Page 1 read from a scan by OCR; it may hold reading errors

Andover Continuum

Power Supply Reference

Schneider MH eElectric

Page 2

© 2010, Schneider Electric All Rights Reserved No part of this publication may be reproduced, read or stored in a retrieval system, or transmitted, in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without prior written permission of Schneider Electric. This document is produced in the United States of America. Infinity is a trademark of Schneider Electric. All other trademarks are the property of their respective owners. Andover Continuum Power Supply Reference Rev. G March, 2010 Schneider Electric part number: 30-3001-702 NetController firmware version: 1.53 Related Documents: Andover Continuum I/O System Reference, 30-3001-499 Andover Continuum NetController Reference, 30-3001-703 Andover Continuum Enclosure and Display Module Reference, 30-3001-711 Smoke Control system Design Guide for Continuum, 30-3001-734 Andover Continuum UL 1076 Burglar Alarm System Reference, 30-3001-800 Andover Continuum Access Control Systems Reference, 30-3001-746 The information in this document is furnished for informational purposes only, is subject to change without notice, and should not be construed as a commitment by Schneider Electric. Schneider Electric assumes no liability for any errors or inaccuracies that may appear in this document. On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric. However, there remain references to TAC as a corporate brand throughout the Andover Continuum software. In those instances, the documentation tet still refers to TAC - only to portray the use interface accurately. As the software is updated, these documentation references will be changed to reflect appropriate brand and software changes. All brand names, trademarks, and registered marks are the property of their respective owners. Schneider Electric One High Street North Andover, MA 01845 (978) 975-9600 Fax: (978) 975-9782 http://www.schneider-electric.com/buildings ii

Schneider Electric

Page 3

Regulatory Notices

Radio Interference – Federal Communications Commission This equipment has been tested, and it complies with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions in this manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case you will be required to correct the interference at your own expense.

Radio Interference – Canadian Department of Communications This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.

Brouillage Radioélectrique – Ministère des Communications du Canada Le présent appareil numérique n’émet pas de bruits radioélectriques dépassant les limites applicables aux appareils numériques de la Classe A prescrites dans le Règlement sur le brouillage radioélectrique édicté par le ministère des Communications du Canada.

CE – Compliance to European Union (EU) This equipment complies with the European Union (EU) standards specified in the EU EMC directive 89/336/EEC and/or the product-safety low voltage directive 73/23/EEC, governing the European community.

Andover Continuum Power Supply Reference iii

Page 4

C-Tick – Australian Communications Authority (ACA) This equipment carries the C-Tick label and complies with EMC and radio communications regulations of the Australian Communications Authority (ACA), governing the Australian and New Zealand communities.

WEEE – Directive of the European Union (EU) This equipment and its packaging carry the waste electrical and electronic equipment (WEEE) label, in compliance with European Union (EU) Directive 2002/96/EC, governing the disposal and recycling of electrical and electronic equipment in the European community.

iv

Schneider Electric

Page 5

Contents Introduction ............................................................... 1 Power Module Characteristics .................................. 2 Special System Characteristics................................. 3 Mechanical Installation.............................................. 4 Input Power Connection............................................ 7 Building Ground Requirements ................................. 9 DC Input Power Connection.................................... 10 UPS Connections.................................................... 11 External Power Indicator Connection...................... 12 Output Power Connection ....................................... 13 Output Connections ................................................ 14 Auxiliary Power Connection .................................... 15 Auxiliary Supply Conversion ................................... 16 Operation ................................................................ 19 Troubleshooting ...................................................... 20

Andover Continuum Power Supply Reference v

Page 6

vi

Schneider Electric

Page 7

TCX 865 Power Supplies

Introduction This manual describes the installation, care and use of the Andover Continuum power supply modules. The Andover Continuum power supply modules are part of the Schneider Electric Andover Continuum Ethernet-based intelligent building system. The Andover Continuum system allows you to cost-effectively mix and match DIN rail-mounted CPU, power supply, and various combinations of I/O modules and user interfaces to meet your control and monitoring needs. The power supplies offered include an impressive array of features. Including the standard 120/240 VAC modules, some models reduce or eliminate the impact of power failure through a built-in battery back-up system with integral charger. Another allows – 48VDC power based industries such as telecommunications to provide uninterrupted power to critical environmental monitoring and control equipment using their own battery-backed power systems. Each module includes provision for an optional AC power indicator LED. This option is ideal if you mount your Andover Continuum system within a larger control panel or enclosure and wish to verify power to the system from a separate location. The power supply modules feature a casing designed for natural convection cooling. Quick-release fasteners, built-into the back of the module, are provided for DIN rail mounting⎯no tools required. These fasteners also snap into a locked position that features integral reinforced holes for panel mounting in non-DIN situations.

