Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 29 of 30

Variable speed drives Altivar 61 Catalogue: Functions, pages 200 to 207

Pages 200 to 207 of 211, from Variable speed drives Altivar 61 Catalogue

The original document is the PDF (4.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Telemecanique Altivar 61 ATV61, Schneider Altivar 61 ATV61 and Square D Altivar 61 ATV61

Page 200

Connections, references

Starters, drives and communication

0

0

Communication via Modbus Plus network

Modbus Plus wiring system Quantum

10

4 Network # 2

Premium

11 8 10

4

10

11

4

5

4

11

Network # 1

12

4

2

12 6

6

11

4

13

7 RS 232

1

3

RS 485

9 Fibre optic link

1

ATV 71

ATV 61

13

13

ATV 31

ATS 48

Quantum

Modbus Plus bus connection elements (1) Cards and gateways Description

Used with

ATV 61, ATV 71 Communication cards equipped with one 9-way female SUB-D connector ATS 48, ATV 31 Modbus Plus/Modbus gateway 4 RS 232 ports power supply 115…220 Va RS 232/RS 485 interface ATS 48, ATV 31 power supply 24 V c, 20 mA (2)

Code

Reference

1

VW3 A3 302

Weight kg 0.300

2

NW BM85000

3.158

3

XGS Z24

0.105

Code

Reference

Weight kg 0.230

Connection accessories Description

Use

Modbus Plus tap For connecting via a tap junction 4 990 NAD 230 00 (IP 20) Modbus Plus in-line connector Gateway, bridge and repeater 5 AS MBKT 085 0.035 Connector with Modbus Plus Bridge and repeater 6 AS MBKT 185 0.260 terminator (sold in lots of 2) Modbus Plus electrical repeater Extension beyond 450 m or 7 NW RR85 001 2.677 up to 64 subscribers Modbus Plus bridge with Connection of 4 networks maximum 8 NW BP85 002 2.813 4 ports Line/station fibre optic – 9 490 NRP 254 00 2.856 repeater NW NRP 253 00 2.863 Point-to-point fibre optic Used to connect an electrical segment to – repeater the fibre optic segment (3000 m maximum) Wiring tool Inserting trunk and drop cables in a – 043 509 383 3.000 990 NAD 230 00 tap (1) To order other connection elements, please consult our specialist “Automation platform Modicon Premium and Unity - PL7 software” and “Automation platform Modicon Quantum” catalogues. (2) Please consult our specialist “Interfaces, I/O splitter boxes and power supplies” catalogue.

Presentation: page 196

Characteristics: page 197

198 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 201

References (continued)

0

Starters, drives and communication

0

Communication via Modbus Plus network

Modbus Plus bus connection elements (continued) (1) Cables Description Trunk cables for Modbus Plus

Drop cables One 9-way male SUB-D connector and one stripped end

Used From 990 NAD 230 00 Modbus Plus tap

Code To 10 990 NAD 230 00 Modbus Plus tap, AS MBKT 085 Modbus Plus in-line connector, Modbus Plus connector with terminators AS MBKT 185

Premium, Quantum 990 NAD 230 00 Modbus Plus tap PLCs, NW BP85 002 Modbus Plus bridge with 4 ports, 490 NRP 253 00 line/ station fibre optic repeater ATV 61, ATV 71 990 NAD 230 00 (+ VW3 A3 302 Modbus Plus tap communication card)

11

12

Length m 30.5

Reference 490 NAA 271 01

Weight kg 1.833

152.5

490 NAA 271 02

10.135

305

490 NAA 271 03

18.940

457

490 NAA 271 04

30.000

1525

490 NAA 271 06

112.950

2.4

990 NAD 211 10

0.169

6

990 NAD 211 30

0.459

2.4

990 NAD 219 10

0.142

6

990 NAD 219 30

0.465

RS 232/RS 485 13 3 VW3 A8 306 D30 0.115 ATS 48, ATV 31, interface NW BM85000 Modbus Plus/ Modbus gateway (1) To order other connection elements, please consult our specialist “Automation platform Modicon Premium and Unity - PL7 software” and “Automation platform Modicon Quantum” catalogues.

