Page 24

Presentation, references

0

Variable speed drives for asynchronous motors

0

Altivar 61 Option: accessories Adapter for 115 V a logic inputs This adapter is used to connect 115 V a logic signals to the logic inputs on the drive or an I/O extension card. 7 logic inputs with capacitive impedance at 60 Hz of 0.22 µF are available for connecting the logic signals: b Max. current: 200 mA b Response time: 5 ms to change from state 0 to state 1, 20 ms to change from state 1 to state 0 b Logic state 0 for a voltage below 20 V, logic state 1 for a voltage between 70 V and 132 V The power supply must be provided by a 115 V a external power supply (min. 70 V, max. 132 V). References Description

Reference

Adapter for 115 V a logic inputs

VW3 A3 101

Weight kg –

533236

Control card fan kit 1

This kit is required for ATV 61HD18M3X…HD45M3X and ATV 61HD22N4…HD75N4 drives. It enables the drive to operate at an ambient temperature of 50°C to 60°C, for example, if it is mounted in an IP 54 enclosure. The circulation of air around the electronic cards prevents the formation of hot spots. Check the derating to be applied to the drive nominal current, see derating curves on pages 138 to 143. The kit 1 is mounted on the upper part of the drive. It is powered by the drive. It consists of: b A fan subassembly b Fixing accessories b A manual References For drives

Reference

ATV 61HD18M3X, HD22M3X ATV 61HD22N4 ATV 61HD30N4, HD37N4

VW3 A9 404

Weight kg –

VW3 A9 405

–

ATV 61HD30M3X…HD45M3X

VW3 A9 406

–

ATV 61HD45N4…HD75N4

VW3 A9 407

–

Control card fan kit

Dimensions: page 95

22 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 25

Presentation, references (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 Option: accessories

Kit for flush-mounting in a dust and damp-proof enclosure

533254

This kit can be used to mount the power part of the drive outside the enclosure (IP 54 degree of protection), which reduces the power dissipated into the enclosure, see page 146. It is available for ATV 61HpppM3, ATV 61HpppM3X, ATV 61HD55M3XD…ATV 61HD90M3XD, ATV 61HD90N4…HC31N4 and ATV 61HD90N4D…ATV 61HC31N4D drives. With this type of mounting, the maximum internal temperature in the enclosure can then reach 60°C without it being necessary to derate the drive current. Between 50°C and 60°C, a control card fan kit must be used for the ATV 61HD18M3X…HD45M3X and ATV 61HD22N4…HD75N4 drives to prevent hot spots, see page 22. The back of the enclosure must be drilled and cut out for this type of mounting.

ATV 61HU75N4 flush-mounted

The kit consists of: b A metal frame of the right size for the drive rating b Corner pieces b Seals b A fan support. This can be used to move the fans so that they can be accessed from the front of the enclosure b Fixing accessories b A cutting and drilling template b A manual.

533255

References For drives

ATV 61HC31N4D flush-mounted

Reference

Weight kg 2.700

ATV 61H075M3…HU15M3 VW3 A9 501 ATV 61H075N4…HU22N4 ATV 61HU22M3…HU40M3 VW3 A9 502 3.100 ATV 61HU30N4, HU40N4 ATV 61HU55M3 VW3 A9 503 3.700 ATV 61HU55N4, HU75N4 ATV 61HU75M3 VW3 A9 504 4.600 ATV 61HD11N4 ATV 61HD11M3X, HD15M3X VW3 A9 505 4.900 ATV 61HD15N4, HD18N4 ATV 61HD18M3X, HD22M3X VW3 A9 506 3.900 ATV 61HD22N4 ATV 61HD30N4, HD37N4 VW3 A9 507 4.200 ATV 61HD30M3X…HD45M3X VW3 A9 508 4.900 ATV 61HD45N4…HD75N4 VW3 A9 509 5.200 VW3 A9 510 (1) 5.100 ATV 61HD55M3X, HD75M3X ATV 61HD55M3XD, HD75M3XD ATV 61HD90N4, HC11N4, ATV 61HD90N4D, HC11N4D VW3 A9 511 (1) 3.600 ATV 61HD90M3X ATV 61HD90M3XD ATV 61HC13N4 ATV 61HC13N4D ATV 61HC16N4 VW3 A9 512 (1) 4.300 ATV 61HC16N4D ATV 61HC22N4 VW3 A9 513 (1) 4.700 ATV 61HC22N4D ATV 61HC25N4, HC31N4 Without braking unit VW3 A9 514 (1) 4.700 ATV 61HC25N4D, HC31N4D With braking unit VW3 A9 515 (1) 4.700 (1) The procedure for cutting out and drilling the enclosure varies depending on whether the DC choke is present or not: - Drives supplied with DC choke: ATV 61HD55M3X…HD90M3X, ATV 61HD90N4…HC31N4, - Drives supplied without DC choke: ATV 61HD55M3XD…HD90M3XD, ATV 61HD90N4D…HC31N4D. See pages 97 and 98.

