Page 17
Installation Guide
Input Power Connectors Part Numbers
The following table lists part numbers for input power connectors. Input
Part Number
AC
52-0378-000 (5-terminal)
DC
52-0380-000 (2-terminal)
Note: The ASP890300 is shipped with these connectors installed.
Compatible Backplanes
The following backplanes are compatible with the ASP890300. Name
Description
AS-H810-208*
10", ASP890300 plus three I/O modules.
AS-H810-209*
10", ASP890300 plus three I/O modules.
AS-H819-209
19", ASP890300 plus six I/O modules.
AS-H827-209
27", ASP890300 plus ten I/O modules.
*Repair/service exchange only
Typical Configuration
Here is a typical ASP890300 configuration. PLC
S908 RIO HEAD H819-103 Tap
Power J892 800 800 I/O I/O Supply P810
Drop #2
ASCII Devices
Tap
P890300
75 Ω Terminator
H819-209 800 800 I/O I/O
Drop #3
ASCII Devices
31004128 01 July 2002
17
Page 18
Installation Guide
Remote I/O
The following table describes ASP890300 remote I/O. Compatibility
Drop I/O Capacity
ASCII Port Capacity
18
All S908 Commands and Responses
Cable Medium
Coax, Single or Redundant Options
Termination
75Ω Internal
Shield Grounding Method
Capacitor Coupled to Chassis Ground
Device Address
1-32
The following table describes ASP890300 drop I/O capacity. Max Number of 800 Racks
5 Max: 1 Primary, 4 Secondary
Max Number of Inputs
1024 Points/64 Words
Max Number of Outputs
1024 Points/64 Words
Max I/O
2048 Points/128 Words
Drop Hold Up Time
300ms to 6553.6 seconds 10ms increments
Drop Scan Time
5ms for 256 I/O Points
The following table describes ASP890300 ASCII port capacity. Total Number ASCII Ports per Drop
2
Total Number ASCII Drops per System
16
Total Number ASCII Ports per System
32
31004128 01 July 2002
Page 19
Installation Guide
Switch Settings Switch Label
The following graphic shows the switch label. J892 Port ASCI Address
I/O Drop Address
Mode Select
DTR
XON/ XOFF Port 1 Port 2 HANDSHAKE
Mode Select Switch
TENS
ONES
TENS
ONES
POSITION
0. No Operation 1. P/J 890/Single 2. P/J 890/Dual 3. P892/Single/ASCII 4. P892/Dual/ASCII 5. J892/Single/ASCII 6. J892/Dual/ASCII 7. Upgrade Exec FLASH RTU 8. Upgrade Exec FLASH ASCII 9. No Operation
The following table describes the ASP890300 mode select switch. Rotary Switch Position
Label Nomenclature
Function
0
No Operation
Not Used
1
P/J 890/Single
P89x/J89x Single Cable/ASCII Disabled
2
P/J 890/Dual
P89x/J89x Dual Cable/ASCII Disabled
3
P892/Single/ASCII
P892 Single Cable/ASCII Enabled Port Address Switch Disabled
4
P892/Dual/ASCII
P892 Dual Cable/ASCII Enabled Port Address Switch Disabled
5
J892/Single/ASCII
J892 Single Cable/ASCII Enabled Port Address Switch Enabled
6
J892/Dual/ASCII
J892 Dual Cable/ASCII Enabled Port Address Switch Enabled
7
Upgrade Exec FLASH RTU
Flash Update via Port 1 using RTU Mode parameters Drop Functionally Disabled
8
Upgrade Exec FLASH ASCII
Flash Update via Port 1 using ASCII Mode parameters Drop Functionally Disabled
9
No Operation
Not Used l Switch settings read only on power up l Invalid switch position setting will be indicated by flashing Comm Error A and Comm Error B LEDs
31004128 01 July 2002
19
Page 20
Installation Guide
I/O Drop Address Switches
The following table describes the ASP890300 drop address switches. Switch Type
Function
Numbered
Valid Setting
10 Position Rotary
Ones
0-9
0-9
10 Position Rotary
Tens
0-9
0-3 l Switch settings read only on power up l Drop address settings of 0 or greater than 32 are invalid addresses l Invalid address setting will be indicated by flashing Comm Error A and Comm Error B LEDs P892 (Mode 3/4) ASCII Port Addressing
The following table describes the ASP890300’s P892 (Mode 3/4) ASCII port addressing determined by the I/O drop address switches. Drop Address
ASCII Address
Drop Address
ASCII Address
1
1,2
9
17,18
2
3,4
10
19,20
3
5,6
11
21,22
4
7,8
12
23,24
5
9,10
13
25,26
6
11,12
14
27,28
7
13,14
15
29,30
8
15,16
16
