Page 17

Installation Guide

Input Power Connectors Part Numbers

The following table lists part numbers for input power connectors. Input

Part Number

AC

52-0378-000 (5-terminal)

DC

52-0380-000 (2-terminal)

Note: The ASP890300 is shipped with these connectors installed.

Compatible Backplanes

The following backplanes are compatible with the ASP890300. Name

Description

AS-H810-208*

10", ASP890300 plus three I/O modules.

AS-H810-209*

10", ASP890300 plus three I/O modules.

AS-H819-209

19", ASP890300 plus six I/O modules.

AS-H827-209

27", ASP890300 plus ten I/O modules.

*Repair/service exchange only

Typical Configuration

Here is a typical ASP890300 configuration. PLC

S908 RIO HEAD H819-103 Tap

Power J892 800 800 I/O I/O Supply P810

Drop #2

ASCII Devices

Tap

P890300

75 Ω Terminator

H819-209 800 800 I/O I/O

Drop #3

ASCII Devices

31004128 01 July 2002

17

Page 18

Installation Guide

Remote I/O

The following table describes ASP890300 remote I/O. Compatibility

Drop I/O Capacity

ASCII Port Capacity

18

All S908 Commands and Responses

Cable Medium

Coax, Single or Redundant Options

Termination

75Ω Internal

Shield Grounding Method

Capacitor Coupled to Chassis Ground

Device Address

1-32

The following table describes ASP890300 drop I/O capacity. Max Number of 800 Racks

5 Max: 1 Primary, 4 Secondary

Max Number of Inputs

1024 Points/64 Words

Max Number of Outputs

1024 Points/64 Words

Max I/O

2048 Points/128 Words

Drop Hold Up Time

300ms to 6553.6 seconds 10ms increments

Drop Scan Time

5ms for 256 I/O Points

The following table describes ASP890300 ASCII port capacity. Total Number ASCII Ports per Drop

2

Total Number ASCII Drops per System

16

Total Number ASCII Ports per System

32

31004128 01 July 2002

Page 19

Installation Guide

Switch Settings Switch Label

The following graphic shows the switch label. J892 Port ASCI Address

I/O Drop Address

Mode Select

DTR

XON/ XOFF Port 1 Port 2 HANDSHAKE

Mode Select Switch

TENS

ONES

TENS

ONES

POSITION

0. No Operation 1. P/J 890/Single 2. P/J 890/Dual 3. P892/Single/ASCII 4. P892/Dual/ASCII 5. J892/Single/ASCII 6. J892/Dual/ASCII 7. Upgrade Exec FLASH RTU 8. Upgrade Exec FLASH ASCII 9. No Operation

The following table describes the ASP890300 mode select switch. Rotary Switch Position

Label Nomenclature

Function

0

No Operation

Not Used

1

P/J 890/Single

P89x/J89x Single Cable/ASCII Disabled

2

P/J 890/Dual

P89x/J89x Dual Cable/ASCII Disabled

3

P892/Single/ASCII

P892 Single Cable/ASCII Enabled Port Address Switch Disabled

4

P892/Dual/ASCII

P892 Dual Cable/ASCII Enabled Port Address Switch Disabled

5

J892/Single/ASCII

J892 Single Cable/ASCII Enabled Port Address Switch Enabled

6

J892/Dual/ASCII

J892 Dual Cable/ASCII Enabled Port Address Switch Enabled

7

Upgrade Exec FLASH RTU

Flash Update via Port 1 using RTU Mode parameters Drop Functionally Disabled

8

Upgrade Exec FLASH ASCII

Flash Update via Port 1 using ASCII Mode parameters Drop Functionally Disabled

9

No Operation

Not Used l Switch settings read only on power up l Invalid switch position setting will be indicated by flashing Comm Error A and Comm Error B LEDs

31004128 01 July 2002

19

Page 20

Installation Guide

I/O Drop Address Switches

The following table describes the ASP890300 drop address switches. Switch Type

Function

Numbered

Valid Setting

10 Position Rotary

Ones

0-9

0-9

10 Position Rotary

Tens

0-9

0-3 l Switch settings read only on power up l Drop address settings of 0 or greater than 32 are invalid addresses l Invalid address setting will be indicated by flashing Comm Error A and Comm Error B LEDs P892 (Mode 3/4) ASCII Port Addressing

The following table describes the ASP890300’s P892 (Mode 3/4) ASCII port addressing determined by the I/O drop address switches. Drop Address