Dimensions: pages 96 to 98

23 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 26

Presentation, references (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 Option: accessories

534544

Kit for UL Type 1 conformity (mounting outside the enclosure) When the drive is mounted directly on a wall outside the enclosure, this kit can be used to ensure UL Type 1 conformity when connecting the cables with a tube. The shielding is connected inside the kit. For ATV 61HpppM3, ATV 61HD11M3X…HD45M3X and ATV 61H075N4 …HD75N4 drives, the kit consists of: b All the mechanical parts 1 including a pre-cut plate 2 for connecting the tubes 3 b Fixing accessories b A manual.

1

2

For ATV 61HD55M3X…HD90M3X and ATV 61HD90N4…HC31N4 drives, the kit consists of: b An IP 54 casing 4 used to maintain the IP 54 degree of protection for the power part b An EMC plate 5 b A UL Type 1 cover 7 b A pre-drilled plate 6 for connecting the tubes 3 b Fixing accessories b A manual.

3

534545

References

7

4

5

6

For drives

Reference

ATV 61H075M3…HU15M3 ATV 61H075N4…HU22N4 ATV 61HU22M3…HU40M3 ATV 61HU30N4, HU40N4 ATV 61HU55M3 ATV 61HU55N4, HU75N4 ATV 61HU75M3 ATV 61HD11N4 ATV 61HD11M3X, HD15M3X ATV 61HD15N4, HD18N4 ATV 61HD18M3X, HD22M3X ATV 61HD22N4 ATV 61HD30N4, HD37N4 ATV 61HD30M3X…HD45M3X ATV 61HD45N4…HD75N4 ATV 61HD55M3X, HD75M3X ATV 61HD90N4, HC11N4 ATV 61HD90M3X ATV 61HC13N4 ATV 61HC16N4 ATV 61HC22N4 ATV 61HC25N4, HC31N4

VW3 A9 201

Weight kg 1.300

VW3 A9 202

1.500

VW3 A9 203

1.800

VW3 A9 204

2.000

VW3 A9 205

2.800

VW3 A9 206

4.000

VW3 A9 207 VW3 A9 217 VW3 A9 208 VW3 A9 209

5.000 7.000 7.000 9.400

VW3 A9 210

11.800

VW3 A9 211 VW3 A9 212 VW3 A9 213 VW3 A9 214

11.600 14.600 19.500 19.500

Without braking unit With braking unit

3

UL Type 1 conformity kits

Dimensions: pages 99 and 100

24 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 27

Presentation, references (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 Option: accessories

533326

Kits for IP 21 or IP 31 conformity (mounting outside the enclosure) When the drive is mounted directly on a wall outside the enclosure, this kit can be used to ensure conformity with IP 21 or IP 31 degree of protection when connecting the cables with a cable gland. The shielding is connected inside the kit. For ATV 61HpppM3, ATV 61HD11M3X…HD45M3X and ATV 61H075N4…HD75N4 drives, the kit conforms to IP 21 degree of protection. It consists of: b All the mechanical parts 1 including a drilled plate 2 for attaching the cable glands 3 b Fixing accessories b A manual. For ATV 61HD55M3X…HD90M3X and ATV 61HD90N4…HC63N4 drives, the kit conforms to IP 31 degree of protection. It consists of: b An IP 54 casing 4 used to maintain the IP 54 degree of protection for the power part b An EMC plate with cable clips 5 b An IP 31 cover 6 b Fixing accessories b A manual.

