal keys

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

T/K (control via graphic display terminal)

Schemes: pages 112 to 127

153 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 156

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61

522169

Start-up (continued) b MONITORING menu The MONITORING menu can be used to display commands, the operation of the motor and application through the drive of its I/O or of the communication network connections. Term

RUN

+43.33Hz

5.4A

:

43.3 Hz

Motor current

:

5.4 A

Motor speed

:

1300 rpm

Motor thermal state :

80 %

Code

:

<<

80A

+50.00Hz

1 0 1 0

PR

LI7

LI1

LI8

LI2

LI9

LI3

LI4

LI5

LI6

LI10 LI11 LI12 LI13 LI14

<<

Displaying physical values

>>

5.4A

+50.00Hz

COMMUNICATION MAP

85 %

Quick

>>

Mod.

RUN

Logic input map

Frequency Ref.

Drv thermal state

Term

RUN

1.2 MONITORING

Cmd channel

:

Modbus

Cmd Value

:

ABCD Hex

Active ref. channel :

CANopen

Frequency ref.

:

+50.00 Hz

ETA status word

:

Quick

Code

Logic input map

<<

2153 Hex

Quick

>>

Communication map

One of the uses of this menu is to display the alarm groups, thermal states and electrical values such as: v electrical power consumed by the drive v the drive’s cumulative electrical power, etc.

Configuration and settings

522154

The SETTINGS menu can be used to configure all the drive’s settings. Activating a function automatically provides access to the related settings on the same screen (the application functions are described on pages 158 to 175). RUN

Term

+50.00Hz 1250A

RDY

Term

+0.00Hz

0.0A

0,01

2 preset speeds

:

LI3

:

3,00 s

4 preset speeds

:

LI4

Deceleration

:

3,00 s

8 preset speeds

:

LI5

Acceleration 2

:

5,00 s

Preset speed 2

:

10.0 Hz

Deceleration 2

:

5,00 s

Preset speed 3

:

Code

<<

>>

Code

Quick

Settings screen

<<

9.51 s

15.0 Hz

>>

0A

+0.00Hz

ACCELERATION

Acceleration

Ramp increment :

Term

RDY

PRESET SPEEDS

1.3 SETTINGS

Min=0,01

Max=9999

Quick

<<

Setting a function

>>

Quick

Configuring a value

Operation

533525

The display screen appears automatically every time the drive is turned on. There are different possible scenarios: b One or two bar charts are displayed. b One, two or five digital values are displayed. Term

RUN

+43.33Hz 5.4A

Motor speed

+38.0Hz

RUN

10A

Max=1500 Quick

<<

References: pages 18 to 21

>>

+43.33Hz

5.4A

Frequency Ref.

:

Motor current

:

5.4 A

Motor speed

:

1300 rpm

Motor thermal state :

80 %

Drv thermal state

1 digital value

Characteristics: pages 8 to 15

Term

1.2 MONITORING

+45.1 Hz

1 bar chart

Presentation: pages 4 to 7

Term

Output frequency

1300 rpm Min=0

DEC

Code

Quick

<<

43.3 Hz

:

85 %

>>

Quick

5 digital values

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

154 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 157

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61

533523

Maintenance, diagnostics Term

SCF1

+50.00Hz

0.0A

FAULT HISTORY Short circuit b Response to faults or alarms It is possible to use the alarm management or drive operation configuration functions to take corrective measures before stopping the machine.

Overcurrent External FLT Overvoltage Undervoltage

Help

Quick

522162

Fault history

SCF1

Term

New functions have been added to the Altivar 61 drive to enable it to provide quick and simple maintenance, ultimately boosting productivity:

+50.00Hz

0.0A

MOTOR SHORT CIRCUIT b Fault history and help When a fault occurs, a help screen is available to quickly identify the cause of the fault. As soon as the fault occurs, values such as speed, current, thermal state, timer are saved and restored in the fault history. The last 8 faults are stored.

Check the connection cables and the motor insulation. Perform the diagnostic test.

Quick

534639

Troubleshooting screen

Term

RUN

+50.00Hz

5.4A

1.11 IDENTIFICATION ATV61HU22N4 2.2 kW / 3HP 380 / 480 V b IDENTIFICATION menu The IDENTIFICATION menu can be used to display the relevant serial numbers and software versions, thereby helping to manage the equipment base. This information, also available from the PowerSuite software workshop, can be exported to other database-type software applications.

