Variable speed drives Altivar 61 Catalogue, pages 18 to 20

Pages 18 to 20 of 211: Operation; Altivar 61 Supply voltage 200…240V 50/60 Hz

The original document is the PDF (4.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Telemecanique Altivar 61 ATV61, Schneider Altivar 61 ATV61 and Square D Altivar 61 ATV61

Page 18

Operation

0

Variable speed drives for asynchronous motors

0

Altivar 61

Torque characteristics (typical curves) The curves opposite define the available continuous torque and transient overtorque for both force-cooled and self-cooled motors. The only difference is in the ability of the motor to provide a high continuous torque at less than half the nominal speed. Open loop applications 1 Self-cooled motor: continuous useful torque (1) 2 Force-cooled motor: continuous useful torque 3 Overtorque for 60 seconds maximum for ATV 61Wppppp (UL Type 12/IP 54 drives) 4 Overtorque for 60 seconds maximum for ATV 61Hppppp (UL Type 1/IP 20 drives) 5 Torque in overspeed at constant power (2)

T/Tn 2,25

2 1,75 1,50

4 3

1,30 1,25 1,20

2

1 0,95

5

0,75

1 0,50 0,25 0 0

25/30

50/60

75/90

100/120

Hz

Open loop applications

Motor thermal protection Altivar 61 drives feature thermal protection designed specifically for self-cooled or force-cooled variable speed motors. The drive calculates the motor thermal state even when it is switched off. This motor thermal protection is designed for a maximum ambient temperature of 40°C around the motor. If the temperature around the motor exceeds 40°C, thermal protection should be provided directly by thermistor probes (PTC) integrated in the motor. The probes are managed directly by the drive. (1) For power ratings y 250 W, motor derating is 20% instead of 50% at very low frequencies. (2) The motor nominal frequency and the maximum output frequency can be adjusted from 10 to 500 Hz or 1000 Hz, depending on the rating. Check the mechanical overspeed characteristics of the selected motor with the manufacturer.

Presentation: pages 4 to 7

References: pages 18 to 21

Dimensions: pages 90 to 111

Schemes: pages 112 to 127

Functions: pages 148 to 175

16 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 19

Operation (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61

Special uses Using Altivar 61 drives with synchronous motors Altivar 61 drives are also suitable for powering synchronous motors (sinusoidal electromotive force) in open loop mode and are used to achieve performance levels comparable to those associated with an asynchronous motor in sensorless flux vector control. This drive/motor combination makes it possible to obtain remarkable speed accuracy and maximum torque even at zero speed. The design and construction of synchronous motors are such that they offer enhanced power density and highspeed performance in a compact unit. Drive control for synchronous motors does not cause stalling.

In1

Altivar 61

Connecting motors in parallel The nominal current of the drive must be greater than or equal to the sum of the currents of the motors to be controlled. In this case, provide external thermal protection for each motor using probes or thermal overload relays. For cable runs over a certain length, taking account of all the tap links, it is advisable either to install an output filter between the drive and the motors or to use the overvoltage limitation function.

M1

Output filter

In2

M2

Inx

If several motors are used in parallel, there are 2 possible scenarios: b The motors have equal power ratings, in which case the torque characteristics will remain optimized after the drive has been configured b The motors have different power ratings, in which case the torque characteristics will not be optimized for all the motors.

Mx

In drive > In1 + In2 +…Inx

Connecting motors in parallel

Switching the motor at the drive output The drive can be switched when locked or unlocked. If the drive is switched on-the-fly (drive unlocked), the motor is controlled and accelerates until it reaches the reference speed smoothly following the acceleration ramp. This use requires configuration of the automatic catching a spinning load ("catch on the fly") and the motor phase loss on output cut functions.

KM1 Altivar 61

M

Typical applications: loss of safety circuit at drive output, bypass function, switching of motors connected in parallel. On new installations, it is recommended that the Power Removal safety function is used.

N t t2 t1 1 t

KM1 0 KM1: Output contactor t1: deceleration without ramp (freewheel) t2: acceleration with ramp N: Speed

Example of loss of output contactor

Test on a low power motor or without a motor In a testing or maintenance environment the drive can be checked without having to switch to a motor with the same rating as the drive (particularly useful in the case of high power drives). This use requires deactivation of motor phase loss function.

Presentation: pages 4 to 7

Dimensions: pages 90 to 111

References: pages 18 to 21

Schemes: pages 112 to 127

Functions: pages 148 to 175

17 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 20

References

0

Variable speed drives for asynchronous motors

0

Altivar 61 Supply voltage 200…240V 50/60 Hz

UL Type 1/IP 20 drives Motor Power indicated on plate (1)

kW

HP

Line supply Line current (2)

Apparent power

200 V 240 V A A

240 V kVA

Maximum prospective line Isc

Altivar 61 Max. continuous current (1)

kA

230 V A

Max. transient current for 60 s

Reference (3)