1

2

3 References

533327

For drives

6

4

ATV 61H075M3…HU15M3 ATV 61H075N4…HU22N4 ATV 61HU22M3…HU40M3 ATV 61HU30N4, HU40N4 ATV 61HU55M3 ATV 61HU55N4, HU75N4 ATV 61HU75M3 ATV 61HD11N4 ATV 61HD11M3X, HD15M3X ATV 61HD15N4, HD18N4 ATV 61HD18M3X, HD22M3X ATV 61HD22N4 ATV 61HD30N4, HD37N4 ATV 61HD30M3X…HD45M3X ATV 61HD45N4…HD75N4 ATV 61HD55M3X, HD75M3X ATV 61HD90N4, HC11N4 ATV 61HD90M3X ATV 61HC13N4 ATV 61HC16N4 ATV 61HC22N4 ATV 61HC25N4, HC31N4 Without braking unit With braking unit ATV 61HC40N4, HC50N4 ATV 61HC63N4

Degree of Reference protection IP 21 VW3 A9 101

Weight kg 1.300

IP 21

VW3 A9 102

1.500

IP 21

VW3 A9 103

1.800

IP 21

VW3 A9 104

2.000

IP 21

VW3 A9 105

2.800

IP 21

VW3 A9 106

4.000

IP 21 IP 21 IP 21 IP 31

VW3 A9 107 VW3 A9 117 VW3 A9 108 VW3 A9 109

5.000 7.000 7.000 9.400

IP 31

VW3 A9 110

11.800

IP 31 IP 31 IP 31 IP 31 IP 31 IP 31

VW3 A9 111 VW3 A9 112 VW3 A9 113 VW3 A9 114 VW3 A9 115 VW3 A9 116

11.600 14.600 19.500 19.500 25.000 35.000

5

IP 21 or IP 31 conformity kits

Dimensions: pages 99 and 100

25 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 28

Presentation, references (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 Option: accessories

Substitution kit for Altivar 38 drives This kit 1 is used to install an Altivar 61 drive in place of an Altivar 38 drive using the same fixing holes. It includes the mechanical adapters required for mounting. References Old drive 533238

1

Motor Power kW HP

Replaced by

Reference

Weight kg

Replacing an Altivar 38 drive with an integrated EMC filter Three phase supply voltage: 380…480 V 50/60 Hz

VW3 A9 304

ATV 38HU18N4 ATV 38HU29N4 ATV 38HU41N4 ATV 38HU54N4 ATV 38HU72N4 ATV 38HU90N4 ATV 38HD12N4 ATV 38HD16N4 ATV 38HD23N4 ATV 38HD25N4 ATV 38HD28N4 ATV 38HD33N4 ATV 38HD46N4 ATV 38HD54N4 ATV 38HD64N4 ATV 38HD79N4

0.75 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75

1 2 3 – 5 7.5 10 15 20 25 30 40 50 60 75 100

ATV 61H075N4 ATV 61HU15N4 ATV 61HU22N4 ATV 61HU30N4 ATV 61HU40N4 ATV 61HU55N4 ATV 61HU75N4 ATV 61HD11N4 ATV 61HD15N4 ATV 61HD18N4 ATV 61HD22N4 ATV 61HD30N4 ATV 61HD37N4 ATV 61HD45N4 ATV 61HD55N4 ATV 61HD75N4

VW3 A9 302 VW3 A9 302 VW3 A9 303 VW3 A9 304 VW3 A9 304 VW3 A9 305 VW3 A9 306 VW3 A9 307 VW3 A9 308 VW3 A9 309 VW3 A9 310 VW3 A9 311 VW3 A9 311 VW3 A9 315 VW3 A9 315 VW3 A9 315

– – – – – – – – – – – – – – – –

26 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 29

References (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61

533237

Option: accessories

1

References (continued) Old drive

Motor Power kW HP

Replaced by

Reference

Weight kg

Replacing an Altivar 38 drive without an integrated EMC filter Three phase supply voltage: 380…480 V 50/60 Hz ATV 38HD25N4X ATV 38HD28N4X ATV 38HD33N4X ATV 38HD46N4X ATV 38HD54N4X ATV 38HD64N4X ATV 38HD79N4X

