Page 25
Installation Guide
Flashing LED Error Codes
The following table describes the ASP890300 flashing LED codes. Comm Active Flashes
Error Condition
0
Power Down Interrupt
1
Kernel Mode
2
Not Used
3
OBM Error
4
Bad/Unexpected Interrupt LAN Chip Error Receive Abort Error Transmission Loop Time-out Transmission DMA Time-out Cable A Initialization Error Cable A DMA Xfer Error Cable B DMA Xfer Error Cable A Dump Data Error Cable A DMA Hung Cable B DMA Hung Cable A/B DRQ Hung Power Up LAN Error Cable B Initialization Error
5
RAM Address Error
6
RAM Data Error
7
Exec Checksum Error
8
Kernel Detected Error
*
*Invalid Switch Setting
*Comm A/B Error LEDs flash together indicating an invalid switch setting. Examples: Invalid Loop Address, Invalid ASCII Port Address, Invalid Mode Setting.
31004128 01 July 2002
25
Page 26
Installation Guide
If an ASP890300 Remote I/O Processor exhibits any of the above flashing LED codes, follow the steps below. If . . .
Then . . .
an ASP890300 Remote I/O Processor stops cycle the processor power off and back on operating and exhibits any of the flashing when it is safe to do so. LED codes in the previous table,
26
Comm Active is flashing in any of the following patterns: l one blink l seven blinks, or l eight blinks, power cycle as above, then reflash the executive software (see ASP890300 Executive Software Reflash, p. 49).
neither of the above two actions restore normal operation, replace the processor.
31004128 01 July 2002
Page 27
Installation Guide
Installation Overview
The following procedure describes how to install an ASP890300 Processor. The processor is installed in an H810-208, H810-209, or H819/H827-209 800 Series I/O Housing in the left-most slot.
Panel Software Requirements
The ASP890300 is a direct replacement for the ASP89X-000 processor. If you need to reconfigure a program, you may use any panel software that supports P89X processors. Select the P89X when traffic copping (I/O mapping).
31004128 01 July 2002
27
Page 28
Installation Guide
Installing a ASP890300 Processor
Use the following procedure to install an ASP890300 Processor. Step
Action
1
Set the processor’s Mode Select and Drop Address switches appropriately (shown in Switch Settings, p. 19). l For example, when replacing or emulating an AS-P890-000, AS-J890-001, or AS-J890-101, select Rotary Switch Position 1.
2
If using ASCII communications, set the processor’s Port Address and Handshake switches as required. l The Port 1/Port 2 Handshake and J892 Port ASCI Address switches are ignored if the Mode switch setting indicates ASCII is disabled. l The Handshake switches are enabled if a switch position indicating ASCII Enabled is selected. l The J892 Port ASCI switches are enabled as indicated.
DANGER HAZARDOUS VOLTAGE l Disconnect all power before working on equipment. l Verify correct terminal connections when wiring. Failure to follow this precaution will result in death, serious injury, or equipment damage. Step
28
Action
3
Ensure the processor power source is switched off. Connect power wires to the appropriate AC or DC power connector terminals. If using AC power, for 115VAC operation, insert a jumper between terminals 4 and 5.
4
Connect the Remote I/O coaxial cables. Plug the power connectors into the processor. NOTE: Due to space restrictions (especially if the backplane is rack-mounted), drop cables must be RG-6 maximum. If using dual cables, the suggested method for cable connection is to attach the CHAN A cable first, then the CHAN B. When disconnecting, reverse the process, and remove the CHAN B cable first.
5
Insert the processor into the leftmost slot of the backplane. Press firmly to ensure it is properly seated in the backplane.
6
Tighten the captive screws at the top and bottom of the processor.
7
If used, plug the ASCII connectors into the processor.
8
For AC application, switch on "AC Pwr" For DC application, switch on "DC Pwr"
9
Apply power when the system is ready for processor operation. Make sure that the PWR OK and RDY LEDs are ON. If the system PLC is in RUN mode, make sure that the COMM ACTIVE LED is ON and the OURBUS ERROR LED is OFF.