Cable for Modbus 1 RJ45 connector and one stripped end

Presentation: page 196

Characteristics: page 197

Connections: page 198

199 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 202

Starters, drives and communication

Presentation, characteristics, connections,

0

Communication via Uni-Telway bus

0

Presentation The Uni-Telway bus is a standard means of communication between control system components (PLCs, HMI terminals, supervisors, variable speed drives, numerical controllers, etc).

Premium

TSX Micro

The Uni-Telway bus requires a master station (Premium, TSX Micro PLCs) which manages the allocation of bus access rights to the various connected slave stations (HMI terminals, variable speed drives, etc). The slave stations can communicate with one another without programming the master station. An industrial HMI terminal (Magelis type) can be connected directly to the bus and can be used to adjust drives without developing applications specific to the PLC.

Uni-Telway bus

The Altivar 61 and Altivar 71 variable speed drives can be connected to the Uni-Telway bus via a communication card VW A3 303. XBT Magelis ATV 71

ATV 61

Characteristics Structure

Topology Physical interface Link Access method Transmission mode Data rate Medium Number of stations Length of bus Tap links UNI-TE

Services

Bus RS 485 isolated Multidrop Master/slave type Asynchronous transmission in baseband 4.8…19.2 Kbps Double shielded twisted pair 28 maximum 1000 m maximum excluding tap links 20 m maximum Request/response of up to 240 bytes (1) initiated by any connected station. Unsolicited point-to-point data of up to 240 bytes (1) without confirmation report, initiated by any connected station. Broadcast messages of up to 240 bytes (1) initiated by the master station. Transparent communication, via the master station, with any X-WAY architecture. Diagnostics, debugging, adjustment, programming of PLCs. Check character on each frame, acknowledgement and, if required, repetition of messages ensure security of transmission. The bus status table, transmission error counters and station status can be accessed on each station.

Other functions Security Monitoring

Uni-Telway bus wiring system TSX Micro (Terminal port)

Premium + TSX SCY 21601

4 10

5

8

5

8

11

6

11

1

7

9

11

1

8

1 3 Premium + TSX SCP 114

ATV 61

ATV 71

ATV 71

(1) Limited to 128 bytes with the Premium and TSX Micro PLC terminal port.

200 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 203

References

0

Starters, drives and communication

0

Communication via Uni-Telway bus

Uni-Telway bus connection elements (1) Cards, kit and module Description

Used with

Code

Protocol

Reference

Communication card card equipped with a 9-way female SUB-D connector RS 485 type III PCMCIA card (compatible with RS 422) 1.2...19.2 Kbps Communication module

ATV 61, ATV 71

1

Uni-Telway, Modbus

VW3 A3 303

Weight kg 0.300

Premium, Atrium, TSX Micro PLCs or TSX SCY 21601 module Premium or Atrium PLC

3

Uni-Telway, Modbus, character mode Uni-Telway, Modbus, character mode

TSX SCP 114

0.105

TSX SCY 21601

0.360

Use

Code

4

533153

Connection accessories Description

533155

TSX SCA 62

Reference

2-channel junction box, trunk 5 Subscriber socket cable extension and line Two 15-way female terminator SUB-D connectors and 2 screw terminals Tap junction Junction box, trunk cable 6 3 screw terminals extension and line terminator Terminal port connection box Connection of a TSX Micro or 7 with integrated cable of Premium PLC via the PLC length 1 m terminal port and line terminator

TSX SCA 62

Weight kg 0.570

TSX SCA 50

0.520

TSX P ACC 01

0.690

Cables Description Uni-Telway double shielded twisted pair cables

533154

TSX SCA 50

TSX P ACC 01

Cables for isolated RS 485 tap link

Cable for Uni-Telway and Modbus bus 2 male SUB-D connectors, 9 and 15-way

Used Code From To 8 TSX SCA 62 TSX SCA 50 subscriber junction box, socket, TSX SCA 62 TSX SCA 50 subscriber junction box, socket, TSX P ACC 01 TSX P ACC 01 terminal port terminal port connection box connection box TSX SCP 114 card

TSX SCA 50 junction box TSX SCA 62 subscriber socket TSX SCA 50 Integrated junction box channel (channel 0) of TSX SCA 62 TSX SCY 2160 subscriber 1 module socket TSX SCA 62 ATV 61, subscriber ATV 71 (+VW3 A3 303 socket communication card)