18.5 22 30 37 45 55 75

25 30 40 50 60 75 100

ATV 61HD18N4 ATV 61HD22N4 ATV 61HD30N4 ATV 61HD37N4 ATV 61HD45N4 ATV 61HD55N4 ATV 61HD75N4

VW3 A9 309 VW3 A9 310 VW3 A9 311 VW3 A9 311 VW3 A9 315 VW3 A9 315 VW3 A9 315

– – – – – – –

VW3 A9 315

27 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 30

Presentation, references

0

Variable speed drives for asynchronous motors

0

Altivar 61 Options: dialogue

534487

Remote graphic display terminal

1

2 3

7

4

6

5

2 3

1

(this display terminal can be supplied with the drive or ordered separately) This display terminal is attached to the front of the drive. In the case of drives supplied without a graphic display terminal, it covers the integrated 7-segment display terminal. It can be: b Used remotely in conjunction with the appropriate accessories (see below) b Connected to several drives using multidrop link components (see page 29) It is used: b To control, adjust and configure the drive b To display the current values (motor, input/output values, etc.) b To save and download configurations; 4 configuration files can be saved. The terminal’s maximum operating temperature is 60°C and it features IP 54 protection. Description 1 Graphic display: - 8 lines, 240 x 160 pixels - Large digits that can be read from 5 m away - Supports display of bar charts 2 Assignable function keys F1, F2, F3, F4: - Dialogue functions: direct access, help screens, navigation - Application functions: “Local Remote”, preset speed 3 “STOP/RESET”: local control of motor stop/fault reset 4 “RUN”: local control of motor operation 5 Navigation button: - Press: saves the current value (ENT) - Turn ±: increases or decreases the value, takes you to the next or previous line. 6 “FWD/REV”: reverses the direction of rotation of the motor 7 “ESC”: aborts a value, a parameter or a menu to return to the previous selection Note: Keys 3, 4 and 6 can be used to control the drive directly. References Description

Code

Reference

Remote graphic display terminal

1

VW3 A1 101

Weight kg 0.145

Graphic display terminal accessories The available accessories are: b A remote mounting kit for mounting on an enclosure door with IP 54 degree of protection. It includes: v All the mechanical fittings v The screws and bolts b A transparent door which attaches to the remote mechanics to achieve IP 65 degree of protection b A cable equipped with two RJ45 connectors so that the graphic display terminal can be connected to the Altivar 61 drive (1, 3, 5 or 10 m lengths available) b An RJ45 female/female adapter for connecting the VW3 A1 101 graphic display terminal to the VW3 A1 104 Rppp remote cable

4

5

References Description

Code

Remote mounting kit (1) Door (2) Remote cables Equipped with 2 RJ45 connectors

2 3 4 4 4 4 5

1

4

Length m – – 1 3 5 10 –

Degree of protection IP 54 IP 65 – – – – –

Reference

Weight kg VW3 A1 102 0.150 VW3 A1 103 0.040 VW3 A1 104 R10 0.050 VW3 A1 104 R30 0.150 VW3 A1 104 R50 0.250 VW3 A1 104 R100 0.500 VW3 A1 105 0.010

RJ45 female/female adaptor (1) In this case, use a VW3 A1 104 R pp remote connecting cable, which must be ordered separately (see above). (2) To be mounted on remote mounting kit VW3 A1 102 (for mounting on an enclosure door), which must be ordered separately (see above).

Dimensions: page 101

28 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 31

References (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61 Options: dialogue

Multidrop link components These components enable a graphic display terminal to be connected to several drives via a multidrop link. This multidrop link is connected to the Modbus terminal port on the front of the drive. Connection accessories

5

2

5

2

4 VW3 A1 102

ATV 61

1 6 3

2

6

6 2

2 3 2

Description

Code

Modbus splitter box 10 RJ45 connectors and 1 screw terminal Modbus T- With integrated junction 0.3 m cable boxes With integrated 1 m cable Modbus For R = 120 Ω line RJ45 C = 1 nF terminator connector Remote For the VW3 A1 101 mounting kit graphic display terminal

