Page 160

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61

Functions suitable for pumping and ventilation applications b Motor control profiles v Energy saving ratio This type of command makes it possible to optimize the energy consumed based on the load applied to the machine. v Quadratic ratio (Kn2) This type of command is optimized for centrifugal pumps and ventilators. b PID regulator This can be used to regulate a process with a reference and feedback given by a sensor. Function suitable for controlling traction on a winder. Pr2 Pr4

LI PII

A

Internal references rP2 rP3 rP4 Preset PID references nO AI1 ... AI4 RP Network AI

PID feedback

PIC tLS

Auto/Man. Gains rdG

+ rIG

PAU POH

AC2

+ rPG

PrP

+ POL

Scaling PIF

Error threshold Sleep/wake-up

Ramp nO rPI

Error inversion

Predictive speed reference FP1

PIF1 / PIF2 PIP1 / PIP2

B

Ramps

“Start” state

ACC dEC x PSr nO SP2 ... SP16 ...

PIM Manual reference

(man.)

Preset manual references

ACC: acceleration, dEC: deceleration, LI: logic inputs, B: Speed reference.

v Internal references - rPI: reference transmitted by the graphic display terminal or a communication network. - A: reference given by Fr1 or Fr1b with the summing, subtraction and multiplication functions, as appropriate. The “PII” parameter is used to choose between these two references. v Preset PID references 2 or 4 PID references are available. Table showing combinations of selected PID references:

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

LIx (Pr4) 0

LIy (Pr2) 0

Reference rPI or A

0

1 rP2

1

0 rP3

1

1 rP4

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

158 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 161

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 b PID regulator (continued) v PID feedback PID feedback can be assigned to one of the analog inputs (AI1 to AI4) or the frequency control input (RP), depending on the option cards present. It can also be transmitted by a communication network (network AI). Frequency Sleep

LSP + SLE LSP

0 t tLS

PID error

Wake-up rSL t

0 LSP: Low speed SLE: Adjustable restart threshold tLS: Maximum low speed operating time rSL: Restart error threshold

Example of operation of sleep/wake-up function

The following 4 functionalities can be used in combination with the PID regulator: v PI feedback supervision v Sleep/wake-up This function is used in addition to the PID regulator to avoid extended operation at too low speeds that is unnecessary or undesirable. It stops the motor following a period of reduced speed operation. This duration (tLS parameter) and this speed (LSP + SLE parameters) can be adjusted. It restarts the motor if the error or the PID feedback exceeds an adjustable threshold (rSL or UPP parameters depending on the threshold). v Activate sleep mode by flow detection This function is used in applications where zero flow cannot be detected by the sleep function alone. v Alarms Minimum and maximum monitoring thresholds of the PID regulator feedback and monitoring threshold of the PID regulator error. v Predictive speed reference This reference can come from the terminals (analog inputs, etc.), the graphic display terminal or a communication network. This speed input gives an initial reference for starting. v Auto/Man. This can be used to switch from speed regulation mode (Man.) to PID regulation mode (Auto). A logic input or command word bit is used for switching. Speed regulation mode (Man.) The manual reference is transmitted via the terminals (analog inputs, preset speeds, etc.). With manual switching, the speed reference changes according to the ramp times ACC and dEC. PID regulation mode (Auto) In automatic mode it is possible to: - Adapt the references and feedback to the process (transformation) - Correct a PID inversion - Adjust the proportional, integral and derivative gains (Kp, Ki and Kd) - Shunt the integral - Use the “alarm” on the logic output or display it on the graphic display terminal, if the threshold is exceeded (Max. feedback, Min. feedback and PID error) - Display the PID reference, PID feedback, PID error and PID output on the graphic display terminal and assign them to an analog output - Apply a ramp (time = PrP) to the PID reference. The motor speed is limited to between LSP and HSP. It is displayed as process values. b Forced operation In combination with the function inhibiting all faults, this function allows the run command to be forced in a defined direction and the reference to be forced to a configured value. b Flow limit Allows the flow of a fluid to be limited, for pumps.

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

159 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 162

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61

Other application functions b 2-wire control This can be used to control the direction of operation by means of a stay-put contact. It is enabled by means of 1 or 2 logic inputs (non-reversing or reversing). This function is suitable for all non-reversing and reversing applications. 3 operating modes are possible: v Detection of the state of the logic inputs v Detection of a change in state of the logic inputs v Detection of the state of the logic inputs with forward operation always having priority over reverse Altivar 61 control terminals

24 V

LI1

LIx

LI1: forward LIx: reverse

Wiring diagram for 2-wire control f (Hz)

0 t b 3-wire control This can be used to control the operating and stopping direction by means of pulsed contacts. It is enabled by means of 2 or 3 logic inputs (non-reversing or reversing).

