Variable speed drives Altivar 61 Catalogue: Functions, pages 170 to 179

Pages 170 to 179 of 211, from Variable speed drives Altivar 61 Catalogue

The original document is the PDF (4.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Telemecanique Altivar 61 ATV61, Schneider Altivar 61 ATV61 and Square D Altivar 61 ATV61

Page 170

Functions (continued)

Variable speed drives for asynchronous motors

0

0

Altivar 61 b Parameter set switching (multi-parameter) This can be used to switch 3 sets of 15 parameters maximum when the motor is running. Each set can contain a different value for each of the parameters. The sets are switched using 1 or 2 logic inputs or command word bits. Function suitable for machines involving 2 or 3 manufacturing processes. Configuration 0 if the two contacts are open.

b Motor or configuration switching (multi-motor or multi-configuration) The Altivar 61 drive can have 3 configurations, which can be activated remotely, allowing it to adapt to: v 2 or 3 different motors or mechanisms in multi-motor mode. In this instance, the thermal state for all the motors is calculated and saved. This means that each motor is protected thermally. v 2 or 3 configurations for the same motor in multi-configuration mode. This function can also be used to save the current configuration in another memory zone, which it can be retrieved from. Switching is carried out using 1 or 2 logic inputs, depending on the number of motors or configurations chosen (2 or 3).

ATV 61 LO or R

LIx

Configuration 0

Configuration 1 LO or R

+ 24 V Configuration 1 Configuration 2

LIy

LO or R Configuration 2

Multi-motor and multi-configuration modes cannot be used together.

M0

M1

M2

Schematic diagram for multi-motor mode f (Hz) Fr1b

Fr1 t Forward or 1 Reverse 0 t

1 t

LIx 0

Example of reference switching

Presentation: pages 4 to 7

Characteristics: pages 8 to 15 b Reference switching Switching between two references (speed, PID, etc.) can be enabled by: v a logic input v a command word bit Reference 1 (Fr1) is active if the logic input (or command word bit) is at 0; reference 2 (Fr1b) is active if the logic input (or command word bit) is at 1. References can be switched with the motor running. Reference Fr1b, like Fr1, can originate from: v an analog input (AI) v a frequency control input (RP) v the graphic display terminal v the Modbus or CANopen bus v a communication card v the “Controller Inside” programmable card

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

168 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 171

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 b Operations on the references (summing, subtraction, multiplication) Summing, subtraction and multiplication inputs can be activated simultaneously.

Fr1 or Fr1b

SA2

The drive reference is thus: v reference of drive A = (Fr1 or Fr1b + SA2 + SA3 - dA2 - dA3) x MA2 x MA3

SA3 dA2

A v Summing inputs They can be used to add 2 to 3 references from different sources to Fr1 or Fr1b (see “Reference switching”). The references to be added together are selected from all the possible types of reference.

dA3 MA2 MA3

A: drive reference SA2, SA3: summing inputs dA2, dA3: subtraction inputs MA2, MA3: multiplication inputs.

Example: Reference Fr1 or Fr1b from AI1 Reference SA2 from CANopen Reference SA3 from a communication card Reference of drive A = Fr1 or Fr1b + SA2 + SA3. v Subtraction inputs They can be used to subtract 2 to 3 references from different sources from Fr1 or Fr1b (see “Reference switching”). The references to be subtracted are selected from all the possible types of reference. Example: Reference Fr1 or Fr1b from AI1 Reference dA2 from CANopen Reference dA3 from a communication card Reference of drive A = Fr1 or Fr1b - dA2 - dA3. v Multiplication inputs They can be used to multiply 2 to 3 references from different sources by Fr1 or Fr1b (see “Reference switching”). The references to be multiplied are selected from all the possible types of reference. Example: Reference Fr1 or Fr1b from AI1 Reference MA2 from CANopen Reference MA3 from a communication card Reference of drive A = Fr1 or Fr1b x MA2 x MA3.

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

169 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 172

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 b Torque limit This can be used to limit the torque in the motor and generator quadrants using separate settings. There are two types of torque limit: v one with a value set by a parameter v the other with a value given by an analog input or a frequency control input. When both torque limit types are enabled it is the lowest value which is read. They can be switched using a logic input or command word bit. This function is not available for voltage/frequency ratio. Torque + 130 % 100 %

Speed – Reverse

Generator mode Reverse speed – torque +

Motor mode Forward speed + torque +

Motor mode Reverse speed – torque –

Generator mode Forward speed + torque –

Speed + Forward

100 % 130 % Overload range Motor torque Torque limit

Torque –

The torque limit operates in both directions of rotation in motor or generator mode.

522170 b Torque or current limit detection This function can be used to detect when the current or torque limit has been reached. Depending on the configuration, it is possible to: v use an alarm to signal this v lock the drive after an adjustable period of time. Term

RDY

+0.00Hz

0.0A

2nd CURRENT LIMIT. I Limit. 2 activ.