1

Sold in lots Unit of reference – LU9 GC3

2

–

VW3 A8 306 TF03

–

2

–

VW3 A8 306 TF10

–

3

2

VW3 A8 306 RC

0.010

4

–

VW3 A1 102

0.150

Code

Length m 1

Reference VW3 A1 104 R10

Weight kg 0.050

3

VW3 A1 104 R30

0.150

5

VW3 A1 104 R50

0.250

10

VW3 A1 104 R100

0.500

0.3

VW3 A8 306 R03

0.025

1

VW3 A8 306 R10

0.060

3

VW3 A8 306 R30

0.130

Connecting cables (equipped with 2 RJ45 connectors) Used with

ATV 61

Weight kg 0.500

For remote operation of the Altivar 61 5 and the VW3 A1 101 graphic display terminal

Example of connection via multidrop link

Modbus bus

6

522837

PowerSuite software workshop

PowerSuite software workshop

The PowerSuite software workshop offers the following benefits: b Messages can be displayed in plain text in several languages (English, French, German, Italian and Spanish) b Work can be prepared in the design office without having to connect the drive to the PC b Configurations and settings can be saved to floppy disk or hard disk and downloaded to the drive b Print facility b Altivar 38 files can be converted for transfer to an Altivar 61 drive b Oscillograms can be displayed See pages 178 to 181.

Dimensions: page 101

29 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 32

Presentation, characteristics

0

Variable speed drives for asynchronous motors

0

Altivar 61 Options: I/O extension cards

Presentation 532728

Altivar 61 drives can be specially adapted to particular application areas by installing I/O extension cards. Two models are available: b Card with logic I/O featuring: v 1 relay logic output (“C/O” contact) v 4 x 24 V c positive or negative logic inputs v 2 x 24 V c open collector positive or negative logic outputs v 1 input for PTC probes b Card with extended I/O featuring: v 1 differential current analog input (0…20 mA) v 1 software-configurable voltage (0…10 V c) or current (0…20 mA) analog input v 2 software-configurable voltage ( ± 10 V c, 0…10 V) or current (0…20 mA) analog outputs v 1 relay logic output v 4 x 24 V c positive or negative logic inputs v 2 x 24 V c open collector positive or negative logic outputs v 1 input for PTC probes v 1 frequency control input

VW3 A3 202

Characteristics Logic I/O card VW3 A3 201 Internal supplies available

Short-circuit and overload protection: b 1 x 24 V c supply (min. 21 V, max. 27 V), maximum current 200 mA for the complete drive and I/O extension card assembly b 1 x 10.5 V c supply (± 5%) for the reference potentiometer (1 to 10 kΩ), max. current 10 mA

Configurable relay output

R3A, R3B, R3C

1 relay logic output, one “N/C” contact and one “N/O” contact with common point. Minimum switching capacity: 3 mA for 24 V c Maximum switching capacity: b on resistive load (cos ϕ = 1): 5 A for 250 V a or 30 V c b on inductive load (cos ϕ = 0.4 and L/R = 7 ms): 2 A for 250 V a or 30 V c Electrical service life: 100,000 operations Maximum response time: 7 ms ± 0.5 ms

Logic inputs

LI7…LI10

Positive logic (Source)

4 programmable logic inputs, 24 V c, compatible with level 1 PLC, IEC 65A-68 standard Impedance 3.5 kΩ Maximum voltage: 30 V Multiple assignment makes it possible to configure several functions on one input Maximum sampling time: 2 ms ± 0.5 ms State 0 if y 5 V or logic input not wired, state 1 if u 11 V

Negative logic (Sink)

State 0 if u 16 V or logic input not wired, state 1 if y 10 V

Logic outputs

LO1, LO2

Input for PTC probes

TH1+/TH1-

2 x 24 V c assignable open collector positive logic (Source) or negative logic (Sink) outputs, compatible with level 1 PLC, IEC 65A-68 standard 24 V c internal or 24 V c external power supply (min. 12 V, max. 30 V) Maximum current: 200 mA Logic output common (CLO) isolated from other signals Maximum sampling time: 2 ms ± 0.5 ms. The active state is software-configurable as is a delay for each switching operation 1 input for a maximum of 6 PTC probes mounted in series: b nominal value < 1.5 kΩ b trip resistance 3 kΩ, reset value 1.8 kΩ b short-circuit protection < 50 Ω 1.5 mm2 (AWG 16) 0.25 Nm

