Page 41
Upgrade Guide
Replacement of Slot Mount PLCs Compatibility
The ASP890300 is backplane compatible with Slot Mount PLC installations. These include: l PC-0984-380/1/5; PC-E984-381/5 l PC-0984-480/5; PC-E984-480/5 l PC-0984-680/5; PC-E984-685 l PC-0984-780/5; PC-E984-785
AC Power Connector Rewiring
Rewiring is required to accommodate one 2 terminal and one 3 terminal connector, which include a 115/230VAC jumper selection option as opposed to the switch selectable option in the original units. Rewiring requires a small slotted screwdriver. DANGER HAZARDOUS VOLTAGE l Disconnect all power before working on equipment. l Verify correct terminal connections when wiring. Failure to follow this precaution will result in death, serious injury, or equipment damage.
Power Considerations
If replacing high end slot mount PLCs: Both +5VDC I/O power and the Combined load in PC-0984-680/5s and PC-0984-780/5s are rated 1A higher than the ASP890300. If the Primary backplane power requirements exceed the ASP890300 capabilities, enough I/O modules must be removed from the primary backplane to bring the current load within specified limits. In this case, an additional backplane and power supply will need to be added in the configuration unless the extra modules can be added to an existing powered backplane. See I/O Module Current Requirements, p. 46 and Power Supply Capacities in Remote Drop Secondary Applications, p. 45. Secondary backplanes AS-H819-100 and AS-H827-100 support 7 and 11 I/O modules, respectively. Subtract two modules if power supplies need to be added.
Backplane Interconnection Cables
For more information, see Backplane Interconnection Diagrams, p. 42
31004128 01 July 2002
41
Page 42
Upgrade Guide
Backplane Interconnection Diagrams The following illustration shows ASP890300 configurations with no secondary power supply. ASP890300
ASP890300 with No Secondary Power Supply
I/O
AS-W801-002: 1.5’ AS-W801-006: 6.0’ AS-W801-012: 12.0’
AS-W80X-0XX AS-W808-002: AS-W808-006: AS-W808-008: AS-W802-012:
1.5’ 6.0’ 8.0’ 12.0’
AS-W801-XXX
I/O
42
31004128 01 July 2002
Page 43
Upgrade Guide
The following illustration shows ASP890300 configurations with a secondary power supply. ASP890300
ASP890300 with a Secondary Power Supply Installed
AS-W801-002: 1.5’ AS-W801-XXX AS-W801-006: 6.0’ AS-W801-012: 12.0’
31004128 01 July 2002
P8XX
AS-W804-0XX AS-W804-002: 1.5’ AS-W804-006: 6.0’ AS-W804-012: 12.0’
I/O
I/O
43
Page 44
Upgrade Guide
ASP89X Capacity Information Capacity Current Capacity (A) Type
44
+5.0V +4.3V -5.0V
Max Combined +5V and +4.3V Load
Input
AS-P89X-000 3.0
3.0
0.25
3.0
115/230VAC, 0.75A @115VAC, or 24VDC, 2A
ASP890300
6.0
0.5
7.0
115VAC, 1.1A, 50/60Hz 230VAC, 0.65A, 50/60Hz 24VDC, 4A
7.0
31004128 01 July 2002
Page 45
Upgrade Guide
Power Supply Capacities in Remote Drop Secondary Applications Power Supply Capacities
Current Capacity (A) Type
+5.0V
+4.3V
-5.0V
Max Combined +5V Input and +4.3V Load
AS-P800-003
2.5
10.0
0.5
12.5
115/230VAC, 1.5A @115VAC
AS-P801-001
5.0
10.0
0.5
15.0
115/230VAC, 1.7A @115VAC
AS-P802-001
2.5
10.0
0.5
12.5
24VDC, 8A
AS-P810-001
5.0
5.0
0.3
10.0
115/230VAC, 1.6A @115VAC
AS-P830-000
5.0
6.0
0.5
6.0
115/230VAC, 0.5A @115VAC, or 24VDC, 2A
AS-P840-000
5.0
10.0
0.5
15.0*
115/230VAC, 1.1A @115VAC
*55° C max; 12A max @ 60° C
31004128 01 July 2002
45
Page 46
Upgrade Guide
I/O Module Current Requirements Requirements Current (mA) @ Module
46
+5.0V
+4.3V
-5.0V
AS-B802-008
76
240
0
AS-B803-008
27
1
2
AS-B804-116
76
480
0
AS-B804-116
76
480
0
AS-B804-148
76
480
0
AS-B805-016
40
1
14
AS-B806-032
210
1
0
AS-B806-124
210
1
0
AS-B807-132
80
2
0
AS-B808-016
76
480
0
AS-B809-016
42
1
15
AS-B810-008
50
240
0
AS-B814-001
120
220
0
AS-B814-002
120
220
0
AS-B814-108
107
800
0
AS-B817-116
25
2
8
AS-B817-216
25
2
8
AS-B820-008
90
80
0
AS-B821-008
20
0
0
AS-B821-108
27
1
10
AS-B824-016
32
260
0
AS-B825-016
27
1
15
AS-B826-032
90
1
0
AS-B827-032
30
1
0
AS-B828-016
32
220
0
AS-B829-016
120
0
0
AS-B829-116
21
1
0
AS-B832-016
32
235
0
AS-B833-016
27
2
0
31004128 01 July 2002
Page 47
Upgrade Guide
Current (mA) @
31004128 01 July 2002
Module
+5.0V
+4.3V
-5.0V
AS-B836-016
50
603
0
AS-B837-016
40
1
15
AS-B838-032
160
1
0
AS-B840-008
120
220
0
AS-B840-108
67
400
0
AS-B842-008
120
220
0
AS-B846-001
65
1
0
AS-B846-002
65
1
0
AS-B849-016
40
1
15
AS-B853-016
40
1
15
AS-B855-016
80
1
0
AS-B862-001
180
220
0
AS-B863-001
180
220
0
AS-B863-032
250
0
0
AS-B863-132
350
10
0
AS-B864-001
100
100
0
AS-B865-001
400
600
0
AS-B868-001
180
220
0
AS-B869-001
180
220
0
AS-B872-002
540
220
0
AS-B872-011
240
880
0
AS-B872-100
475
5
0
AS-B872-200
750
5
0
AS-B873-001
400
440
0
AS-B873-002
300
300
0
AS-B873-011
300
440
0
AS-B873-012
300
300
0
AS-B875-001
300
440
0
AS-B875-002
300
300
0
AS-B875-011
300
440
0
AS-B875-012
300
300
0
AS-B875-102
650
975
0
AS-B875-111
500
900
0
47
Page 48
Upgrade Guide
Current (mA) @
48
Module
+5.0V
+4.3V
-5.0V
AS-B875-200
550
10
0
AS-B881-001
30
1
0
AS-B881-108
285
240
0
AS-B881-508
300
0
0
AS-B882-032
300
10
0
AS-B882-116
350
10
0
AS-B882-239
188
0
0
AS-B883-001
667
0
0
AS-B883-101
1000
0
0
AS-B883-111
1000
0
0
AS-B883-200
400
5
0
AS-B883-201
640
5
0
AS-B884-002
50
2
0
AS-B885-001
500
1760
0
AS-B885-002
500
1760
0
AS-B885-100
25
0
0
AS-B885-101
25
0
0
AS-B885-110
25
0
0
AS-B885-111
25
0
0
AS-B984-100
0
0
0
AS-B984-101
0
0
0
31004128 01 July 2002