Page 21
Auxiliary Power Connection PS 120/240 AC 50(U), AC 65(U), AC 85(U) In situations where a large number of I/O modules are used, the power available from one supply module may not be sufficient. In these scenarios an auxiliary power supply can be connected to supply necessary power to the extended I/O group. All Andover Continuum power supply models can be used as auxiliary power supplies. However, the UPS versions must be modified slightly before it is used. Generally the auxiliary power supply is added to a remotely located group of I/O modules. The I/O modules that are to be powered by the auxiliary supply still connect to the other modules so that data may flow between the functional blocks of the system, however, these I/O modules must receive power from only the auxiliary supply. A 2-conductor shielded cable eliminating the 24 VDC signals (pins 4 & 5) is connected between the last I/O module powered by the main power supply and the remotely located I/O modules powered by the auxiliary supply:
Main Power Supply
CPU
4-Conductor Shielded Cable
2-Conductor Shielded Cable
Aux. Power Supply
From I/O Modules powered by Main power supply
5 4 3 2 1
5 4 3 2 1
I/O Modules powered by Aux. power supply
Specific information regarding cable preparation and overall system layout may be found in the Andover Continuum I/O System Reference, 30-3001-499.
Andover Continuum Power Supply Reference
15
Page 22
Auxiliary Supply Conversion PS 120/240 AC 50-U, AC 65-U and AC 85-U The UPS versions of the 120/240 AC power supply include two status signals that are meant for use by a CPU module. When connecting directly to an I/O module you want to disable these signals. There are two versions of the printed circuit board within the Power Supply. One includes a mode switch, the other requires components to be removed. On newer versions of the supply, a Mode switch inside the cover allows you to easily disable these signals. In order to access these components you must remove the plastic cover from the case. 1
Remove power from the unit.
2
Press both cover removal tabs inward simultaneously and pull up: 3XOO&RYHU8SZDUG ZLWK7DEV'HSUHVVHG
3UHVV7KHVH7DEV
3
Locate the Mode switch using the diagram below:
I/O AUX
CPU (UPS)
-
Mode Switch: CPU (UPS)
AUXILIARY OPERATION I/O AUX
16
Schneider Electric
CPU (UPS)
NORMAL OPERATION I/O AUX
Page 23
With the tip of a small screwdriver, carefully slide the switch to the AUX position. To reverse this change, simply slide the switch back to the CPU position. 4
Replace the cover.
On older versions of the supply, two jumper components must be removed from the printed circuit board. In order to access these components you must remove the plastic cover from the case. 1
Press both cover removal tabs inward simultaneously: 3XOO&RYHU8SZDUG ZLWK7DEV'HSUHVVHG
3UHVV7KHVH7DEV
2
Locate the two jumper components using the diagram below: -
-
5HPRYH &RPSRQHQWV --
3
Carefully snip (cut) the wire leads of each of the two components. Be sure to snip only the leads for these components. Other components in close proximity to these are important to the operation of the supply.
4
Replace the cover.
Andover Continuum Power Supply Reference
17
Page 24
PS 120/240 AC 25 Output Connection The PS 120/240 AC 25 is an auxiliary +5V power supply that is designed to power accessory devices such as the EnergyLink 2500 Ethernet converters. The following is a typical connection application: 5 4 3
PS 120/240 AC 25
+5V SHLD
GND
SHLD GND +5V
18
Schneider Electric
ENL 2500 Series
Page 25
Operation Power On After installation, to apply power to the system, the power switch located on the left side of the power module case must be depressed. The switch is a rocker type with each side marked according to function. Pressing the side marked with the I turns the power on. To remove power, press the side marked O. Status Indicators The power supply includes a green Main Power indicator, which when illuminated indicates that primary power (AC or DC) is applied and the power switch is turned on.
The UPS model also includes another indicator reporting the presence of backup battery power. When the power supply is in UPS backup mode this indicator illuminates in a yellow color.
Andover Continuum Power Supply Reference
19
Page 26
Troubleshooting No Response to Power Switch If there are no indicators displayed on the status panel after power-up, the unit is not operating. This could be due to the loss of primary AC power or other internal dysfunction. •
Check that power is available and connected properly to the AC or DC Input power terminals. This can be done using a multimeter.
•
If input power appears to be OK, remove power and all other connections from the unit. Open the cover. Remove the plug-in power fuse component(s) and check for continuity with an Ohm meter. If the fuse is blown, replace it with a similar value fuse (see diagrams). After replacement, replace the cover.
PS 120/240 AC 50, AC 65, AC 85
$PS 9'& 6ORZ%ORZ)XVH
20
Schneider Electric
Page 27
PS 120/240 AC 50-U, AC 65-U, AC 85-U
Andover P/N: 01-2100-207
Andover P/N: 01-2100-039
PS –48 DC 50
7 Amp 90 VDC Fuse
5 Amp 250 VDC Fuse Andover P/N: 01-2100-403
The UPS model includes a separate Picofuse for the battery. The fuse is inserted into socket holes on the board. To remove, gently pull the fuse from the board.
Andover Continuum Power Supply Reference
21
Page 28
PS –48 DC 50-U
The –48V models include a Picofuse. The fuse is inserted into socket holes on the board. To remove, gently pull the fuse from the board.
22
Schneider Electric
Page 29
Andover Continuum Power Supply Reference
Page 30
Andover Continuum Power Supply Reference Document Number 30-3001-702 Rev. G
30-3001-702
Andover Continuum Power Supply Reference