Maximum I/O connection capacity and tightening torque

Schemes: page 120

30 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 33

Characteristics (continued), references

0

Variable speed drives for asynchronous motors

0

Altivar 61 Options: I/O extension cards

Characteristics (continued) Extended I/O card VW3 A3 202 Internal supplies available

Analog inputs AI

AI3+/AI3-

AI4

Analog outputs

AO2, AO3

Configurable relay output

R4A, R4B, R4C

Logic inputs

LI11…LI14

Logic outputs

Positive logic (Source) Negative logic (Sink) LO3, LO4

Input for PTC probes

TH2+/TH2-

Frequency control input

RP

Maximum I/O connection capacity and tightening torque

Short-circuit and overload protection: b 1 x 24 V c supply (min. 21 V, max. 27 V), max. current 200 mA for the complete drive and I/O extension card assembly b 1 x 10.5 V c supply (± 5%) for the reference potentiometer (1 to 10 kΩ), max. current 10 mA 1 X-Y mA differential current analog input by programming X and Y from 0 to 20 mA, with impedance 250 Ω Maximum sampling time: 5 ms ± 1 ms Resolution: 11 bits + 1 sign bit Accuracy: ± 0.6% for a temperature variation of 60°C Linearity: ± 0.15% of the maximum value 1 software-configurable current or voltage analog input: b voltage analog input 0…10 V c, impedance 30 kΩ (maximum safe voltage 24 V) b X-Y mA current analog input by programming X and Y from 0 to 20 mA, with impedance 250 Ω Maximum sampling time: 5 ms ± 1 ms Resolution: 11 bits Accuracy: ± 0.6% for a temperature variation of 60°C Linearity: ± 0.15% of the maximum value 2 software-configurable current or voltage analog outputs: b voltage analog output ± 10 V c, 0…10 V, minimum load impedance 470 Ω b X-Y mA current analog output by programming X and Y from 0 to 20 mA, maximum load impedance 500 Ω Maximum sampling time: 5 ms ± 1 ms Resolution: 10 bits Accuracy: ± 1% for a temperature variation of 60°C Linearity: ± 0.2% of the maximum value 1 relay logic output, one “N/C” contact and one “N/O” contact with common point. Minimum switching capacity: 3 mA for 24 V c Maximum switching capacity: b on resistive load (cos ϕ = 1): 5 A for 250 V a or 30 V c b on inductive load (cos ϕ = 0.4 and L/R = 7 ms): 1.5 A for 250 V a or 30 V c Electrical service life: 100,000 operations Maximum response time: 10 ms ± 1 ms 4 programmable logic inputs, 24 V c, compatible with level 1 PLC, IEC 65A-68 standard Impedance 3.5 kΩ Maximum voltage: 30 V Multiple assignment makes it possible to configure several functions on one input Maximum sampling time: 5 ms ± 1 ms State 0 if y 5 V or logic input not wired, state 1 if u 11 V State 0 if u 16 V or logic input not wired, state 1 if y 10 V 2 x 24 V c assignable open collector positive logic (Source) or negative logic (Sink) outputs, compatible with level 1 PLC, IEC 65A-68 standard Maximum voltage: 30 V Maximum current: 200 mA Logic output common (CLO) isolated from other signals Maximum sampling time: 5 ms ± 1 ms. The active state is software-configurable as is a delay for each switching operation 1 input for a maximum of 6 PTC probes mounted in series: b nominal value < 1.5 kΩ b trip resistance 3 kΩ, reset value 1.8 kΩ b short-circuit protection < 50 Ω Frequency range: 0…30 kHz Cyclic ratio: 50 % ± 10 % Maximum sampling time: 5 ms ± 1 ms Maximum input voltage 30 V, 15 mA Add a resistor if the input voltage is greater than 5 V (510 Ω for 12 V, 910 Ω for 15 V, 1.3 kΩ for 24 V) State 0 if < 1.2 V, state 1 if > 3.5 V 1.5 mm2 (AWG 16) 0.25 Nm

References I/O extension cards (1) Description

Reference

Logic I/O card

VW3 A3 201

Weight kg 0.300

Extended I/O card

VW3 A3 202

0.300

(1) The Altivar 61 cannot support more than one I/O card with the same reference. Please refer to the compatibility tables summarizing the possible combinations for drives, options and accessories on pages 84 to 89.

Schemes: page 120

31 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com