About the Book
At a Glance Document Scope
The ASP890300 Remote I/O Processor overcomes component obsolescence issues affecting the existing Remote I/O processor models. This product insures continued availability of coaxial cable linked Remote I/O network offerings. Simultaneously, it maintains compatibility with its P890/P892 predecessors. Dual cable functionality and increased I/O power availability are added features. This manual provides specifications and operational information for the product. It also contains information about replacing equipment in earlier models. Note: Equipment replacement guidelines, including those for J890/892, J810/812 and 984 slot-mounted controllers, are listed in Appendix A. Please review these guidelines before performing an upgrade.
Validity Note
31004128 01 July 2002
The data and illustrations found in this book are not binding. We reserve the right to modify our products in line with our policy of continuous product development. The information in this document is subject to change without notice and should not be construed as a commitment by Schneider Electric.
9
Page 10
Product Related Warnings
Schneider Electric assumes no responsibility for any errors that may appear in this document. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us. No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of Schneider Electric. All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to assure compliance with documented system data, only the manufacturer should perform repairs to components. When controllers are used for applications with technical safety requirements, please follow the relevant instructions. Failure to use Schneider Electric software or approved software with our hardware products may result in inury, harm, or improper operating results. Failure to observe this product related warning can result in injury or equipment damage.
User Comments
We welcome your comments about this document. You can reach us by e-mail at TECHCOMM@modicon.com
10
31004128 01 July 2002
Page 11
ASP890300 Installation Guide
1 At a Glance Purpose
This guide describes the Modicon ASP890300 800 I/O Remote receiver with Power.
What’s in this Chapter?
This chapter contains the following topics:
31004128 01 July 2002
Topic
Page
ASP890300 General Description
12
Indicators
15
Power, Backplanes, I/O and Typical Configuration
16
Switch Settings
19
Diagnostics
24
Installation
27
Specifications
29
11
Page 12
Installation Guide
ASP890300 General Description Overview
The MODICON ASP890300 800 I/O Remote I/O processor with Power provides an interface between PLCs and 800 Series Remote I/O modules.Two half-duplex ASCII ports are available. The basic modes of operation are P890/P892/J890 replication (AS-P89X-000 and AS-J890-X0X) and J892 emulation (AS-J892-X0X). The ASP890300 Processor is compatible with all Schneider Electric controllers that support the S908/CRP-type Remote I/O networks and all 800 Series I/O modules. Remote I/O communication is accomplished over single or dual coaxial cable networks. The number of drops and points supported depends on the system PLC. Operating modes are rotary switch-selectable, and include single or dual RI/O cable. These, in part, eliminate improper Comm Error LED indications when operating with a single cable connecting the drop. Rotary switch selectable operating modes, plus two executive reflash options are: l J890/P890 single or dual RI/O cable operation l J892 and P892 single or dual RI/O cable operation l RTU or ASCII reflash modes Executive software stored in flash memory may be updated through ASCII Port 1.
ASP890300 Compatibility
Those replacing the P89X processors will find the ASP890300 both power and backplane compatible. Some connector rewiring will be required. J890 or J892 processor replacement will require a backplane replacement. Depending on the number of I/O modules in the drop, a replacement may also include an additional power supply and rewiring. Note: Equipment replacement guidelines, including those for J810/J812 and 984 slot-mount controllers are described in Appendix A. Please review this material before performing an upgrade. The ASP890300 Processor is mounted into primary 10-, 19- or 27-inch 800 Series I/O backplanes. These provide connectivity between the processor and I/O modules.
12
31004128 01 July 2002
Page 13
Installation Guide
Power
The processor is self-powered from either 115/230VAC or 24VDC sources. These power sources are independently switched ON/OFF on the front panel. The 115V/230VAC inputs are jumper-selectable on the power connector. Up to 7A of combined +5.0VDC and +4.3VDC load current is supplied by the processor to I/O in the primary backplane. No other power supplies may be used to augment the ASP890300. Power for I/O modules in secondary backplanes can be provided by auxiliary supplies interconnected with appropriate cables (see ASP890300 Universal Hardware Upgrade Guide, p. 35).