Stop 1 t

0

This function is suitable for all non-reversing and reversing applications.

1

LI1: Stop LI2: Forward LIx: Reverse

Altivar 61 control terminals

Forward t

0

24 V

LI1

LI2

LIx

1 Reverse 0 t

Example of 3-wire control operation

Wiring diagram for 3-wire control

522164 b Phase rotation This function can be used to reverse the direction of rotation without modifying the drive wiring.

RDY

Term

+0.00Hz

0.0A

RAMP Ramp shape

: Ramp increment :

Linear

Acceleration

:

3.92 s

Deceleration

:

0.54 s

Ramp 2 threshold :

0.0 Hz

Code

0.01 b Ramps v Acceleration and deceleration ramp times This can be used to define acceleration and deceleration ramp times according to the application and the machine dynamics. f (Hz)

f (Hz) FrS

FrS

Quick

Ramp settings t

0 t

0 t2 t1

Linear acceleration ramp

Linear deceleration ramp

FrS: Nominal motor frequency t1: Acceleration time t2: Deceleration time t1 and t2 can be set independently from 0.01 to 9000 s (according to one of the following ramp increments: 0.01 s, 0.1 s or 1 s); Factory setting: 3 s.

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

160 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 163

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 v Acceleration and deceleration ramp profile This can be used to gradually increase the output frequency starting from a speed reference, following a linear profile or a preset profile. In the case of applications involving handling, packaging and passenger transport, the use of S ramps takes up mechanical play and eliminates jolts and also limits “non-following” of speed during rapid transient operation of high-inertia machines. Selecting “linear”, “S”, “U” or customized profiles assigns both the acceleration and deceleration ramps. S ramps

U ramps f (Hz)

f (Hz)

FrS t t

0 t2 t2 t1 t1 f (Hz)

f (Hz)

f (Hz)

FrS

FrS

FrS

0

Customized ramps t2 t2 t1

FrS: Nominal motor frequency t1: Ramp time set t2 = 0.6 x t1 The curve coefficient is fixed.

t1

FrS: Nominal motor frequency t1: Ramp time set t2 = 0.5 x t1 The curve coefficient is fixed.

f (Hz) HSP dE2

AC2 dEC

ACC Forward 1 or 0 reverse 1 LI4 0 t t

FrS

0 t0

0 f (Hz)

FrS t tA1 t

0 tA3 tA2

ACC or AC2 tA4 dEC or dE2

FrS: Nominal motor frequency tA1: Can be set between 0 and 100% (of ACC or AC2) tA2: Can be set between 0 and (100% - tA1) (of ACC or AC2) tA3: Can be set between 0 and 100% (of dEC or dE2) tA4: Can be set between 0 and (100% - tA3) (of dEC or dE2) ACC: Acceleration ramp 1 time AC2: Acceleration ramp 2 time dEC: Deceleration ramp 1 time dE2: Deceleration ramp 2 time v Ramp switching This can be used to switch 2 acceleration and deceleration ramp times, which can be adjusted separately. Ramp switching can be enabled by: - a logic input - a frequency threshold - a combination of the logic input (or a command word bit) and the frequency threshold - a command word bit t

Example of switching using logic input LI4 Acceleration 1 (ACC) and deceleration 1 (dEC): - adjustment 0.01 to 9000 s - factory setting 3 s Acceleration 2 (AC2) and deceleration 2 (dE2): - adjustment 0.01 to 9000 s - factory setting 5 s HSP: high speed.

Function suitable for: - material handling with smooth starting and approach - machines with fast steady state speed correction v Automatic adaptation of deceleration ramp This can be used to automatically adapt the deceleration ramp if the initial setting is too low when the load inertia is taken into account. This function prevents the drive from locking in the event of an overbraking fault. When this function is active and a short deceleration time has been set, the drive optimizes the motor power supply in order to achieve a high braking torque. Function suitable for all applications which do not need to stop at a precise moment and do not use braking resistors. Automatic adaption must be disabled for machines with a stop position on a ramp and using a braking resistor.

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

161 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 164

Functions (continued)

0

Variable speed drives for asynchronous motors

0

534800

Altivar 61

RDY

Term

+0.00Hz

0.0A

PRESET SPEEDS 2 preset speeds

:

LI3

4 preset speeds

:

LI4

8 preset speeds

:

LI5

Preset speed 2

:

10.0 Hz

Preset speed 3

:

Code

<<

15.0 Hz

>>

Quick b Preset speeds This can be used to switch preset speed references. Choose between two, four or eight preset speeds. Enabled by means of 1, 2 or 3 logic inputs. Preset speeds can be set in increments of 0.1 Hz, from 0 Hz to 500 Hz or 1000 Hz, depending on the rating. Function suitable for material handling and machines with several operating speeds. f (Hz)

Preset speed settings

The speed achieved with the LI3 and LI4 inputs at 0 is LSP or speed reference, resulting from the operations carried out on the references.