31,32 l Switch settings read only on power up l ASCII port rotary address switches disabled in this mode l ASCII port addresses are related to the drop address and are based upon this table l Drops 17 through 32 can still be used for 800 I/O, but cannot have associated ASCII ports J892 Port ASCII Address Switches
The following table describes the ASP890300 ASCII port address switches. Switch Type
Function
Numbered
Valid Setting
10 Position Rotary
Ones
0-9
0-9
10 Position Rotary
Tens
0-9
0-3 l Switch settings read only on power up l Switch valid for Modes 5/6 only l ASCII port address settings of 0 or greater than 31 are invalid addresses l Invalid address setting will be indicated by flashing Comm Error A and Comm Error B LEDs
20
31004128 01 July 2002
Page 21
Installation Guide
J892 (Mode 5/6) ASCII Port Addressing
The following table describes the ASP890300’s J892 (Mode 5/6) ASCII port addressing determined by the J892 port ASCII address switches. Switch Setting
ASCII Port Address
Switch Setting
ASCII Address
1 or 2
1, 2
17 or 18
17, 18
3 or 4
3, 4
19 or 20
19, 20
5 or 6
5, 6
21 or 22
21, 22
7 or 8
7, 8
23 or 24
23, 24
9 or 10
9, 10
25 or 26
25, 26
11 or 12
11, 12
27 or 28
27, 28
13 or 14
13, 14
29 or 30
29, 30
15 or 16
15, 16
31 or 32
31, 32 l Switch settings read only on power up l ASCII port rotary address switches enabled in this mode l ASCII port addresses of 0 and greater than 32 are invalid l Invalid address setting will be indicated by flashing Comm Error A and Comm Error B LEDs ASCII Port Handshake Switch
The following table describes the ASCII port handshake switch. 2 Position DIP Switch Port 1
Port 2
Function Data Terminal Ready XON/XOFF Data Terminal Ready XON/XOFF l Switch settings read only on power up
31004128 01 July 2002
21
Page 22
Installation Guide
ASCII Port Interface Connector
The following table describes the ASCII port interface connector. Female 9 Pin D-Type Pin Number
Signal Name
1
Description Not Used
2
RXD
Receive Data
3
TXD
Transmit Data
4
DTR
Data Terminal Ready
5
SGND
Signal Ground
6
DSR
Data Set Ready
7
RTS
Request to Send
8
CTS
Clear to Send
9
Not Used l D-sub shell tied to chassis ground. ASCII Port Parameters
ASCII Cable Distance
22
The following table describes programmable ASCII port parameters. Port Address
1-32
Baud Rate
50, 75, 110, 134, 150, 300, 600, 1200, 1800, 2000, 2400, 3600, 4800, 7200, 9600, 19200
Data Bits
5, 6, 7, 8
Parity
None, Odd, Even
Stop Bits
1 or 2
The maximum cable distance is 50 feet (15 meters).
31004128 01 July 2002
Page 23
Installation Guide
Sample Pin Layout
The following figure describes one possible pin layout for a cable connecting a ASP890300 ASCII port and another device using hardwired flow control. Actual pin numbers may vary between remote devices. ASCII PORT (9-PIN) REMOTE DEVICE (25-PIN) (DTR/DSR) (DTR/DSR) Name
Pin
Pin
Name
TXD
3 2 4
RXD
RTS
3 2 7
CTS DSR SG DTR
8 6 5 4
5 20 7 6
CTS DTR SG DSR
RXD
31004128 01 July 2002
. . . .
TXD
RTS
23
Page 24
Installation Guide
Diagnostics Overview
The ASP890300 performs two classes of confidence tests, power-up tests and runtime tests. The power-up tests are designed to detect problems within the board hardware before lighting the ready LED and going on-line to receive and hand off data. The run-time tests attempt to catch board hardware problems while the ASP890300 is handling data and will force the unit to go off line if errors are detected. Errors always cause the ASP890300 to flash appropriate LEDs and to turn off the ready LED. The only way of returning to normal operation from a fatal error is to power cycle the unit.
Confidence Tests
The following table describes actions performed by ASP890300 confidence tests.
24
Confidence Test
Action Performed
Flash Checksum
Performs a checksum of the executive flash
RAM Data Test
Verifies RAM data integrity
RAM Address Test
Verifies RAM address integrity
LAN Controller
Verifies LAN controller integrity
OBM Test
Verifies OURBUS integrity
31004128 01 July 2002