ASCII Address

Drop Address

ASCII Address

1

1,2

9

17,18

2

3,4

10

19,20

3

5,6

11

21,22

4

7,8

12

23,24

5

9,10

13

25,26

6

11,12

14

27,28

7

13,14

15

29,30

8

15,16

16

31,32 l Switch settings read only on power up l ASCII port rotary address switches disabled in this mode l ASCII port addresses are related to the drop address and are based upon this table l Drops 17 through 32 can still be used for 800 I/O, but cannot have associated ASCII ports J892 Port ASCII Address Switches

The following table describes the ASP890300 ASCII port address switches. Switch Type

Function

Numbered

Valid Setting

10 Position Rotary

Ones

0-9

0-9

10 Position Rotary

Tens

0-9

0-3 l Switch settings read only on power up l Switch valid for Modes 5/6 only l ASCII port address settings of 0 or greater than 31 are invalid addresses l Invalid address setting will be indicated by flashing Comm Error A and Comm Error B LEDs

20

31004128 01 July 2002

Page 21

Installation Guide

J892 (Mode 5/6) ASCII Port Addressing

The following table describes the ASP890300’s J892 (Mode 5/6) ASCII port addressing determined by the J892 port ASCII address switches. Switch Setting

ASCII Port Address

Switch Setting

ASCII Address

1 or 2

1, 2

17 or 18

17, 18

3 or 4

3, 4

19 or 20

19, 20

5 or 6

5, 6

21 or 22

21, 22

7 or 8

7, 8

23 or 24

23, 24

9 or 10

9, 10

25 or 26

25, 26

11 or 12

11, 12

27 or 28

27, 28

13 or 14

13, 14

29 or 30

29, 30

15 or 16

15, 16

31 or 32

31, 32 l Switch settings read only on power up l ASCII port rotary address switches enabled in this mode l ASCII port addresses of 0 and greater than 32 are invalid l Invalid address setting will be indicated by flashing Comm Error A and Comm Error B LEDs ASCII Port Handshake Switch

The following table describes the ASCII port handshake switch. 2 Position DIP Switch Port 1

Port 2

Function Data Terminal Ready XON/XOFF Data Terminal Ready XON/XOFF l Switch settings read only on power up

31004128 01 July 2002

21

Page 22

Installation Guide

ASCII Port Interface Connector

The following table describes the ASCII port interface connector. Female 9 Pin D-Type Pin Number

Signal Name

1

Description Not Used

2

RXD

Receive Data

3

TXD

Transmit Data

4

DTR

Data Terminal Ready

5

SGND

Signal Ground

6

DSR

Data Set Ready

7

RTS

Request to Send

8

CTS

Clear to Send

9

Not Used l D-sub shell tied to chassis ground. ASCII Port Parameters

ASCII Cable Distance

22

The following table describes programmable ASCII port parameters. Port Address

1-32

Baud Rate

50, 75, 110, 134, 150, 300, 600, 1200, 1800, 2000, 2400, 3600, 4800, 7200, 9600, 19200

Data Bits

5, 6, 7, 8

Parity

None, Odd, Even

Stop Bits

1 or 2

The maximum cable distance is 50 feet (15 meters).

31004128 01 July 2002

Page 23

Installation Guide

Sample Pin Layout

The following figure describes one possible pin layout for a cable connecting a ASP890300 ASCII port and another device using hardwired flow control. Actual pin numbers may vary between remote devices. ASCII PORT (9-PIN) REMOTE DEVICE (25-PIN) (DTR/DSR) (DTR/DSR) Name

Pin

Pin

Name

TXD

3 2 4

RXD

RTS

3 2 7

CTS DSR SG DTR

8 6 5 4

5 20 7 6

CTS DTR SG DSR

RXD

31004128 01 July 2002

. . . .

TXD

RTS

23

Page 24

Installation Guide

Diagnostics Overview

The ASP890300 performs two classes of confidence tests, power-up tests and runtime tests. The power-up tests are designed to detect problems within the board hardware before lighting the ready LED and going on-line to receive and hand off data. The run-time tests attempt to catch board hardware problems while the ASP890300 is handling data and will force the unit to go off line if errors are detected. Errors always cause the ASP890300 to flash appropriate LEDs and to turn off the ready LED. The only way of returning to normal operation from a fatal error is to power cycle the unit.

Confidence Tests

The following table describes actions performed by ASP890300 confidence tests.

24

Confidence Test

Action Performed

Flash Checksum

Performs a checksum of the executive flash

RAM Data Test

Verifies RAM data integrity

RAM Address Test

Verifies RAM address integrity

LAN Controller

Verifies LAN controller integrity

OBM Test

Verifies OURBUS integrity

31004128 01 July 2002