Andover Continuum Power Supply Reference

1

Page 8

Power Module Characteristics The following table lists the features included in the Andover Continuum power supply modules: Model

Input Voltage

Power Output

PS 120/240 AC 50*

120-240 VAC

50 W

PS 120/240 AC 50-U* †

120-240 VAC

35 W

PS 120/240 AC 65

120-240 VAC

65 W

PS 120/240 AC 65-U

120-240 VAC

50 W

PS 120/240 AC 85

120-240 VAC

85 W

PS 120/240 AC 85-U †

120-240 VAC

70 W

UPS

PS –48 DC 50*

-48 VDC

50 W

DC Input

PS –48 DC 50-U PS 120/240 AC 25

-48 VDC 120-240 VAC

50 W 5V @25 W

DC Input, UPS

* These units are listed for use in UL 294 applications.

Features UPS UPS

† These units are listed for UL 1076

PS 120/240 AC 50-U, PS 120/240 AC 65-U, PS 120/240 AC 85-U, PS –48 DC 50-U These modules provide 35, 70 and 50 Watts (respectively) of power for the CPU and I/O modules. They contain features that reduce or eliminate the impact of power failure. An external 24 VDC battery source may be connected to provide uninterruptible power. A built-in battery charger assures the battery is charged at all times. Using standard rechargeable lead acid batteries, this unit provides full UPS operation including all I/O modules for up to 60 minutes at 35 watts power consumption; full operation of the CPU module only (including modem and network interface) with no I/O power for 4 hours; or backup of DRAM and real-time clock only for 72 hours duration. These backup modes are selected and controlled through Schneider Electric’s Plain English® programming language.

PS 120/240 AC 50, PS 120/240 AC 65, PS 120/240 AC 85 These power supplies are non-UPS versions of the above listed modules. They supply a full 50 and 85 Watts (respectively) of power and can also be used as auxiliary power sources to power additional I/O modules directly, extending the capabilities of a typical Andover Continuum system, even to remote locations.

PS –48 DC 50 This model accepts a –48 VDC input voltage that allows industries such as telecommunications to provide uninterrupted power to critical environmental monitoring and control equipment using their own battery-backed power systems. 2

Schneider Electric

Page 9

PS 120/240 AC 25 This power supply provides a +5VDC output at 25 Watts of power and is used as an external power source to power third party devices and sensors.

Special System Characteristics Smoke Control Operation (UL 864) Power Supplies available through Schneider Electric that are listed with UL for Smoke Control applications and the options pertaining to smoke control operation are the following: Model

Input Voltage

Power Output

PS 120/240 AC 65*

120-240 VAC

65 W

PS 120/240 AC 65-U*

120-240 VAC

50 W

PS 120/240 AC 50

120-240 VAC

50 W

PS 120/240 AC 50-U

120-240 VAC

35 W

PS 120/240 AC 25

120-240 VAC

5V @25 W

Features

UPS

UPS

* The 24VDC output is not power limited. When the supply is not connected directly into a NetController the AC Power and Low Battery logic outputs (pins 1&2) should not be used.

Access Control Operation (UL 294), Burglar Alarm Operation (UL 1076) Power Supplies available through Schneider Electric that are listed with UL for Access Control and Burglar Alarm applications are the following: Model

Input Voltage

Power Output

PS 120/240 AC 85

120-240 VAC

85 W

PS 120/240 AC 85-U

120-240 VAC

70 W

PS 120/240 AC 50

120-240 VAC

50 W

PS 120/240 AC 50-U

120-240 VAC

35 W

PS -48 DC 50

- 48 VDC

50 W

Features

UPS

UPS

Andover Continuum Power Supply Reference

3

Page 10

Mechanical Installation NOTE TO INSTALLER: This device must be properly installed to suit its intended application. EUROPEAN INSTALLATIONS: These power supplies are listed as Class 1 devices intended for installation in an IP2 enclosure. The Andover Continuum Enclosure is an IP2 enclosure. ATTENTION: Disconnect from supply before removing! The power supply modules can be mounted to a standard DIN rail or be directly mounted to a panel using screws. Hardware facilitating both mounting methods is included as an integral part of the case design. On the back of each module are molded DIN rail guide fingers. The design allows the module to easily hook onto and slide along a standard DIN rail.

Special clamps are provided on the case, allowing you to lock the module in place, once it is in position.

4