20 15 10 LSP

Factory settings: t Forward 1 or Reverse LI2 0

1st speed: LSP (low speed or speed reference) 2th speed: 10 Hz t

3th speed: 15 Hz

1 4th speed: 20 Hz

LI3 0 t

1 t

LI4 0

Example of operation with 4 preset speeds and 2 logic inputs b JOG operation This can be used for pulse operation with minimum ramp times (0.1 s), limited speed reference and minimum time between 2 pulses. It is enabled by 1 logic input and pulses given by the operating direction command. Function suitable for machines with product insertion in manual mode (example: gradual movement of the mechanism during maintenance operations). f (Hz)

t JGt Forward 1 or Reverse 0 t

1 JOG t

0

JGt: minimum time between 2 pulses, which Speed reference: can be set from 0 to 10 Hz, can be set between 0.5 and 2 s. factory setting 10 Hz.

Example of JOG operation b Limiting low speed operating time The motor is stopped automatically after a period of operation at low speed (LSP) with a zero reference and a run command present. This time can be set between 0.1 and 999.9 seconds (0 corresponds to an unlimited time). Factory setting 0 s. The motor restarts automatically on the ramp when the reference reappears or if the run command is interrupted and then re-established. Function suitable for automatic Stops/Starts.

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

162 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 165

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 b Motor control types v Flux Vector Control with sensor (FVC) In voltage mode, this control type can be used to obtain the best static and dynamic torque performance. v Sensorless Flux Vector Control In voltage mode, this control type can be used with a single motor or motors connected in parallel. In current mode, this profile performs better than the previous type, but it cannot supply power to motors connected in parallel. v 2-point Vector Control The zone for operating at constant power can be optimized by defining an additional point in the control profile. This function should be used with motors offering a two-part defluxing zone. It can be used to limit the voltage at the motor terminals when the motor is being powered by a high line supply. v Voltage/frequency ratio This control type is particularly suitable for special motors (high-speed motors, synchronized asynchronous motors, etc.). The ratio can be adjusted by 2 or 5 points and used to achieve output frequencies of up to 1000 Hz. v Synchronous motor This control type is exclusively reserved for controlling open loop synchronous permanent magnet motors with sinusoidal electromotive force (EMF). b Limiting motor overvoltage The Altivar 61 drive inverter bridge control can be used to limit overvoltage in the motor terminals, which is double the voltage level in the DC bus (Stressless PWM). This function is useful in cases where long lengths of cabling, rewound motors or motors in a low isolation class are involved. b Auto-tuning Auto-tuning can be performed: v using a dialogue tool (graphical display terminal, PowerSuite software workshop, integrated 7-segment display terminal) v via a communication network v automatically every time the drive is switched on v by enabling a logic input. Auto-tuning can be used to enhance application performance. In Flux Vector Control mode (FVC open loop with voltage regulation), certain parameters are measured periodically. Saving the motor thermal state can help to compensate exactly for the motor resistors, even after the drive has been switched off. b Switching frequency, noise reduction The switching frequency setting permits a reduction in the noise generated by the motor for any application requiring a low level of noise. The switching frequency is modulated randomly in order to avoid resonance. This function can be disabled if it causes instability. Switching the intermediate DC voltage at high frequency is useful for supplying the motor with a current wave having little harmonic distortion. The switching frequency is adjustable during operation to reduce the noise generated by the motor. Value: 1 to 16 kHz depending on rating

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

163 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 166

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 b Motor fluxing This can be used to obtain rapid high torque on start-up; magnetic flux needs to be already established in the motor. There is a choice between open loop or closed loop operation. In continuous mode, the drive automatically establishes the flux when it is powered up. In non-continuous mode: v If a logic input or command word bit is assigned to the motor fluxing command, flux is established when the command is confirmed. v If neither a logic input nor command word bit has been assigned, or if the latter are not active when a run command is given, fluxing occurs when the motor starts. Fluxing is accelerated if a higher current than the nominal motor current is applied, then it is set to the value of the motor no-load current.

LIp

LO/Rp

0

W

V

U b Output contactor command This allows the drive to control a contactor located between the drive and the motor. The request to close the contactor is made when a run command appears. The request to open the contactor is made when there is no current in the motor.

Feedback

+ 24 V

Command

ATV 61

K20

KM2

Note: If a DC injection braking function has been configured it should not be left operating too long in stop mode, as the contactor only opens at the end of braking.

