Modicon ASP890300 Remote I/O Processor Installation Guide: CE Requirements for ASP890300/ 800 Series I/O Systems

Pages 53 to 56 of 60, from Modicon ASP890300 Remote I/O Processor Installation Guide

The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Modicon AS-H819-209, AEG AS-H819-209, Gould AS-H819-209 and Schneider AS-H819-209

Page 53

CE Requirements for ASP890300/ 800 Series I/O Systems

C

At a Glance Purpose

This chapter covers the installation requirements necessary to maintain compliance with the European Directive for EMC 89/336/EEC for certain 800 Series I/O system components. The majority of 800 Series I/O components are approved per these requirements; however, examine your particular product/shipping carton for the CE mark to ensure approval.

What’s in this Chapter?

This chapter contains the following topics:

31004128 01 July 2002

Topic

Page

Requirements

54

Installation

55

Parts List

56

53

Page 54

CE Requirements for ASP890300/800 Series I/O Systems

Requirements Requirements List

54

The following requirements should be followed for installations complying with the CE marking. l All wiring for power supply and I/O lines must be in grounded steel conduits (EMT) or must use braided shielded cable. If shielded cable is used, the braid must have 80% or more shield coverage, and the outside diameter of the braid (without jacket) must be in the range of 0.189 ... 0.237 in (4.8 ... 6.0 mm). l All cable shields must be grounded, using clips on the Grounding Bar (Modicon part number CER001). Shield is not terminated at module field connector. l Install braided earth ground as shown in Figure 1 from building earth ground to grounding clip (or clips as required) and to backplane ground reference. l Use a 110/220 Vac Line Filter (Schaffner part number FN670-30/6). Install as shown in the AC power input figure.

31004128 01 July 2002

Page 55

CE Requirements for ASP890300/800 Series I/O Systems

Installation Remote Drop Example

The following graphics show the correct CE installation for a remote drop.

From Tap

RI/O Cable

Braided Shielded Cable

Reference Ground Point

To Earth Ground

Tie Wraps to Hold Cables in Grounding Clips (Outputs Only)

Typical CE Installation for a Remote Drop

AC Power In Shield of Cable

Brown

AC Line (Brown)

Brown

AC Neut (Blue) GND (GRN/YEL)

(Blue) Neut (Brown) Hot

Line Filter Blue

Blue Case Tab Shield Earth Ground

GND (Green/Yellow) And Shield To Mounting Screw Of Line Filter

+ _ DC Power In Area Of Detail ASP890300

31004128 01 July 2002

55

Page 56

CE Requirements for ASP890300/800 Series I/O Systems

Parts List Manufacturers Part Numbers/ Instructions Callout

Vendor

Part Number

Description

1

Schaffner

FN670-3/06

Install next to the 984 CPU. Line Filter (Fast on terminals) Dimensions: Length: 3.4 in (85 mm) Width: 2.2 in (55 mm) Height: 1.6 in (40 mm) Mounting Holes: 0.2 in (5.3 mm) dia.: 3 in (75 mm) centerline mounted Fast on Terminals: 0.25 in (6.4 mm)

2

Modicon

CER001 or equivalent

Grounding Bar

3

Instructions

All cable shields must be grounded. NOTE: Not required if using steel conduit.

Flat Ground Braided Cable

4

Oflex

35005 3 conductor 100cy Series

Shielded Cable

The maximum length is 30 in (760 mm); the shield is terminated at the EMI Line Filter, open at CPU end. The third conductor is not used.

5

Oflex

35005 3 conductor 100cy Series

Shielded Cable

Terminate the shield at panel ground, at EMI Filter.

56

31004128 01 July 2002