Appl. Software V1.0 IE 01 MC Software V1.0 IE 01

<<

>>

Quick

522157

Identification screen

RUN

Term

+50.00Hz

5.4A

SERVICE MESSAGE For technical support, dial 32 12 75

Quick Example of a customized message b Test functions The Altivar 61 drive includes the following test functions: v Identifying any motor short-circuit before start-up v Running, via the graphic display terminal or PowerSuite software workshop, automatic procedures during maintenance operations aimed at testing: - the motor - the drive power components The test results are shown on the graphic display terminal or using the PowerSuite software workshop. It is also possible to write and read messages in the drive using the graphic display terminal or the PowerSuite software workshop. b Oscilloscope function The Altivar 61 drive has an oscilloscope function, which produces traces that can be viewed using the PowerSuite software workshop. The PowerSuite software workshop can also be used to carry out remote diagnostics via modem.

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

155 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 158

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61

Controlling the drive b Via the drive I/O Control signals are transmitted via cable to the I/O. Functions are assigned to logic inputs, analog inputs, etc. A logic input can be assigned to more than one function. This means that two functions can be controlled using a single signal, thereby limiting the number of inputs required. The Altivar 61 drive I/O can be configured independently from each other. For instance, v A time delay can be applied when it comes to reading the logic inputs, so as to avoid any bounce-back from certain switches. v Transforming incoming signals on the analog inputs can help the drive fully adapt to the control devices and applications: - Minimum and maximum values for the input signal - Input filtering in order to eliminate unwanted interference from the signals received - Magnifying glass effect through delinearizing the input signal in order to increase the precision with small amplitude signals - “Pedestal” and “Deadband” functions for signals in order to prevent low speed operations which can have an adverse effect on the application - “Mid-point” function, which can be used from a unipolar input signal to obtain a bipolar output signal to control the speed and direction of rotation v Transforming analog outputs which transfer information sent by the drive to other devices (display units, drives, PLCs, etc.): - voltage or current output signal - minimum and maximum values for the output signal - output signal filtering Logic outputs can be delayed on activation and deactivation. The output state can also be configured when the signal is active. The frequency control signals are also transformed by the drive: v signal frequency minimum and maximum values (30 kHz on the extended I/O card’s RP input). b Via the remote graphic display terminal The rotation commands and references (speed or PID) can be controlled via the graphic display terminal. Some application functions can also be assigned to the function keys F1, F2, F3 and F4 on the graphic display terminal. It is possible to manage a change in command and/or reference source (bumpless function) in different ways. Example: two options are offered when switching control from via the terminals to via the graphic display terminal: v stop the Altivar 61 drive, or v continue operation with a copy of the direction of rotation and reference

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

156 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 159

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61

Controlling the drive (continued) b Via a communication network v I/O profile The I/O profile, which is easy and quick to use, can be used to control the Altivar 61 drive via the communication network, in the same way as via the I/O terminals. When commands are sent via a network they are written in a command word. This word behaves like virtual terminals containing logic inputs. Application functions can be assigned to the bits of this word. More than one function can be assigned to the same bit. The commands and references can come from different sources, such as the terminals, graphic display terminal or communication networks. Each source can be set or switched individually using logic inputs or command word bits. The I/O profile is supported by all integrated communication ports (Modbus, CANopen), as well as by all the communication cards available (Ethernet TCP/IP, Fipio, Profibus DP, etc.). v CiA DSP 402 profile ( “Device Profile Drives and Motion Control”) This profile from the organization CiA (CAN in Automation) describes standard functions, parameters and operation for variable speed drives. This standard is an extension of the Drivecom profile. The Altivar 61 drive complies with the CiA DSP 402 standard and it supports the following 2 modes in this profile: separate and not separate. Separate mode The Start/Stop commands and references can come from different sources. Example: the speed reference is transmitted by the Ethernet TCP/IP network and the Start/Stop commands by the logic signals wired on the terminals. Each source can be set or switched individually using logic inputs or command word bits. Not separate mode The Start/Stop commands and references (speed, torque, PID, etc.) come from the same source (example: CANopen bus). It is possible to replace this source by another one, using a logic input or command word bit. The CiA DSP 402 profile is supported by all integrated communication ports (Modbus, CANopen), as well as by all the communication cards available (Ethernet TCP/IP, Fipio, Profibus DP, etc.). v ODVA profile The ODVA profile is supported by the DeviceNet communication card.

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

157 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com