Page 53
CE Requirements for ASP890300/ 800 Series I/O Systems
C
At a Glance Purpose
This chapter covers the installation requirements necessary to maintain compliance with the European Directive for EMC 89/336/EEC for certain 800 Series I/O system components. The majority of 800 Series I/O components are approved per these requirements; however, examine your particular product/shipping carton for the CE mark to ensure approval.
What’s in this Chapter?
This chapter contains the following topics:
31004128 01 July 2002
Topic
Page
Requirements
54
Installation
55
Parts List
56
53
Page 54
CE Requirements for ASP890300/800 Series I/O Systems
Requirements Requirements List
54
The following requirements should be followed for installations complying with the CE marking. l All wiring for power supply and I/O lines must be in grounded steel conduits (EMT) or must use braided shielded cable. If shielded cable is used, the braid must have 80% or more shield coverage, and the outside diameter of the braid (without jacket) must be in the range of 0.189 ... 0.237 in (4.8 ... 6.0 mm). l All cable shields must be grounded, using clips on the Grounding Bar (Modicon part number CER001). Shield is not terminated at module field connector. l Install braided earth ground as shown in Figure 1 from building earth ground to grounding clip (or clips as required) and to backplane ground reference. l Use a 110/220 Vac Line Filter (Schaffner part number FN670-30/6). Install as shown in the AC power input figure.
31004128 01 July 2002
Page 55
CE Requirements for ASP890300/800 Series I/O Systems
Installation Remote Drop Example
The following graphics show the correct CE installation for a remote drop.
From Tap
RI/O Cable
Braided Shielded Cable
Reference Ground Point
To Earth Ground
Tie Wraps to Hold Cables in Grounding Clips (Outputs Only)
Typical CE Installation for a Remote Drop
AC Power In Shield of Cable
Brown
AC Line (Brown)
Brown
AC Neut (Blue) GND (GRN/YEL)
(Blue) Neut (Brown) Hot
Line Filter Blue
Blue Case Tab Shield Earth Ground
GND (Green/Yellow) And Shield To Mounting Screw Of Line Filter
+ _ DC Power In Area Of Detail ASP890300
31004128 01 July 2002
55
Page 56
CE Requirements for ASP890300/800 Series I/O Systems
Parts List Manufacturers Part Numbers/ Instructions Callout
Vendor
Part Number
Description
1
Schaffner
FN670-3/06
Install next to the 984 CPU. Line Filter (Fast on terminals) Dimensions: Length: 3.4 in (85 mm) Width: 2.2 in (55 mm) Height: 1.6 in (40 mm) Mounting Holes: 0.2 in (5.3 mm) dia.: 3 in (75 mm) centerline mounted Fast on Terminals: 0.25 in (6.4 mm)
2
Modicon
CER001 or equivalent
Grounding Bar
3
Instructions
All cable shields must be grounded. NOTE: Not required if using steel conduit.
Flat Ground Braided Cable
4
Oflex
35005 3 conductor 100cy Series
Shielded Cable
The maximum length is 30 in (760 mm); the shield is terminated at the EMI Line Filter, open at CPU end. The third conductor is not used.
5
Oflex
35005 3 conductor 100cy Series
Shielded Cable
Terminate the shield at panel ground, at EMI Filter.
56