:

LI6

I Limit. 2 value

:

6.4 A

Current limitation :

7.9 A

Code b Current limit A 2nd current limit can be configured between 1.1 and 1.2 times the nominal drive current and it can be used to limit the rise in motor temperature and the torque. Switching between 2 current limits can be enabled via: v a logic input v a command word bit

Quick

Configuring current switching

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

170 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 173

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61

F: motor frequency t

0 Run command 1 t

0 LIx (saved) 1 b Reference saving This can be used to: v Read and save the speed reference value of the analog input using a logic input when the command lasts longer than 0.1 s v Control the speed of several drives alternately via a single analog reference and a logic input for each drive v Enable via a logic input a line reference (serial link) on several drives in order to synchronize movements by eliminating variations when the reference is sent The reference is acquired 100 ms after the rising edge of the acquisition request. A new reference is not then acquired until a new request is made.

t

0 100 ms

100 ms

100 ms

Analog reference

522167

Example of how reference saving works

RDY

Term

+0.00Hz

0.0A

STOP CONFIGURATION Type of stop

:

Ramp stop

Freewheel assign. :

NO

Fast stop assign. :

LI4

Ramp divider

:

0

DC inject. assign. :

NO

Code

Quick b Stop types v Freewheel stop This function stops the motor by resistive torque if the motor power supply is cut. A freewheel stop is achieved: - by configuring a normal stop command as a freewheel stop (when a run command is over or a stop command occurs) - by enabling a logic input - by activating a command word bit

Configuring stop types v Fast stop This can be used to achieve a braked stop with an acceptable deceleration ramp time (divided by an adjustable coefficient from 0 to 10) for the drive/motor unit to avoid locking in the event of an overbraking fault. If the coefficient is equal to 0 the motor decelerates as fast as possible. This is used for conveyors with emergency stop electrical braking. A fast stop is achieved: - by configuring a normal stop as a fast stop (when a run command is over or a stop command occurs) - by enabling a logic input - by activating a command word bit v Fastest possible stop If the ramp divider coefficient is equal to 0 the motor decelerates as fast as possible. v DC injection stop This can be used to brake high-inertia machines at low speed or maintain torque on stopping. A DC injection stop is achieved: - by configuring a normal stop as a DC injection stop (when a run command is over or a stop command occurs) - by enabling a logic input - by activating a command word bit The DC value and the standstill braking time are adjustable.

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

171 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 174

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 b Motor thermal protection Motor thermal protection is provided by the drive: v directly, through PTC probes located in the motor windings v indirectly, via the integrated thermal relay. Indirect thermal protection is implemented via continuous calculation of its theoretical temperature rise. The microprocessor calculates the theoretical temperature rise of the motor based on various elements: v the operating frequency v the current taken by the motor v the operating time v the maximum ambient temperature around the motor (40°C) v the type of motor ventilation (self-cooled or force-cooled) Thermal protection can be adjusted from 0.5 to 1.2 times the nominal current, depending on the drive type. It must be adjusted to the nominal current indicated on the motor rating plate. Note: The motor thermal state memory returns to zero when the drive control part is switched off.

Trip time in seconds t

10 000 (a 2 h 45)

13 5

10

50 Hz

20

1 000 (a 16 min)

100 0,7

0,8

0,9

1

1,1

1,2

1,3

1,4

1,5 1,6 Motor current/ItH

Motor thermal protection curves v Self-cooled motors: The tripping curves vary with the motor frequency. v Force-cooled motors: Only the 50 Hz tripping curve should be considered, whatever the motor frequency. b Drive thermal protection The drive thermal protection is provided by a PTC probe mounted on the heatsink or integrated with the power module. b IGBT thermal protection The drive manages the switching frequency intelligently according to the IGBT temperature. If the drive’s current rating is exceeded (example: current higher than the nominal drive current for a zero stator frequency), an alarm is displayed and a timer increases for as long the alarm is present. b Machine protection Makes it possible to detect under and/or overload.

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

172 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 175

Functions (continued)

0

Variable speed drives for asynchronous motors

0

522168

Altivar 61

Term

RDY

+0.00Hz

0.0A

4-20mA LOSS Fallback spd Spd maintain Ramp stop Fast stop DC injection

Quick Configuration of the drive’s fault response b Configuring the drive’s fault response (fault management) Different responses can be configured for the drive in the event of a resettable fault occurring: v freewheel stop v drive switches to the fallback speed v drive maintains the speed at which it was operating when the fault occurred until the fault disappears v stop on ramp v fast stop v DC injection stop v no stop (alarm activated) List of resettable faults: v external fault v speed feedback loss v overspeed v output phase loss v auto-tuning fault v loss of 4-20 mA v PTC probe v drive overheating v motor overload if the thermal state is less than 100% v line overvoltage v overbraking v current/torque limit v IGBT overheating v communication faults (Modbus, CANopen and other communication networks), v process overload v process underload v PI supervision, v No flow. b Resetting resettable faults This can be used to remove the last fault using a logic input, command word bit or the STOP/RESET key on the graphic display terminal. The restart conditions after a reset to zero are the same as those of a normal power-up. List of resettable faults, see “Configuring the drive’s fault response”. Line supply undervoltage and input phase loss faults are reset automatically when the line supply is restored. Function suitable for applications where drives are difficult to access, for example, a drive placed on a moving part. b General reset (disables all faults) This function inhibits all faults, including thermal protection (forced operation), and can destroy the drive. Function suitable for applications where restarting may be crucial (conveyor in an oven, smoke extraction system, machines with solidifying products to be discarded). The function is enabled by a logic input. Fault monitoring is active if the logic input is at state 1. All faults are reset on a change of state of the logic input. Note: Use of this function invalidates the guarantee.