A

Weight kg

Single phase supply voltage: 200…240 V 50/60 Hz DF534520

0.37 0.75 1.5 2.2 3 4 5.5

0.5 1 2 3 – 5 7.5

6.9 12 18.2 25.9 25.9 34.9 47.3

5.8 9.9 15.7 22.1 22 29.9 40.1

1.4 2.4 3.7 5.3 5.3 7 9.5

5 5 5 5 5 5 22

3.6 9.6 13.2 16.4 21 33 39.6

5.7 9.6 13.2 16.4 21 33 39.6

ATV 61H075M3 (4) ATV 61HU15M3 (4) ATV 61HU22M3 (4) ATV 61HU30M3 (4) ATV 61HU40M3 (4) (5) ATV 61HU55M3 (4) (5) ATV 61HU75M3 (4) (5)

3.000 3.000 3.000 4.000 4.000 5.500 5.500

5.7 9.6 13.2 16.4 21 33 39.6 64.8 79.2 90 105.6 144 172.8 211.2 265.2 313.5 394.9

ATV 61H075M3 (4) ATV 61HU15M3 (4) ATV 61HU22M3 (4) ATV 61HU30M3 (4) ATV 61HU40M3 (4) ATV 61HU55M3 (4) ATV 61HU75M3 (4) ATV 61HD11M3X (4) (6) ATV 61HD15M3X (4) (6) ATV 61HD18M3X (4) (6) ATV 61HD22M3X (4) (6) ATV 61HD30M3X (4) (6) ATV 61HD37M3X (4) (6) ATV 61HD45M3X (4) (6) ATV 61HD55M3X (6) (7) (8) ATV 61HD75M3X (6) (7) (8) ATV 61HD90M3X (6) (7) (8)

3.000 3.000 4.000 4.000 4.000 5.500 7.000 9.000 9.000 19.000 19.000 39.000 39.000 39.000 59.000 72.000 72.000

ATV 61H075M3 DF534521

Three phase supply voltage: 200…240 V 50/60 Hz

DF534522

ATV 61HU22M3Z

ATV 61HD37M3X

0.75 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90

1 2 3 – 5 7.5 10 15 20 25 30 40 50 60 75 100 125

6.1 11.3 15 19.3 25.8 35 45 53.3 71.7 77 88 124 141 167 200 271 336

5.3 9.6 12.8 16.4 22.9 30.8 39.4 45.8 61.6 69 80 110 127 147 173 232 288

2.2 4 5.3 6.8 9.5 12.8 16.4 19 25.6 28.7 33.3 45.7 52.8 61.1 71.9 96.4 119.7

5 5 5 5 5 22 22 22 22 22 22 22 22 22 35 35 35

4.8 8 11 13.7 17.5 27.5 33 54 66 75 88 120 144 176 221 285 359

(1) These values are for a nominal switching frequency of 12 kHz up to ATV 61HD45M3X or of 2.5 kHz for ATV 61HD55M3X…HD90M3X drives for use in continuous operation. The switching frequency is adjustable from 1…16 kHz up to ATV 61HD45M3X, from 2.5…12 kHz for ATV 61HD55M3X and from 2.5…8 kHz for ATV 61HD75M3X, HD90M3X drives. Above 2.5 or 12 kHz, depending on the rating, the drive reduces the switching frequency itself in the event of an excessive temperature rise. For continuous operation above the nominal switching frequency, derate the nominal drive current, see derating curves on pages 138 to 141. (2) Typical value for the indicated motor power and for the maximum prospective line Isc. (3) The ATV 61HD55M3X…HD90M3X drives come in a reinforced version as standard, enabling them to operate in particular environmental conditions; see the enviromental conditions on page 9. To order the reinforced version of the ATV 61HpppM3 and ATV 61HD11M3X...HD45M3X drives, add at the end of the reference: - S337 for ATV 61Hppp M3. Example: ATV 61H075M3 becomes ATV 61H075M3S337. - 337 for ATV 61H pppM3X. Example: ATV 61HD11M3X becomes ATV 61HD11M3X337. If a reinforced version of the drive is supplied for particular environmental conditions, it must come with a remote graphic display terminal. (4) All drives come with a remote graphic display terminal. The ATV 61H pppM3 and ATV 61HD11M3X...ATV 61HD45M3X drives can be ordered without a graphic display terminal. In this case, add a Z at the end of the reference. They will then come equipped with an integrated 7-segment display terminal. Example: ATV 61H075M3 without a graphic display terminal becomes ATV 61H075M3Z. (5) A line choke must be used, see page 68. (6) Drive supplied without EMC filter. EMC filters are available as an option, see page 76. (7) Drive supplied as standard with a DC choke, which must be used when connecting the drive to the 3-phase supply. For connections to the DC bus, the drive can be ordered without a DC choke by adding D at the end of the reference. Example: ATV 61HD55M3X becomes ATV 61HD55M3XD. (8) Drive supplied without plate for EMC mounting. It is included in the UL Type 1 or IP 31 conformity kits, to be ordered separately, see pages 24 and 25. Note: Consult the tables summarizing the possible combinations: drives, options and accessories, see pages 84 to 87.

Presentation: pages 4 to 7

Characteristics: pages 8 to 15

Dimensions: pages 90 to 95

Schemes: pages 112 to 127

Functions: pages 148 to 175