Length m 100

Reference TSX CSA 100

Weight kg 5.680

200

TSX CSA 200

10.920

500

TSX CSA 500

30.000

9

3

TSX SCP CU 4030

0.160

9

3

TSX SCP CU 4530

0.180

10

3

TSX SCP CU 6030

0.180

10

3

TSX SCY CU 6530

0.200

11

3

VW3 A8 306 2

0.150

(1) To order other elements for connection to the Fipio bus, please consult our specialist “Automation platform Modicon Premium and Unity - PL7 software” and “Automation platform Modicon TSX Micro and PL7 software” catalogues.

201 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 204

Starters, drives and communication

Presentation, description, setting-up

0

0

Communication gateways LUF P

Presentation Communication gateways LUF P allow connection between Modbus and field buses such as Fipio, Profibus DP or DeviceNet. After configuration, these gateways manage information which can be accessed by the Modbus bus and make this information available for read/write functions (command, monitoring, configuration and adjustment) on the field buses. An LUF P communication gateway consists of a box which can be clipped onto a 35 mm omega rail, allowing connection of up to 8 Slaves connected on the Modbus bus. Example of architecture Configuration of gateway by PC

Model U starter-controllers

LUF P

Fipio Profibus DP DeviceNet

(1) Modbus

561511

ATS 48 ATV 31

1 (1) Connection kit for PowerSuite software workshop.

Description Front panel of the product 1 LED indicating : - communication status of the Modbus buses, - gateway status, - communication status of the Fipio, Profibus DP or DeviceNet bus. 2 Connectors for connection to Fipio, Profibus DP or DeviceNet buses.

2

561512

Underside of product 3 RJ45 connector for connection on the Modbus bus 4 RJ45 connector for link to a PC 5 c 24 V power supply 3

Software set-up

4

For the Fipio bus, software set-up of the gateway is performed using either PL7 Micro/Junior/Pro software or ABC Configurator software. For the Profibus DP and DeviceNet buses, software set-up is performed using ABC Configurator. This software is included: b in the PowerSuite software workshop for PC (see page 180), b in the TeSys model U user's manual.

5

Characteristics, references: page 203

Dimensions: page 203

202 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 205

Characteristics, references, dimensions

Starters, drives and communication 0

0

Communication gateways LUF P

Characteristics Bus type Environment Ambient air temperature Degree of protection Electromagnetic compatibility

Conforming to IEC 60664 Around the device

Emission Immunity Number of Modbus slaves which can be connected Connection Modbus To a PC Field bus

Supply Consumption

Max. Typical

Indication/diagnostics Services

Profile Command Monitoring Configuration and adjustment

Fipio Profibus DP DeviceNet Degree of pollution: 2 °C + 5…+ 50 IP 20 Conforming to IEC 50081-2: 1993 Conforming to IEC 61000-6-2: 1999 y8 By RJ45 connector conforming to Schneider Electric RS485 standard By RJ45 connector, with PowerSuite connection kit By SUB D9 female By SUB D9 female By 5-way removable connector connector screw connector V External supply, c 24 ± 10 % mA 280 mA 100 By LED on front panel FED C32 or FED C32P – – 26 configurable words (1) 122 configurable words 256 configurable words 26 configurable words (1) 122 configurable words 256 configurable words By gateway mini messaging facility (PKW) (1) If the gateway is configured using PL7 and not ABC Configurator, the I/O capacity is limited to a total of 26 words.

