Page 136

When the MCS condition (enclosed with dotted line) is OFF, the instructions existing between MCS and MCR will be handled in the following manner. 00000

00002

F-30 MCS

00001

00400

00003

MCS condition

00003 00400 is OFF because it is OFF.

MCS condition

00004 TMR 000

MCS condition

00005 CNT 001

00006

00007

00004

0020

00005 00006

0100

MCS condition Shift direction

TMR is reset because it is OFF. TMR contact turns OFF and the current value to the setting value. ON reset Retained

OFF

Current value

Retained

Setting value

ON reset

OFF reset

09010

Retained

Cleared

Flag

Cleared

Cleared

ON reset

OFF reset

09100

Retained

Cleared

Flag

Cleared

Cleared

00007 00010

00010

00011

00012

Data input Shift input

00011

F-60 SFR 09010

Because it is OFF.

00012

Reset input MCS condition

00013

F-62 09100 U/DC

9

00013 00014

00014

OFF reset

Because CNT contact it is OFF.

00015

Because it is OFF.

00015

MCS condition 00016

00017

00016

F-00 09110 09120 XFER

F-32 04000 SET

No operation is executed because it is OFF. Flag

MCS condition

00017 00020

Flag unaffecting instruction

No change

Flag affecting instruction

Cleared

No operation is executed because it is OFF.

00020

F-33 04000 RST

F-31 MCR

Note 4: With a CNT, F-60, or F-62 instruction, it is possible to ON reset or OFF reset the reset condition using the system memory #202. In case of the OFF reset, reset is done by MCS.

9-61

Page 137

F-32 SET Symbol

Set coil F-32 SET

〔Example for use〕

R

04000

Function

Activate a coil specified by relay number R when the set input is turned ON.

Operation

Activate the R specified by F-32.

After operation

9

Symbol

Set input is at ON (not limited to OFF to ON change) Set input ON 04000 OFF

Contents ON of R

Flag

00400

Unchanged

ON OFF

Note 3: It is recommended that the F-32 (SET) instruction be used in conjunction with the F-33 instruction described on the next item. Note 4: The F-32 (SET) and F-33 (RST) instructions placed between the F-30 (MCS) and F-31 (MCR) instructions are not operative if the operational condition of the F-30 (MCS) is OFF.

Reset coil F-33 RST

〔Example for use〕

R

04002

Function

Deactivate a coil specified by relay number R when the reset input is turned ON.

Operation

Deactivate the R specified by F-33.

Range of R

00400 to 15777

Condition

Reset input is at ON (not limited to OFF to ON change)

After operation

00400

When the set input of 04000 is ON, this instruction sets ON 00400. Once sets ON, 00400 remains ON after the set input is set to OFF. When the set input of 04000 is OFF, this instruction does not affect the state of 00400.

Note 1: If the relay specified by the F-32 (SET) instruction is within the latched relay area, it maintains the last state when the power is recovered from power failure. If the specified relay is outside the latched relay area, it is reset upon power recovery. Note 2: The relay assigned by F-32 (SET) instruction is set to latch output when the JW10 stops operation (system memory #206 = 55(H)), it maintains status before stop operation. If the assigned relay is set to reset output when the JW10 stops operation system memory #206 = 00(H)), it resets at stoppage.

F-33 RST

00400

Set input

Range of OUT 00400 to 15777

Condition

F-32 SET

Instruction 04000

STR F-32

00410

00410

When the reset input of 04002 is ON, this instruction sets OFF 00410. Once sets OFF, 00410 remains OFF after the reset input is set to OFF. When the reset input of 04002 is OFF, this instruction does not affect the state of 00410. Reset input ON 04002 OFF ON 00410 OFF

Contents OFF of R

Flag

Reset input

F-33 RST

Instruction 04002 STR F-33

Unchanged

Note 1: If the relay specified by the F-33 (RST) instruction is within the latched relay area, the last state is retained when the power is recovered from power failure. If the specified relay is outside the latched relay area, it is reset upon power recovery.

Note 2: The relay assigned by F-33 (RST) instruction is set to latch output when the JW10 stops operation (system memory #206 = 55(H)), it maintains status before stop operation. If the assigned relay is set to reset output when the JW10 stops operation system memory #206 = 00(H)).

9-62

Page 138

• The F-32 (SET) and F-33 (RST) instructions allow to output relay to be controlled under more than 1 condition.

04130

F-32 SET

Set input 04131

F-32 SET

Set input 04132

F-32 SET

Set input

• If the set and reset inputs are turned ON or OFF more than 1 time in 1 scan cycle, the data memory used as the relay R is set and reset repeatedly in 1 scan cycle. The result of the relay R (ON or OFF) appearing immediately before I/O processing should be sent to the output terminal, however.