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

173 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 176

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 b Automatic restart This enables the drive to be restarted automatically after it has locked in fault mode if the relevant fault has disappeared and the other operating conditions permit a restart. This restart is performed by a series of automatic attempts separated by increasingly longer waiting periods of 1 s, 5 s, 10 s then 1 minute for the rest. The options for the restart process’s duration are 5, 10 and 30 min., 1, 2, 3 hours and an unlimited time. If the drive has not restarted after the configured time, it will lock and the procedure is abandoned until it has been powered off and on again. The faults which allow the drive to be restarted in this way are: v line overvoltage v motor thermal overload v drive thermal overload v d.c. bus overvoltage v line phase failure v external fault v loss of 4-20 mA v PTC probe v serial link v current or torque limit v output phase loss v line voltage too low. For this fault, the function is always active, even if it is not configured. v process overload v process underload v PI supervision v no flow. v fault caused by CANopen, Modbus or other commmunication networks. These faults are reset automatically as soon as the command word or frequency reference is sent to the drive. For these types of fault, the relay configured as a fault relay remains activated if the function is configured. The speed reference and operating direction must be maintained for this function. This function is suitable for machines or installations which are in continuous operation or unmonitored, and where a restart will not endanger equipment or personnel in any way. b PTC probe protection The probes can be connected directly to the drive control card or to the I/O option cards. The way in which a temperature fault is recorded by the drive can be configured: v permanent record v only recorded when the drive’s power section is switched on v only recorded when the motor is running b IGBT testing When enabled, this function tests every IGBT and the motor connections in order to detect a short-circuit or an open circuit. This test is run every time the drive is powered on and before each motor start. This function must not be enabled with machines with fast cycles in order to preserve the time for recording run commands. b Resetting operating time to zero The drive operating and power-up times can be reset. b External fault This function can lead to the drive locking if a fault occurs in the machine. This fault is flagged on the drive display unit. The fault is flagged if the signal is at 1 or 0, according to the function configuration.

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

174 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 177

Functions (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 b Line contactor control This can be used on each run command to close the line contactor and open it when the motor is no longer on. The drive control section must be powered without fail by an external 24 V c source. This function must be used for simple sequences with a low number of Start/Stop operations (Start/Stop cycle longer than 60 seconds). Emergency stop Line 3 a Run

K10

LO/Rp

0

LIn

L3 W

Forward or reverse

K11

P24

L2 V

LIp

L1

ATV 61

U

KM1

K11 K10

M

24 V

0V

3

24 V c external supply

After a run command, if the line contactor is not closed the drive will lock after an adjustable period of time. b Forced local mode Forced local mode imposes control via the terminals or graphic display terminal and disables all other control modes. Switching to forced local mode may be activated via: v a logic input v a function key on the graphic display terminal The following references and commands are available for forced local mode: v references AI1, AI2, etc. and command via logic inputs v reference and command via the graphic display terminal

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

175 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 178

Functions

0

Variable speed drives for asynchronous motors

0

Altivar 61

Function compatibility table b Configurable I/O The table below lists the incompatibilities between the functions and indicates the priority functions: Stop functions have priority over run commands. The Power Removal safety function takes priority over all other functions. The selection of functions is limited: v By the number of drive I/O which can be reassigned: if necessary, add an I/O extension card. v By the incompatibility of certain functions with one another Functions

PID regulator

Preset speeds

JOG operation

Synchronous motor

PID regulator

Preset speeds

A JOG operation

X Synchronous motor

+/- speed (1)

+/- speed around a reference

Operation on the references

(2)

A

A

Freewheel stop

Fast stop

DC injection stop

(1) Excluding special use with reference channel Fr2. (2) Only the multiplier reference is incompatible with the PID regulator. (3) Priority is given to the first of these two stop modes to be activated. Incompatible functions Compatible functions

Priority functions (functions which cannot be active at the same time)

X

The arrow indicates which function has priority. Example: the "Freewheel stop" function has priority over the "Fast stop" function

N/A

176 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 179

0

0

+/- speed (1)

+/- speed around a reference

Operation on the references

Freewheel stop

Fast stop

DC injection stop

(2)

X X

X

X

A A

(3)

(3)

177 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com