References Description

For use with

With bus type

Reference

Weight kg 0.245 0.245 0.245

Communication gateways

TeSys Model U starter-controllers, Altistart 48, Altivar 31

Fipio/Modbus Profibus DP/Modbus DeviceNet/Modbus

LUF P1 LUF P7 LUF P9

Description

For use with

Connectors

Reference

Connection cables

Modbus (2)

Length m 3

Fipio

0.3 1 3 –

1 RJ45 type connector and one end with stripped wires 2 RJ45 type connectors 2 RJ45 type connectors 2 RJ45 type connectors 1 SUB-D 9 male connector

VW3 A8 306 R03 VW3 A8 306 R10 VW3 A8 306 R30 TSX FP ACC12

0.050 0.050 0.150 0.040

–

1 SUB-D 9 male connector

490 NAD 911 04

–

–

1 SUB-D 9 male connector

490 NAD 911 03

–

822631

Connection accessories

822713

TSX FP ACC 12

Connectors

Profibus mid line Profibus line end

490 NAD 911 03

Weight kg VW3 A8 306 D30 0.150

Documentation Description

Medium

User's manual for TeSys model U range (3)

CD-Rom

Language

Reference

Weight kg 0.022

Multilingual: English, French, German, Italian, LU9 CD1 Spanish (2) See pages 192 and 195. (3) This CD-Rom contains user's manuals for AS-Interface and Modbus communication modules, multifunction control units and gateways, as well as for the gateway programming software, ABC Configurator.

=

120

=

Dimensions

75

Presentation, description: page 202

27

Setting-up: page 202

203 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 206

Starters, drives and communication

Presentation, description, setting-up

0

0

Communication gateway LA9 P307

Presentation Communication gateway LA9 P307 provides connection between the Profibus DP and Modbus buses. It is a Slave on the Profibus DP bus and Master on the Modbus bus. It manages information present on the Modbus bus to make it available for read/write functions in the Master PLC on the Profibus DP bus. Gateway LA9 P307 consists of a box which can be clipped onto a 35 mm omega rail. It manages up to15 Slaves on the Modus bus. Example of architecture Profibus DP

1

3

4

3

4

2 Modbus

7 5

5

6

LT6 P ATS 48

6

LT6 P

ATV 31

1 Gateway LA9 P307, 2 Tap-off cable VW3 P07 306 R10, 3 Modbus splitter box LU9 GC3, 4 Cable TSX CSA p00, 5 Tap-link cable VW3 A8 306 Rpp, 6 Tap-link cable VW3 A8 306 D30, 7 Line end adapter VW3 A8 306 RC.

562298

Description Gateway LA9 P307 comprises: 1 A SUB-D 9-way female connector for connection to the Profibus DP bus, 2 A line end adapter on the Profibus DP bus, 3 Gateway address coding on the Profibus DP bus, 4 Status signalling LED, 5 RJ 45 female connector for connection on the Modbus bus, 6 c 24 V power supply.

1 2 3 4 5 6

Software set-up The gateway is configured using the standard software tools for the Profibus bus. For the Premium automation platform, use SYCON configurator software. The user's manual (.PDF) and the gateway description file (.GSD) are supplied on diskette with the gateway.

Characteristics, references: page 205

Dimensions: page 205

204 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 207

Starters, drives and communication

Characteristics, references, dimensions

0

Communication gateway LA9 P307

0

Characteristics Environment Conforming to IEC 60664 Ambient air temperature Around the device Degree of protection Number of Modbus slaves which can be connected Connection on Modbus Profibus Supply Consumption Indication/diagnostics Services Command Monitoring Configuration and adjustment

°C mA

Degree of pollution: 2 0...+ 50 IP 20 15 RJ 45 connector SUB-D 9-way female connector External supply, c 24 V ± 20 % 150 on c 24 V By LED 16 words 16 words By gateway mini messaging facility (PKW)

562299

References Description

For use with

Reference

Profibus DP/Modbus communication gateway

LT6 P ATS 48 ATV 31

LA9 P307

Weight kg 0.260

Description

For use with

RJ 45 cable with stripped wires

Screw terminal block - T-junction box TSX SCA 50 - Y-junction subscriber socket TSX SCA 62

Length Reference m 3 VW3 A8 306 D30

Weight kg 0.150

SUB-D connector (to be ordered separately) - LT6 P (SUB-D 9 female) RJ 45-RJ 45 cable

ATS 48 ATV 31 Modbus splitter box LU9 GC3

1

VW3 P07 306 R10

Connectors

Profibus mid line

–

490 NAD 911 04

–

Profibus line end

–

490 NAD 911 03

–

822713

LA9 P307

490 NAD 911 03

0.050

Dimensions

93

LA9 P307

76,5

Presentation, description: page 204

35

Setting-up: page 204

205 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com