31004128 01 July 2002
Page 29
Installation Guide
Specifications ASP890300 Specifications
31004128 01 July 2002
The following table describes the specifications of the ASP890300. Remote I/O Cabling
Coaxial cable 75 ohm
Remote I/O Connector
F-Type
Remote I/O Communications Rate
1.544 MHz
I/O scan time
Less than 5ms for 256 I/O points
RIO comm link time
Less than 1ms for 256 I/O points
Drop hold up time
Programmable from 300ms to 6553.6 sec (in 100ms increments
Power supplied to I/O (Short circuit proof)
+5VIO, 7A max* +4.3V, 6A max* -5V, 0.5A max *The +5VIO and +4.3V combined cannot exceed 7A.
Power Requirements
115VAC, 1.1A, 50/60Hz 230VAC, 0.65A, 50/60Hz 24VDC, 4A
Inrush Current
30A @ 115VAC 25A @ 24VDC
Power Loss Hold up time
1 cycle AC loss 1ms @ 24VDC
29
Page 30
Installation Guide
Power Supply
The following table describes ASP890300 power supply testing. (These requirements do not apply to the DC auxiliary input.) Test
Reference
Isolation AC Line to Output
RIO Interface
2500 VDC 1780VAC
Electro-Static Discharge
IEC 1000-4-2
4KV Conducted 8KV Air Gap
Radio Frequency Interference
IEC 1000-4-3
10V/m 27MHz-1GHz
Fast Transient
IEC 1000-4-4
2.0KV Comm mode 2.0KV Diff mode
Surge Withstand
IEC1000-4-5
2.0KV Comm Mode 1.0KV Diff Mode
Conducted RF Susceptibility
IEC1000-4-6
0.15KHz-80MHz 10Vrms
Damped Oscillatory Wave
IEEE472
2.5KV Diff Mode 2.5KV Comm Mode
The following table describes ASP890300 RIO interface testing. Test
Reference
Isolation Coax to Backplane
30
Spec. Limit
Spec. Limit 500 VDC
Electro-Static Discharge
IEC 1000-4-2
4KV Conducted 8KV Air Gap
Radio Frequency Interference
IEC 1000-4-3
10V/m 27MHz-1GHz
Fast Transient
IEC 1000-4-4
1.0KV Cap Clamp
Surge Withstand
IEC1000-4-5
2.0KV to Shield
Conducted RF Susceptibility
IEC1000-4-6
0.15KHz-80MHz 10Vrms
Damped Oscillatory Wave
IEEE472
2.5KV to Shield
31004128 01 July 2002
Page 31
Installation Guide
ASCII Ports
The following table describes ASP890300 ASCII ports testing. Test
Reference
Spec. Limit
Electro-Static Discharge
IEC 1000-4-2
4KV Conducted 8KV Air Gap
Radio Frequency Interference
IEC 1000-4-3
10V/m 27MHz-1GHz
Fast Transient
IEC 1000-4-4
1.0KV Cap Clamp
Surge
IEC1000-4-5
2.0KV to Shield
Conducted RF Susceptibility
IEC1000-4-6
0.15KHz-80MHz 10Vrms
Damped Oscillatory Wave
IEEE472
No Test <30 meters
Isolation
Electromagnetic Emissions
No Test
The following table describes ASP890300 electromagnetic emissions testing. Test
Reference
Spec. Limit
Radiated Emission
EN 55011
30-230MHz in situ at 10M 40dbuV 230-1000MHz in situ at 10M 47dbuV
Conducted Emission
EN55011
0.15-.5MHz 70(66) quasi peak (avg.) dbuV 0.5MHz-30MHz 73(60) quasi peak (avg.) dbuV l Requires external filter Temperature/ Vibration
31004128 01 July 2002
The following table describes ASP890300 temperature and vibration testing. Parameter
Reference
Specification Limits
Storage Temperature
IEC 68-2-14
-40 to +85°C
Operating Temperature
IEC 68-2-14
0 to 60°C Ambient
Humidity Non-Operating
IEC 68-2-3
95% RH at 60°C non-condensing
Humidity Operating
IEC 68-2-3
95% RH at 60°C non-condensing
Altitude
MIL-STD-810
15,000 feet
Vibration Operating
IEC-68-2-6
10-57Hz: 0.075mm Dual Axis
Shock Operating 3 shocks/axis
IEC 68-2-27
15g, 11ms
Free Fall Unpackaged
IEC 68-2-32
1m
31
Page 32
Installation Guide
Agency Approvals
The following table describes ASP890300 agency approvals. Agency UL 508 CSA 22.2-142 CE
32
31004128 01 July 2002