Page 10

Chapter 1. Outline The New Satellite JW10 is a programmable controller (hereafter referred to as "PC") for controlling small scale circuit systems up to 124 of input and output points. Feature 1 Selection of 13 modules JW10 is a compact and module type PC which has all components integrated one body. You can choose from six models of basic modules , five models of expansion module ,and analog input/ output module in accordance with control scale and contents which are used. Outline Model name DC input 16 points, relay output 12 points Unavailable for expansion JW-1324K DC input 16 points(high speed response), transistor output 12 points Unavailable for expansion Basic module JW-1342K DC input 24 points, relay output 16 points *1 JW-1424K DC input 24 points(high speed response), transistor output 16 points *1 JW-1442K DC input 36 points, relay output 24 points *1 JW-1624K DC input 36 points(high speed response), transistor output 24 points *1 JW-1642K DC input 16 points Expansion JW-112N Transistor output 16 points module JW-112S Relay output 16 points JW-114S JW-1124NS DC input 8 points, relay output 8 points JW-1324NS DC input 16 points, relay output 16 points 4 channels 0 to 10V → Binary 12 bits *2 A n a l o g i n p u t JW-14AD 0 to 20mA → Binary 11 bits module 2 channels Binary 12 bits → 0 to 10V *2 Analog output JW-12DA Binary 11 bits → 0 to 20mA module *1 The basic modules, the JW-1424K, JW-1442K, JW-1624K, and JW-1642K, can be connected to 2 expansion modules, 1 analog input module, and 1 analog output module. *2 The JW-14AD and JW-12DA can be connected to any basic module that is version 2.0 or later. Module name

Feature 2 Large memory capacity and variety of application instructions Though the JW10 is a compact PC, it is equipped with a large capacity data memory of 6,656 points of auxiliary relays and 2,048 bytes of registers. The JW10 has a variety of application instructions such as logical operation instruction, arithmetic operation instruction, comparison instruction, etc. so that it can be used for processing data. Feature 3 Equipped with three types of communication function as standard The JW10 is equipped with three types of communication functions: computer link, data link, and remote I/O, as standard. You can construct a network system without any additional modules. (Select one from the three communication functions for use.) (1) Computer link • Enables data communication between one host computer and maximum 63 modules of JW10. (2) Data link • Enables data communication between one JW10 master station and maximum seven modules of JW10 slave stations which can communicate 8 bytes of data for each transmission and reception per one station. (3) Remote I/O • Enables remote data input and output between one JW10 master station and maximum four modules JW10 slave stations and is able to transmit data through 36 points of input and 24 points of output per one station. Data link and remote I/O functions are available using upper model JW20H/30H as a master station and JW10 as slave stations.

1-1

1

Page 11

1

Feature 4 MMI port to be used for computer link Connection port (MMI port) of support tool can be used as computer link. Feature 5 High-speed counter is integrated The JW10 incorporates high-speed counter (two points of single-phase rising pulse input, or one point of 90-degree phase difference 2-phase signals) of maximum frequency 10 kHz so that it can easily receive pulses from rotary encoders.

Data converting software "Mitaro JW10" to export data to a table calculation software "Microsoft Excel*" is available. Using this software, JW10 data can be automatically exported to an Excel work sheet without need of any another software. For details, see the separate manual. * Registered trade mark of Microsoft Corporation, USA.

