Page 49

ASP890300 Executive Software Reflash

B

At a Glance Purpose

The purpose of this chapter is to provide guidelines for reflash of executive software used in the processor. Executive software can be obtained on the Schneider web site, www.schneiderautomation.com, by selecting the appropriate Firmware location. The ASP890300 executive software is resident in flash RAM and may be updated as required. Reflash requires a PC with an available serial port and loaded with Schneider panel software. Concept contains utilities that may be used. Versions of ProWORX and Modsoft that support Quantum will contain reflash utilities.

What’s in this Chapter?

This chapter contains the following topics:

31004128 01 July 2002

Topic

Page

Interconnection

50

Communication Parameters

51

Procedure

52

49

Page 50

Software Reflash

Interconnection Cables

50

Cables that may be used to connect the panel PC serial port to the ASP890300 ASCII port 1 are: l AS-W952-012 Programming Cable, 12’ l 990NAA26320 Programming Cable, 12’ l 990NAA26350 Programming Cable, 50’

31004128 01 July 2002

Page 51

Software Reflash

Communication Parameters RTU and ASCII Mode

31004128 01 July 2002

Communication parameters for RTU and ASCII modes are shown here: RTU Mode

9600 baud, 8 data bits, Even parity, 1 stop bit

ASCII Mode

9600 baud, 7 data bits, Even parity, 1 stop bit

51

Page 52

Software Reflash

Procedure ASP890300 Executive Reflash Procedure

52

Use the following procedure to reflash the ASP890300 executive software. Step

Action

1

At a time when system operation can be interrupted, turn off power to the ASP890300 and other supplies in the affected drop. Ensure the ASP890300 front panel power switches are in the OFF position.

2

Remove module from the backplane. Note the position of the MODE SELECT switch. The switch should be returned to that position when the reflash sequence has been completed. Set the MODE SELECT switch to position 7 (RTU mode) or 8 (ASCII mode)

3

Connect a communication cable from the panel software PC serial port to the ASP890300 ASCII Port 1 ONLY. Port 2 is not supported.

4

The module may be reinserted into the system backplane and powered. It may also be flashed on the bench, e.g. plugged into a spare non-system backplane and powered on. After power is turned on, the Comm Active LED (third from the top) will blink 9 times, then pause, blink 9 times and pause, etc. This indicates the module is in kernel mode and ready to be flashed.

5

In panel software, display the exec download menu.

6

Use the Direct MB Device selection. The address used should be that selected by the ASP890300 address rotary switches. If connected to a Modbus network, insure there are no address conflicts. Set the communication parameters to those listed above per the mode selection, either RTU or ASCII, and perform the normal executive software loading procedure.

7

After the transfer is complete, the panel software will indicate a timeout error, and there will be no further communication to the P890. Look at the ASP890300 LEDs for confirmation that the flash sequence has succeeded. When an exec download has successfully completed, the front panel LEDs will repeatedly blink in the same sequence from top to bottom as that following a power up. If the operation fails, the Comm Active LED will continue to flash as noted in Step 4. NOTE: Some versions of the built-in exec loader in ProWORX may lock up at the end of the transfer.

8

Power down the ASP890300.

9

Unplug the programming cable from the ASCII Port. Remove the module from its backplane. Set the MODE SELECT switch back to the correct position (noted in Step 2).

10

Insert the ASP890300 into the rack. Turn on power to it and other supplies as required. The ASP890300 should operate normally.

31004128 01 July 2002