00400

I/O Processing

I/O Processing

I/O Processing

User program execution

00400 Set input

ON OFF

Reset input

ON OFF

00400

ON OUT (Data memory) OFF ① ② ③

04133 Reset input 04134 Reset input

F-33 RST

00400

F-33 RST

00400

OUT (Output)

ON OFF OFF Not monitorable at ①, ②, ③.

During execution of user program, even the data memory turns ON/OFF more than one time, only the result just before I/O processing can be monitored.

9 • It is recommended that the F-32 (SET) and F-33 (RST) instruction be used in pair. It will simplify the self holding circult.

Reset priority self holding circuit

Set priority self holding circuit 04005

04005 04100

00400

00400 Set 00400 04100

Set Reset 00400

Reset

04100 04005 Set input

F-32 SET

00400

Reset input 04005

04100 Reset input

F-33 RST

00400

Set input

F-33 RST

00400

F-32 SET

00400

Set input 04005

ON OFF

Set input 04005

ON OFF

Reset input 04100

ON OFF

Reset input 04100

ON OFF

OUT 00400

ON OFF

OUT 00400

ON OFF

9-63

Page 139

F-34 TSET Symbol

Comparison with current value of clock This instruction is able to program by JW-1424K/1442K/ (specified relay set) 1624K/1642K and is not able to program by JW-1324K/1342K. F-34 TSET n1 n2

〔Example for use〕

BIT

Function

Compares the constants n1 (hours) and n2 (minutes) with the current value of the clock and sets (turns ON) the specified BIT (relay) if they match.

Operation

Compares the current value of the clock with n1 and n2, and turns ON the relay if the comparison result shows a match.

04002

F-34 TSET

15

30

00400

Instruction 04002 STR F-34 15 30 00400

When input condition 04002 is ON and at 15 hour 30 minutes, relay 00400 turns ON. The relay 00400 which was turned ON remains ON even if input condition 04002 turns OFF. If the current value of the clock is except at 15 hour 30 minutes, the state of relay 00400 does not change.

Range of n1 00 to 23 (decimal) Range of n2 00 to 59 (decimal) Range of BIT 00400 to 15777 Condition

9

After operation

When the input signal is ON (not limited to OFF to ON change) Contents Unchanged of n1 Contents Unchanged of n2 When the assigned time does not match with the clock's current Contents value, the bit condition does not change. of BIT When the assigned time matches with the clock's current value, this bit turns ON. Flag

Unchanged

Note 1: If the relay specified by the F-34 (TSET) instruction is within the latch specified area, it retains its state that existed before the power failure even after power is restored. If the specified relay is outside the latch specified area, it is reset when power is restored.

Note 2: A relay assigned by F-34 (TSET) instruction is set to latch output when the JW10 stops operation (system memory #206 = 55(H)), it maintains status before stop operation. If the assigned relay is set to reset output when the JW10 stops operation system memory #206 = 00(H)), it resets at stoppage. Note 3: Use the F-34 (TSET) instruction as a pair with the F-35 (TRST) instruction on the next page. Note 4: Any F-34 (TSET) and F-35 (TRST) instructions between the F-30 (MCS) and F-31 (MCR) instructions do not function when the operational condition for the F-30 (MCS) instruction is OFF.

9-64

Page 140

F-35 TRST Symbol

Comparison with current value of clock instruction is able to program by JW-1424K/1442K/ (specified relay reset) This 1624K/1642K and is not able to program by JW-1324K/1342K. F-35 TRST n1 n2

〔Example for use〕

BIT

Function

Compares the constants n1 (hours) and n2 (minutes) with the current value of the clock and resets (turns OFF) the specified BIT (relay) if they match.

Operation

Compares the current value of the clock with n1 and n2, and turns OFF the relay if the comparison result shows a match.

Range of n1 00 to 23 (decimal) Range of n2 00 to 59 (decimal)

04003

F-35 TRST

09

15

00410

Instruction 04003 STR F-35 09 15 00410

When input condition 04003 is ON and at 9 hours 15 minutes, relay 00410 turns OFF. The relay which was turned OFF remains OFF even if input condition 04003 turns OFF. If the current value of the clock is except at 9 hour 15 minutes, the state of relay 00410 does not change.

Range of BIT 00400 to 15777 Condition

After operation

When the input signal is ON (not limited to OFF to ON change) Contents Unchanged of n1 Contents Unchanged of n2 When the assigned time does not match with the clock's current Contents value, the bit condition does not change. of BIT When the assigned time matches with the clock's current value, this bit turns OFF. Flag

9

Unchanged

Note 1: If the relay specified by the F-35 (TRST) instruction is within the latch specified area, it retains its state that existed before the power failure even after power is restored. If the specified relay is outside the latch specified area, it is reset when power is restored.