Version of the basic module The system ROM on the basic module has been upgraded by adding new functions. The relation between the additional functions and the corresponding ROM versions are listed in the following table. Additional functions Set system memory #055 (Set run/stop in error of program check) Connection of analog input module (JW14AD) and analog output module (JW-12DA) Remote I/O slave station battery error flag

ROM version

See page

1.4 or later

7-12

2.0 or later

15-1 to 15-10

2.3 or later

13-32

Your system ROM version number can be checked at system memory address #041. (See page 7-11)

1-2

Page 12

Chapter 2. Safety Precautions (1) Setup environment Avoid keeping the JW10 in the following conditions: • Direct sunlight. • Relative humidity which exceeds the range of 5 to 90 %. No condensation due to rapid temperature variation. • Corrosive and flammable gases. (2) Emergency stop circuit • Prepare an emergency stop circuit at an external relay circuit, and connect the halt output from the JW10. (The halt output is integrated in basic module JW-1424K/1442K/1624K/1642K.) • Basic module JW-1324K/1342K does not have halt output. Provide a circuit to make output of JW-1324K/1342K normally ON, and connect this contact point into the emergency stop circuit. In this case, set system memory #206 to 00(H) (turn OFF output when the PC stops operation.) (3) Grounding • Prepare a class-3 grounding of the JW10 separately. Never co-ground with high power equipment grounding lines. (4) Installation • Securely fasten the fixing screws in each module, and confirm again that it is fastened prior to supplying power. Looseness of screws may cause malfunction. • Firmly connect cable (expansion cable), connecting to the basic and expansion modules. Confirm connectors are fastened prior to supplying power. Looseness may cause malfunction. • When JW-1424K/1442K/1624K/1642K is used as basic module, make sure to insert a termination connector on the end module. • Each Module has a ventilation hole to allow for cooling. Do not block the holes. • Install the JW10 vertically against a control panel.

;y;y;y;y ;y;y

Good; Vertical installation

No good; Horizontal installation yyy yyyy;;; ;;;;

(5) Wiring • Keep the input/output lines away from high voltage or strong current lines such as power lines. (6) Cautions for static electricity • Significant amounts of static electricity may build up on the human body in extremely dry conditions. Prior to touching the JW10, discharge the static electricity by touching grounded metals. (7) Cleaning • Use the dry and soft cloths for cleaning. Volatile solvents (alcohol, paint thinner, freon etc.) and wet rags may cause deformation of a change of color. (8) Storage • Keep the JW10 in cool and dry conditions as it is equipped with a battery for memory backup. High ambient temperature may shorten its battery life. • Do not put other objects on the JW10. 2-1

2

Page 13

(9) Overcurrent protection (fuse) • Output circuit of the JW10 basic and expansion modules does not have fuse inside. If a load connected with the output terminals is shorted, it may cause burn out of an external wiring or the module. Therefore, insert protection fuses for outputs of each common line. These protection fuses are to prevent abnormal heat or burn out of modules due to overcurrent. These fuses do not protect output elements and loads. • To secure safety, we recommend to provide fuses for each output point with enough capacity to meet each load.

2

Output side of basic or expansion module

Output side of basic or expansion module Load

Load

Fuse

〜 〜 ・・・・

・・・・

・・・・

・・・・

・・・・

〜 Fuse

〜

〜

Fuse

COM

〜

〜

COM

Load power supply

Load power supply

• When a fuse is blown out, solve the cause (short-circuit of an external wiring, use of load exceeding the rated output) and then replace the relative module.

(10) Description of relay output [output port of JW-1324K/1424K/1624K/114S/1124NS/1324NS] • A relay output is different from a transistor or other semiconductor output.Relays have a limited lifespan, determined by the number of times the relay contracts open and close. In addition, the actual life span of the relay output is greatly affected by the type of load connected, and whether or not there is a protection circuit for the relay. • Generally, inductive loads such as relays and solenoid valves generate surge voltages when the output is turned OFF.This affects the lifespan of the relay.We recommend connecting a protective circuit, as shown below.(If the inductive loads already have integrated protection circuits, additional protective circuits are not necessary.) A relay output equipped with a protective circuit will generally extend its life to two to five times longer than that of relays without a protective circuit. • For frequent open and close operations and for long continuous operation, we recommend using a transistor output instead. In case of DC power supply Inductive load

Relay output

DC power supply

Diode

In case of AC power supply Inductive load

Relay output

AC power supply

Varistor or CR surge killer

2-2