Page 41

Upgrade Guide

Replacement of Slot Mount PLCs Compatibility

The ASP890300 is backplane compatible with Slot Mount PLC installations. These include: l PC-0984-380/1/5; PC-E984-381/5 l PC-0984-480/5; PC-E984-480/5 l PC-0984-680/5; PC-E984-685 l PC-0984-780/5; PC-E984-785

AC Power Connector Rewiring

Rewiring is required to accommodate one 2 terminal and one 3 terminal connector, which include a 115/230VAC jumper selection option as opposed to the switch selectable option in the original units. Rewiring requires a small slotted screwdriver. DANGER HAZARDOUS VOLTAGE l Disconnect all power before working on equipment. l Verify correct terminal connections when wiring. Failure to follow this precaution will result in death, serious injury, or equipment damage.

Power Considerations

If replacing high end slot mount PLCs: Both +5VDC I/O power and the Combined load in PC-0984-680/5s and PC-0984-780/5s are rated 1A higher than the ASP890300. If the Primary backplane power requirements exceed the ASP890300 capabilities, enough I/O modules must be removed from the primary backplane to bring the current load within specified limits. In this case, an additional backplane and power supply will need to be added in the configuration unless the extra modules can be added to an existing powered backplane. See I/O Module Current Requirements, p. 46 and Power Supply Capacities in Remote Drop Secondary Applications, p. 45. Secondary backplanes AS-H819-100 and AS-H827-100 support 7 and 11 I/O modules, respectively. Subtract two modules if power supplies need to be added.

Backplane Interconnection Cables

For more information, see Backplane Interconnection Diagrams, p. 42

31004128 01 July 2002

41

Page 42

Upgrade Guide

Backplane Interconnection Diagrams The following illustration shows ASP890300 configurations with no secondary power supply. ASP890300

ASP890300 with No Secondary Power Supply

I/O

AS-W801-002: 1.5’ AS-W801-006: 6.0’ AS-W801-012: 12.0’

AS-W80X-0XX AS-W808-002: AS-W808-006: AS-W808-008: AS-W802-012:

1.5’ 6.0’ 8.0’ 12.0’

AS-W801-XXX

I/O

42

31004128 01 July 2002

Page 43

Upgrade Guide

The following illustration shows ASP890300 configurations with a secondary power supply. ASP890300

ASP890300 with a Secondary Power Supply Installed

AS-W801-002: 1.5’ AS-W801-XXX AS-W801-006: 6.0’ AS-W801-012: 12.0’

31004128 01 July 2002

P8XX

AS-W804-0XX AS-W804-002: 1.5’ AS-W804-006: 6.0’ AS-W804-012: 12.0’

I/O

I/O

43

Page 44

Upgrade Guide

ASP89X Capacity Information Capacity Current Capacity (A) Type

44

+5.0V +4.3V -5.0V

Max Combined +5V and +4.3V Load

Input

AS-P89X-000 3.0

3.0

0.25

3.0

115/230VAC, 0.75A @115VAC, or 24VDC, 2A

ASP890300

6.0

0.5

7.0

115VAC, 1.1A, 50/60Hz 230VAC, 0.65A, 50/60Hz 24VDC, 4A

7.0

31004128 01 July 2002

Page 45

Upgrade Guide

Power Supply Capacities in Remote Drop Secondary Applications Power Supply Capacities

Current Capacity (A) Type

+5.0V

+4.3V

-5.0V

Max Combined +5V Input and +4.3V Load

AS-P800-003

2.5

10.0

0.5

12.5

115/230VAC, 1.5A @115VAC

AS-P801-001

5.0

10.0

0.5

15.0

115/230VAC, 1.7A @115VAC

AS-P802-001

2.5

10.0

0.5

12.5

24VDC, 8A

AS-P810-001

5.0

5.0

0.3

10.0

115/230VAC, 1.6A @115VAC

AS-P830-000

5.0

6.0

0.5

6.0

115/230VAC, 0.5A @115VAC, or 24VDC, 2A

AS-P840-000

5.0

10.0

0.5

15.0*

115/230VAC, 1.1A @115VAC

*55° C max; 12A max @ 60° C

31004128 01 July 2002

45

Page 46

Upgrade Guide

I/O Module Current Requirements Requirements Current (mA) @ Module

46

+5.0V

+4.3V

-5.0V

AS-B802-008

76

240

0

AS-B803-008

27

1

2

AS-B804-116

76

480

0

AS-B804-116

76

480

0

AS-B804-148

76

480

0

AS-B805-016

40

1

14

AS-B806-032

210

1

0

AS-B806-124

210

1

0

AS-B807-132

80

2

0

AS-B808-016

76

480

0

AS-B809-016

42

1

15

AS-B810-008

50

240

0

AS-B814-001

120

220

0

AS-B814-002

120

220

0

AS-B814-108

107

800

0

AS-B817-116

25

2

8

AS-B817-216

25

2

8

AS-B820-008

90

80

0

AS-B821-008

20

0

0

AS-B821-108

27

1

10

AS-B824-016

32

260

0

AS-B825-016

27

1

15

AS-B826-032

90

1

0

AS-B827-032

30

1

0

AS-B828-016

32

220

0

AS-B829-016

120

0

0

AS-B829-116

21

1

0

AS-B832-016

32

235

0

AS-B833-016

27

2

0

31004128 01 July 2002

Page 47

Upgrade Guide

Current (mA) @

31004128 01 July 2002

Module

+5.0V

+4.3V

-5.0V

AS-B836-016

50

603

0

AS-B837-016

40

1

15

AS-B838-032

160

1

0

AS-B840-008

120

220

0

AS-B840-108

67

400

0

AS-B842-008

120

220

0

AS-B846-001

65

1

0

AS-B846-002

65

1

0

AS-B849-016

40

1

15

AS-B853-016

40

1

15

AS-B855-016

80

1

0

AS-B862-001

180

220

0

AS-B863-001

180

220

0

AS-B863-032

250

0

0

AS-B863-132

350

10

0

AS-B864-001

100

100

0

AS-B865-001

400

600

0

AS-B868-001

180

220

0

AS-B869-001

180

220

0

AS-B872-002

540

220

0

AS-B872-011

240

880

0

AS-B872-100

475

5

0

AS-B872-200

750

5

0

AS-B873-001

400

440

0

AS-B873-002

300

300

0

AS-B873-011

300

440

0

AS-B873-012

300

300

0

AS-B875-001

300

440

0

AS-B875-002

300

300

0

AS-B875-011

300

440

0

AS-B875-012

300

300

0

AS-B875-102

650

975

0

AS-B875-111

500

900

0

47

Page 48

Upgrade Guide

Current (mA) @

48

Module

+5.0V

+4.3V

-5.0V

AS-B875-200

550

10

0

AS-B881-001

30

1

0

AS-B881-108

285

240

0

AS-B881-508

300

0

0

AS-B882-032

300

10

0

AS-B882-116

350

10

0

AS-B882-239

188

0

0

AS-B883-001

667

0

0

AS-B883-101

1000

0

0

AS-B883-111

1000

0

0

AS-B883-200

400

5

0

AS-B883-201

640

5

0

AS-B884-002

50

2

0

AS-B885-001

500

1760

0

AS-B885-002

500

1760

0

AS-B885-100

25

0

0

AS-B885-101

25

0

0

AS-B885-110

25

0

0

AS-B885-111

25

0

0

AS-B984-100

0

0

0

AS-B984-101

0

0

0

31004128 01 July 2002