What is in it
Schneider Electric installation guide for the Modicon ASP890300 Remote I/O processor with power, which links PLCs to 800 Series Remote I/O modules over single or dual coaxial cable. It covers indicators, power, backplanes and typical configurations (including the 19-inch AS-H819-209 backplane), switch settings, diagnostics, installation and specifications, with appendices on replacing older P89X, J89X and J81X adapters, reflashing the executive software, and CE requirements.
Its parts
- ASP890300 Installation Guide
- ASP890300 Universal Hardware Upgrade Guide
- ASP890300 Executive Software Reflash
- CE Requirements for ASP890300/800 Series I/O Systems
From the manual
Key facts from this manual
Each line names its page in the PDF.
Installation guide (31004128 01, Version 1.0, July 2002) for the Modicon ASP890300 Remote I/O processor with built-in power, which links Schneider PLCs to 800 Series I/O modules over a coaxial Remote I/O network. The site files it under the AS-H819-209, which the guide lists as a compatible 19-inch backplane holding the processor plus six I/O modules. It covers switch settings, LED error codes, installation, specifications, replacing older adapters and reflashing the executive software.
- Device type
- Remote I/O processor with built-in power, linking PLCs to 800 Series Remote I/O modules p. 12
- Compatible backplanes
- AS-H819-209 (19 in., processor plus six I/O modules), AS-H827-209 (27 in., ten modules); AS-H810-208 and AS-H810-209 (10 in., three modules) repair/service exchange only p. 17
- Power input
- 115/230VAC (jumper-selected on the power connector) or 24VDC, each switched on the front panel p. 13
- Power requirements
- 115VAC 1.1A or 230VAC 0.65A, 50/60Hz; 24VDC 4A p. 29
- Power to I/O
- +5.0VDC 7.0A, +4.3VDC 6.0A, -5.0VDC 0.5A; +5V and +4.3V combined not over 7.0A p. 16
- Remote I/O link
- 75 ohm coaxial cable, F-type connector, 1.544 MHz; single or redundant cable; internal 75 ohm termination p. 18, 29
- Drop capacity
- Up to 5 racks (1 primary, 4 secondary); 1024 inputs and 1024 outputs, 2048 points/128 words in all p. 18
- ASCII ports
- 2 per drop; female 9-pin D-type; 50 to 19200 baud; cable up to 50 feet (15 meters) p. 18, 22
- I/O scan time
- Less than 5ms for 256 I/O points p. 29
- Power connectors
- AC 52-0378-000 (5-terminal); DC 52-0380-000 (2-terminal); shipped installed p. 17
- Operating temperature
- 0 to 60°C ambient; storage -40 to +85°C p. 31
- Drop address
- Set on two rotary switches (tens and ones); 0 or above 32 is invalid p. 20
- Programming cables
- AS-W952-012 (12 ft), 990NAA26320 (12 ft), 990NAA26350 (50 ft), to ASCII port 1 p. 50
- BNC to F adapter
- 52-0724-000, for AS-J89X-00X installations with BNC coax connectors p. 38
What this manual walks you through
- Setting the mode select switch for single or dual cable and P890, P892 or J892 operation p. 19
- Setting drop and ASCII port addresses and the handshake switches p. 20, 21
- Reading the front panel LED indicators p. 15
- Decoding flashing LED error codes and recovering from them p. 25, 26
- Wiring AC and DC power p. 16
- Installing the processor in the backplane p. 27, 28
- Wiring an ASCII port cable p. 22, 23
- Replacing AS-P89X-000 adapters p. 36
- Replacing AS-J89X and AS-J81X adapters p. 37, 38, 39
- Reflashing the executive software p. 49, 50, 51, 52
Good to know
- Not compatible with J200 or S901 RIO heads; an S908 or CRP type Remote I/O head is required. p. 39
- No other power supply may add to the processor's output; secondary backplanes need auxiliary supplies. p. 13
- Drop cables must be RG-6 maximum because of space limits. p. 28
- Switch settings are read only at power up. p. 19
- After a fatal error, only a power cycle returns the unit to normal operation. p. 24
Questions this manual answers
What does a flashing Comm Active LED mean on the ASP890300?
The number of flashes gives the error, for example 3 for an OBM error, 5 for a RAM address error and 7 for an exec checksum error. Power cycle first; for one, seven or eight blinks also reflash the executive software. p. 25, 26
Which backplanes take the ASP890300?
The AS-H819-209 (19 in.) and AS-H827-209 (27 in.); the 10 in. AS-H810-208 and AS-H810-209 are listed for repair or service exchange only. p. 17
What power does the ASP890300 need?
115VAC at 1.1A, 230VAC at 0.65A, or 24VDC at 4A. For 115VAC a jumper goes between terminals 4 and 5 of the AC connector. p. 16, 29
How do I reflash the ASP890300 firmware?
Set Mode Select to 7 (RTU) or 8 (ASCII), connect the PC to ASCII Port 1 only, and run the exec download in panel software at 9600 baud with the listed parameters. p. 51, 52
Can the ASP890300 replace a J890 or J892 adapter?
Yes, but the backplane must be replaced, and depending on the number of I/O modules an extra power supply and rewiring may be needed. p. 12
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 10 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.