9-65

Note 2: A relay assigned by F-35 (TRST) instruction is set to latch output when the JW10 stops operation (system memory #206 = 55(H)), it maintains status before stop operation. If the assigned relay is set to reset output when the JW10 stops operation system memory #206 = 00(H)), it resets at stoppage.

Page 141

F-40 END

End instruction (END)

The F-40 instruction indicates the end of the program. There is no need of writing the END instruction, except for the following cases, because it will be automatically set in the last address of the program memory when the memory is cleared. (1) Saving scan time • The scan time is the I/O processing time

9

00000

STR

00100

00000

STR

00100 added with the user program execution time. 00001 OR 00011 00011 00001 OR The user program execution time is the total 00002 AND 00021 00002 AND 00021 00003 OUT 00400 time required to execute all instructions from 00003 OUT 00400 00004 STR 00111 00004 STR 00111 the program address 00000 to the END instruction. 01776 AND 00131 01776 AND 00131 • The location of the END instruction 01777 OUT 00470 01777 OUT 00470 NOP 02000 02000 F-40 automatically written after program is 02001 NOP 02001 NOP memory clear, for instance, 02777 (1535th 02002 NOP 02002 NOP word) in the case of basic module is 02776 NOP JW-1324K/1342K and 07777(4096th word) 02776 NOP 02777 F-40 02777 F-40 in case of it is JW1424K/1442K/1624K/1642K. (a) END (02777) only by memory clear (b) F-40 (END)is written in 02000 • Assume now if the last address is 01777 (1024th word) when the ladder chart has written by the support tool such as JW-13PG, 02000 to 12776 are padded with NOP instruction with the END instruction in 02777, so that it requires an unwanted time in order to execute NOP instructions (JW-1324K/1342K is 1.63 µs, JW-1424K/1442K/1624K/1642K is 0.81 µs per word). • If F-40 was written in 02000, it saves the processing time without executing those unwanted NOP instructions, and the control can proceed to a next scan cycle after termination of the user program. (2) To perform a partial program execution during trial run By inserting the F-40 instruction at the end of a sequence block, you will be able to execute only the required portion of the program. If the result was successful, the F-40 may then be deleted.

Note 1: A multiple number of F-40 may exist when the END instruction is written in (1) and (2). In this case, the userprogram terminates at the first F-40. So, it would be necessary to check the location of the END instruction before going into the actual operation. Note 2: The F-40 (END) instruction is unconditional, and it prohibits the following kind of programming.

00010

F-40 END F-40 END

Note 3: Although the F-40 instruction has the highest priority, it will be ignored if an END instruction exists between F-141 (JMP) and F-140 (LABL) or between F-142 (CALL) and F-140 (LABL) and that F-141 or F-142 was executed. 9-66

Page 142

F-41 JCS F-42 JCR

Set jump control (Jump Control Set) Reset jump Control (Jump Control Reset)

When the F-41 (JCS) condition is OFF, all instructions will not be executed, except the F-40 (END) instruction that exists before the F-42 (JCR) instruction. Therefore, it does affect the contents of the data memory, even if there was an instruction that writes the result in the data memory, such as OUT, TMR, CNT, and application instruction. And, it retains the state when JCS condition is ON.

00010

Instruction 00010 STR F-41 STR 00011 00401 OUT 00012 STR 000 TMR 0030 T000 STR 00402 OUT 00013 STR 00014 STR 001 CNT 0010 C001 STR 00403 OUT 00015 STR F-63 09000 F-42

F-41 JCS 00401

00011

00012

TMR 000

0030 00402

T000

00013 CNT 001

00014

0010

00403

C001 00015

F-63 INC

09000

F-42 JCR

00010 (F-41 condition) 00011 00401 (Output) 00012 (Start input)

1.0 second

00402 (Output)

2.0 second

00013 (Counter input) 00014 (Reset input) CNT 001 (Current value)

OFF

0001 0001

0001 0001

0001 0001

0001 0000

00403 (Output) 00015 09000

021 022

022 023

9-67

9

Page 143

Note 1: Attention must be paid to the TMR internal clock (0.1 second clock), CNT counter input and application instruction input condition (which the operation takes place at an OFF to ON transition in the input condition), and F-41 (JCS) condition ON/OFF timing.

JCS condition Input condition

A A

Note 6: F-41 (JCS) and F-42 can be nested between F-30 (MCS) and F-31 (MCR). However, between JCS instruction and JCR instruction are not executed regardless whether the JCS condition be ON or OFF when the MCS condition is OFF.

