Page 33
Appendices
What’s in this Appendix?
31004128 01 July 2002
The appendix contains the following chapters: Chapter
Chapter Name
Page
A
ASP890300 Universal Hardware Upgrade Guide
35
B
ASP890300 Executive Software Reflash
49
C
CE Requirements for ASP890300/800 Series I/O Systems
53
33
Page 34
Appendices
34
31004128 01 July 2002
Page 35
ASP890300 Universal Hardware Upgrade Guide
A
At a Glance Purpose
The purpose of this chapter is to assist users in the physical replacement of existing 800 I/O Remote Adapters with the Schneider Electric ASP890300 Remote I/O Processor. Existing Remote I/O system installations may utilize obsolete taps (MA-0185-000, Revision B or lower). The minimum revision taps that should be used are Revision C or higher. Any revision MA-0185-100 tap may be used. Refer to Section 3.6 of the Modicon Remote I/O Cable System Planning and Installtion Guide (890 USE 101 00) for more information.
What’s in this Chapter?
This chapter contains the following topics:
31004128 01 July 2002
Topic
Page
Replacement of AS-P89X-000 Adapters
36
Replacement of AS-J89X-X0X Adapters
37
Replacement of AS-J81X-000 Adapters
39
Replacement of Slot Mount PLCs
41
Backplane Interconnection Diagrams
42
ASP89X Capacity Information
44
Power Supply Capacities in Remote Drop Secondary Applications
45
I/O Module Current Requirements
46
35
Page 36
Upgrade Guide
Replacement of AS-P89X-000 Adapters Overview
The ASP890300 is backplane compatible with AS-P890-000 and AS-P892-000 installations. The AC power and ASCII port connections are different.
AC Power Connector Rewiring
Rewiring is required to accommodate a 5 terminal connector that includes a 115/ 230VAC jumper selection option as opposed to the switch selectable option in the original units. Rewiring requires a small slotted screwdriver. DANGER HAZARDOUS VOLTAGE l Disconnect all power before working on equipment. l Verify correct terminal connections when wiring. Failure to follow this precaution will result in death, serious injury, or equipment damage.
ASCII Port Connector
36
Pin 1 on the P892 is chassis ground. Pin 1 on the ASP890300 ASCII port connector is not used. The connector shell is chassis ground.
31004128 01 July 2002
Page 37
Upgrade Guide
Replacement of AS-J89X-X0X Adapters Overview
The ASP890300 is not physically compatible if installations use the following adapter models. AS-J890-001
AS-J892-001
AS-J890-002
AS-J892-002
AS-J890-101
AS-J892-101
AS-J890-102
AS-J892-102
In these installations, you will need to: l replace the primary backplanes (housings) l perform power calculations to determine if additional supplies are needed (see I/O Module Current Requirements, p. 46) l consider backplane interconnection cables l review ASCII port and coaxial cable connection Primary Backplane Replacement
ASP890300 modules are compatible with: l AS-H810-208 (10", ASP890300 plus three I/O modules)* l AS-H810-209 (10", ASP890300 plus three I/O modules)* l AS-H819-209 (19", ASP890300 plus six I/O modules) l AS-H827-209 (27", ASP890300 plus ten I/O modules) *Repair/service exchange only.
Power Considerations
If the primary backplane power requirements exceed the ASP890300 capabilities, enough I/O modules must be removed from the primary backplane to bring the current load within specified limits. In this case, an additional backplane and power supply will need to be added in the configuration unless the extra modules can be added to an existing powered backplane. For further reference, see Power Supply Capacities in Remote Drop Secondary Applications, p. 45 and I/O Module Current Requirements, p. 46. Secondary backplanes AS-H819-100 and AS-H827-100 support 7 and 11 I/O modules, respectively. Subtract two modules if power supplies need to be added.
Backplane Interconnection Cables
See Backplane Interconnection Diagrams, p. 42 for appropriate configurations.
31004128 01 July 2002
37
Page 38
Upgrade Guide
ASCII Port Pinout Comparison
The following table shows how the ASCII port pinouts are used on the J892 and ASP890300. Terminal
J892 (25 pin)
ASP890300 (9 pin)
1
Shield
Not Used
2
TXD
RXD
3
RXD
TXD
4
RTS
DTR
5
CTS
SGND
6
DSR
DSR
7
Ground
RTS
8
Not Used
CTS
20
DTR
N/A l The ASP890300 connector shell is chassis ground. Coaxial Cable Interconnection/ Terminations
38
AS-J89X-00X Remote I/O Adapters - These have BNC type connectors which are not compatible with the F style connections on ASP890300 modules. Installers may use BNC Jack to Male "F" Connector Adapters, part number 52-0724-000. The external 75Ω terminator added in series with the coax drop cable must be removed as the ASP890300 is terminated internally. AS-J890-10X Remote I/O Adapters are compatible in this respect. They have "F" type coaxial cable connectors and are terminated internally.
31004128 01 July 2002
Page 39
Upgrade Guide
Replacement of AS-J81X-000 Adapters Overview Note: You are reminded the ASP890300 is not compatible with J200 or S901 RIO heads that communicate with J810/J812 modules. Use of the ASP890300 requires the use of an S908 or CRP type RI/O head. The ASP890300 is not physically compatible if installations use the following adapter models: AS-J810-000
AS-J812-000
In these installations, you will need to: l replace the primary backplanes (housings) l perform power calculations to determine if additional supplies are needed (see I/O Module Current Requirements, p. 46) l consider backplane interconnection cables l review ASCII Port and coaxial cable connections Primary Backplane Replacement
ASP890300 modules are compatible with: l AS-H810-208 (10", ASP890300 plus three I/O modules)* l AS-H810-209 (10", ASP890300 plus three I/O modules)* l AS-H819-209 (19", ASP890300 plus six I/O modules) l AS-H827-209 (27", ASP890300 plus ten I/O modules) *Repair/service exchange only.
Power Considerations
If the primary backplane power requirements exceed the ASP890300 capabilities, enough I/O modules must be removed from the primary backplane to bring the current load within specified limits. In this case, an additional backplane and power supply will need to be added in the configuration unless the extra modules can be added to an existing powered backplane. For further reference, see Power Supply Capacities in Remote Drop Secondary Applications, p. 45 and I/O Module Current Requirements, p. 46. Secondary backplanes AS-H819-100 and AS-H827-100 support 7 and 11 I/O modules, respectively. Subtract two modules if power supplies need to be added.
Backplane Interconnection Cables
See Backplane Interconnection Diagrams, p. 42 for appropriate configurations.
31004128 01 July 2002
39
Page 40
Upgrade Guide
ASCII Port Pinout Comparison
The following table shows how the ASCII port pinouts are used on the J812 and ASP890300. Terminal
J812 (25 pin)
ASP890300 (9 pin)
1
GND
Not Used
2
TXD
RXD
3
RXD
TXD
4
RTS
DTR
5
CTS
SGND
6
DSR
DSR
7
SGND
RTS
8
Not Used
CTS
20
DTR
N/A l The ASP890300 connector shell is chassis ground. Coaxial Cable Interconnection/ Terminations
40
These have BNC type connectors which are not compatible with the F style connections on ASP890300 modules. Unless otherwise accommodated, installers may use BNC Jack to Male "F" Connector Adapters, part number 52-0724-000.
31004128 01 July 2002