KM2

K20 M 3

KM2

Output contactor command

Presentation: pages 4 to 7

Characteristics: pages 8 to 15 b Stop on thermal alarm This can be used to: v Allow a movement to end before examining a thermal fault. There are two adjustable thresholds used to define the thermal state level which, when exceeded, makes a machine stop; v Prevent a new run command from being accepted as long as the drive and motor temperatures are not less than 100%.

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

164 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 167

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61

522166 b Uncontrolled output cut It is possible to configure output phase loss protection, which will allow the drive or motor circuit to be broken without the drive becoming locked in fault mode and facilitate a smooth restart after the motor has been reconnected. The output phase loss may also lock the drive, depending on the configuration. RDY

Term

+0.00Hz

0.0A

+/- SPEED

+ speed assign. :

LI3

- speed assign. : Ref. saved

:

Code

LI4 RAM

Quick

+/- speed function settings b +/- speed This can be used to increase or decrease a speed reference by means of 1 or 2 logic inputs, with or without the last reference being saved (motorized potentiometer function). This function is suitable for centralized control of a machine with several sections operating in one direction or for control by a handling crane pendant control station with two operating directions. Two types of operation are available: v Use of single action buttons: 2 logic inputs are required in addition to the operating direction(s). v Use of double action buttons: only 1 logic input assigned to + speed is required. v Use of single action buttons: 2 logic inputs are required in addition to the operating direction(s). f (Hz) HSP

LSP t

Forward 1 or Reverse 0 t

1

+ speed 0 t

1

- speed 0 t

LSP: low speed, HSP: high speed

Example of "+/- speed" with 2 logic inputs, single action buttons and reference saving v Use of double action buttons: only 1 logic input assigned to + speed is required. Logic inputs: Forward

Reverse a c

+ speed b d

Forward button Reverse button a and b: 1st press c and d: 2st press

Released 1st press (- speed) (speed maintained) – a

2nd press (+ speed)

– c and d c a and b f (Hz) HSP

LSP 0 LSP t HSP Forward 2nd press 1st press 0 b b a a a a a a a

Reverse 2e press 1st press 0 c d c t t

LSP: low speed, HSP: high speed

Example with double action buttons and 1 logic input Note: This type of +/- speed control is incompatible with 3-wire control.

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

165 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 168

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 v Reference saving This function is associated with +/- speed control. This can be used for reading and saving the last speed reference prior to the loss of the run command or line supply. The reference saved is applied the next time a run command is received. v +/- speed around a reference The reference is given by Fr1 or Fr1b, including, if relevant, the summing, subtraction and multiplication functions, as well as the preset speeds. During the run command the drive goes to the reference, following the acceleration and deceleration ramps (pressing +/- speed makes the speed vary around this reference according to acceleration ramp 2 and deceleration ramp 2). + or - speed variation around the reference is limited to a percentage of the reference (SRP parameter). When operation has stopped, the amended reference is not saved. The maximum total reference is always limited by high speed (HSP parameter) and the minimum reference (LSP parameter).

Motor frequency

+ SRP % Reference – SRP %

LSP LSP – SRP % Reference + SRP % + speed – speed Direction of operation

Forward

Forward Reverse

Example of +/- speed around a 2-wire control reference b Automatic catching of a spinning load with speed detection (“catch on the fly”) This function can be used to restart the motor smoothly after one of the following events, provided the run command is still present: v loss of line supply or power off v fault reset or automatic restart v freewheel stop. Once the event is over, the effective speed of the motor is detected in order to restart on a ramp at this speed and return to the reference speed. The speed detection time can reach 0.5 s. This function is suitable for machines which suffer low motor speed loss during a power failure (high-inertia machines such as centrifuges, etc.).

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

166 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 169

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 b Undervoltage management Depending on the application, it is possible to configure the Altivar 61’s response to undervoltages or power failures. If undervoltage occurs: v The Altivar 61 drive can continue operating with undervoltage levels up to -50% (adjustable threshold) v If the drive locks as a result, management of the fault relay can be configured (open or not). If the fault relay does not open an alarm is shown. The Altivar 61 drive can also be configured to prevent the drive locking (using an alarm): v Controlled stop according to the type of stop configured v Deceleration based on a ramp which it automatically adapts to maintain the DC bus voltage, thereby preventing the drive from locking in fault mode v Instant IGBT (inverter bridge) loss followed by power supplied to the motor as soon as the line voltage has reappeared. This function can be used to prevent the Altivar 61 drive being reinitialized. b Braking balance When several drives are connected on a common DC bus, this function can be used to adjust the braking thresholds in order to balance the braking powers among the various drives or braking units. b Braking resistor thermal protection The Altivar 61 drive incorporates thermal protection for braking resistors if it is not equipped with a thermal switch. If the resistor thermal state is too high an alarm can be assigned to the logic output or the drive may lock in fault mode, depending on how the function is programmed.

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

167 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com