B B

①

②

ON

ON (Not executed)

C C

③

④

00020

OFF

00021

- Operation takes place at a rising of ① because

9

F-30 MCS

ON (Executed)

the JCS condition is ON. - Operation does not take place at a rising of ② because the JCS condition is OFF. - Operation does not take place at a rising of ③ because the JCS condition is OFF. - The JCS condition turns to ON while ③ is ON, but operation does not take place as it does not recognize that the input condition has changed from OFF to ON, because the input condition is ON with which theJCS condition of A changes from ON to OFF and the input condition is ON with which the JCS condition of B changes from OFF to ON. - Operation does not take place at a rising of ④ because the JCS condition is OFF. - The JCS condition becomes ON while ④ is ON. Operation takes place immediately after the JCS condition of C changes from OFF to ON because there was no change in that the input condition is OFF with which the JCS condition of B changes from ON to OFF and the input condition is ON with which the JCS condition of C changes from OFF to ON.

00022

00410

F-41 JCS

00023

00411

00024

TMR 0025 010 F-42 JCR F-31 MCR

00026

00412

Instruction 00020 STR F-30 00021 STR 00410 OUT 00022 STR F-41 STR OUT STR TMR F-42 F-31 STR OUT

MCS condition (00020) Input (00021) Output (00410) JCS condition (00022)

Note 2: The END instruction will be executed regardless whether the JCS condition be ON or OFF when there was an F-40(END) instruction between F-41(JCS) and F-42(JCR). And the user program execution is terminated and the control proceeds to the next scan cycle. Note 3: It is not possible to insert another F-41 and F-42 between F-41 (JCS) and F-42 (JCR). It will evoke "JCS ERROR" on the hand-held programmer during program check, if such a program was written.

Input (00023) Output (00411) Start input (00024) 2.5 seconds

TMR not reset

Note 4: F-42(JCR) is an unconditional instruction. 00010 F-42 JCR It prohibits the program like shown above. Note 5: To use an application instruction that operates at a rising edge of F-41 (JCS) and F-42 (JCR), the input condition must be different from F-41 (JCS). No operation will take place if the condition is same.

9-68

TMR reset

00023 00411 00024 010 0025

00026 00412

Page 144

F-43 CPL

Complement bit (ComPLement)

The F-43 instruction complements the bit in the accumulator.

00100

04001

F-43 instruction STR 00100 AND 04001 F-43 OUT 00407

00407

00100

04001

00407

Results from the STR instruction to the F-43 instruction are complemented and sent to the output relay 00407. Use of F-43 permits to obtain the complemented output without the use of auxiliary contact. 00000 00001 00003 04100

00000 00001 00003 F-43 00400

00002

00002

04100

00400

Note 1: The F-43 instruction may be used for a single or a multiple number of contacts. Note 2: Pay attention that the following programs (a) and (b) will not produce the same result because the F-43 instruction is the instruction that complement the contents of the accumulator.

00000 00001

F-43

00002

00400

00000 00001

F-43

00000 00002

(a)

(b)

9-69

00400

9

Page 145

Differentiate at ON

F-44 ↑

The F-44 instruction sends 1 scan time pulse when the immediate state of the accumulator changes from OFF to ON.

00000 00001 F-44

Instruction 00000 STR 00001 AND F-44 04000 OUT

04000

00000

00001 Output 04000 1scan time

1scan time

Note 1:Note that a different result is produced when the sequence of the F-44 program is changed in the above ladder chart. (Identical in case of F-45.)

Note 3: 00010 00011

F-44

00400

00012 00000

F-44

00001

04000

9

Accumulator ACC 00000

STR 00010

Output from F-44

STR 00011 1 scan time

STR STR F-44 OR AND OUT

00010 00011 00012 STR 00400

Stack register S1

00010

00011

00010

1 scan time

F-44 00001

OR

Output 04000 1 scan time

00011

F-44

00011

F-44

00012

00010

00010

00012 00010 00011 F-44

AND STR

00012 00010 00011 F-44

Note 2: The F-44 instruction scans only once even if inserted between an F-47 instruction (level operation condition set) and an F-48 instruction (level operation condition reset). (See F-47 and F48.)

OUT 00400

00012

The accumulator turns ON for only a scan cycle that 00011 changed from OFF to ON. 00010

00011

00012 △t 00100 △t 1 scan time

Differential signal is not issued.

In the above example, a differential signal is not issued even if 00010 has changed from OFF to ON when 00011 is ON, because 00010 is ANDed by the AND/STR instruction.

9・ 70