Front, Bottom, and Left Side View
The ASP890300 is depicted below.
OFF
NEUT HOT
AC PW R ON
DC -
115V JUMPER
OFF DC PWR
PORT 1
ON
PORT 2
PWR OK
CHAN A
CHAN B
READY COMM ACTIVE COMM ERROR A COMM ERROR B ASCII ACTIVE ASCII ERROR OURBUS ERROR
The ASP890300 is shipped with the above label temporarily attached to the 5-pin power connector.
TE I/O REMO ESSOR PR OC
J892 Port ASCI Address
I/O Drop Address
Mode Select
DTR
XON/ XOFF Port 1 Port 2 HANDSHAKE
31004128 01 July 2002
TENS
ONES
TENS
ONES
POSITION
0. No Operation 1. P/J 890/Single 2. P/J 890/Dual 3. P892/Single/ASCII 4. P892/Dual/ASCII 5. J892/Single/ASCII 6. J892/Dual/ASCII 7. Upgrade Exec FLASH RTU 8. Upgrade Exec FLASH ASCII 9. No Operation
13
Page 14
31004128 01 July 2002 J892 Port ASCII Address
I/O Drop Address
DTR XON / XOFF Port 1 Port 2
TENS
ONES
TENS
ONES
HANDSHAKE
14 Mode Select 0. No Operation 1. P/J 890/Single 2. P/J 890/Dual 3. P892/Single/ASCII 4. P892/Dual/ASCII 5. J892/Single/ASCII POSITION 6. J892/Dual/ASCII 7. Upgrade Exec FLASH RTU 8. Upgrade Exec FLASH ASCII 9. No Operation
Right Side View and Label
The label is on the lower, right side. The label is upside-down. See Switch Settings, p. 19 for explanation of label terms.
Installation Guide
Page 15
Installation Guide
Indicators LED Indicators
31004128 01 July 2002
The following table describes the LED Indicators. LED Nomenclature
Color
Function/Indication
PWR OK
Green
Power voltages are good and within specified specifications.
READY
Green
All internal diagnostics have completed successfully and the unit is available for normal operation.
COMM ACTIVE
Green
Unit is successfully and actively communicating on the remote I/O network.
COMM ERROR A
Red
Cable A is experiencing communications errors due to any of the following: l broken cable l poor or loose coaxial connection l intermittent noise l mode selector switch is in wrong position
COMM ERROR B
Red
Cable B is experiencing communications errors due to any of the following: l broken or missing cable l poor or loose coaxial connection l intermittent noise l mode selector switch is in wrong position
ASCII ACTIVE
Green
ASCII port is active.
ASCII ERROR
Red
Unit is experiencing errors with ASCII communication port.
OURBUS ERROR
Red
Unit is experiencing errors with a local I/O module, or: l the entry in the traffic cop does not match the I/O module type; l the I/O module is not present; or l the I/O module is no longer operative.
15
Page 16
Installation Guide
Power, Backplanes, I/O and Typical Configuration Power Supplied for I/O
AC Power Input Connections
The following table describes the power supplied for I/O use. The combination of the +5V and +4.3V loads shall not exceed 7.0A Voltage
Current
+5.0VDC
7.0A
+4.3VDC
6.0A
-5.0VDC
0.5A
The following table describes the ASP890300 AC power connector. Terminal
Nomenclature
Function
1
N
Neutral AC Line
2
L
Hot AC Line
3
G
Ground
4
Jumper inserted between 4 and 5 for 115V operation
5
DANGER HAZARDOUS VOLTAGE l Disconnect all power before working on equipment. l Verify correct terminal connections when wiring. Failure to follow this precaution will result in death, serious injury, or equipment damage.
DC Power Input Connections
16
The following table describes the ASP890300 DC power connector. Terminal
Nomenclature
Function
1
DC+
+24.0VDC
2
DC-
Common
31004128 01 July 2002