The text of a manual · part 4 of 37
Sharp Programmable Controller New Satellite JW10 User's Manual: Chapter 3 System Configuration
Pages 14 to 20 of 307, from Sharp Programmable Controller New Satellite JW10 User's Manual
The original document is the PDF (5.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Sharp jW-10CM
Page 14
Chapter 3. System Configuration 3-1
Basic system configuration
[1] System configuration Basic module JW-1324K
Expansion module JW-1342K
JW-112N
3 DC input: 16 points DC input: 16 points Relay output: 12 points Transistor output: (Unavailable expansion) 12 points (Unavailable expansion)
JW-1424K
JW-1442K
DC input: 16 points JW-114S
JW-112S
Expansion cable Transistor output: 16 points
DC input: 24 points Relay output: 16 points
DC input: 24 points Transistor output: 16 points
JW-1624K
JW-1642K
DC input: 36 points Relay output: 24 points
• Attached to the expansion/analog input/analog output module (4 cm) • JW-104EC(40 cm)
Relay output: 16 points
JW-1124NS
JW-1324NS
DC input: 8 points Relay output: 8 points
DC input: 16 points Relay output: 16 points
DC input: 36 points Transistor output: 24 points
Analog input/output module
Note 1: Up to two expansion modules can be connected. Note 2: One analog input and one analog output module can be connected. They can be operated by any basic PG connection cable module that has version 2.0 or later JW-12KC (2 m) ROM code. Note 3: Only one expansion cable JW104EC is usable per one system.
JW-14AD
JW-12DA
Analog input: 4 channels
Analog output: 2 channels
Support tools
Hand-held programmer JW-13PG [with A B mark]
Converter (Delivered with ladder software)
Communication adapter II (Delivered with ladder software)
Personal computer (IBM-PC DOS/V)
Personal computer (PC 98)
Multipurpose programmer JW-50PG [Ver.5.3 or later] Ladder software JW-50SP(English) JW-52SP(Japanese) [Ver.5.3 or later]
3-1
Ladder software JW-92SP(Japanese) [Ver.5.3 or later]
Page 15
[2] Table of module Module name
Model name
Basic module
JW-1324K
Outline Power voltage
85 to 250VAC
24 VDC input
16 points
Accessories Instruction manual
1
Instruction manual
1
Instruction manual
1
Instruction manual
1
Instruction manual
1
Instruction manual
1
Relay output 12 points Max. No. of I/O points 28 points (unavailable expansion) Program capacity 1.5K words JW-1342K
3
Power voltage 85 to 250VAC 24 VDC input (high speed response) 16 points Transistor output 12 points Max. No. of I/O points 28 points (unavailable expansion) Program capacity 1.5K words
JW-1424K
Power voltage
85 to 250VAC
24 VDC input
24 points
Relay output
16 points
Max. No. of I/O points 104 points
JW-1442K
Program capacity
4K words
Power voltage
85 to 250VAC
24 VDC input
24 points
Transistor output
16 points
Max. No. of I/O points 104 points
JW-1624K
Program capacity
4K words
Power voltage
85 to 250VAC
24 VDC input
36 points
Relay output
24 points
Max. No. of I/O points 124 points
JW-1642K
Program capacity
4K words
Power voltage
85 to 250VAC
24 VDC input
36 points
Transistor output
24 points
Max. No. of I/O points 124 points
Expansion module
Program capacity
4K words
JW-112N
24 VDC input
16 points
Expansion cable (4cm)
1
JW-112S
Transistor output
16 points
Expansion cable (4cm)
1
JW-114S
Relay output
16 points
Expansion cable (4 cm)
1
JW-1124NS
24 VDC input
8 points
Expansion cable (4 cm)
1
Relay output
8 points
24 VDC input
16 points
Expansion cable (4 cm)
1
Relay output
16 points
4 channels
Instruction manual
1
0 to 10V→Binary 12 bits
Expansion cable (4cm)
1
0 to 12mA→Binary 11 bits 2 channels
Instruction manual
1
Binary 12 bits→0 to 10V
Expansion cable (4cm)
1
JW-1324NS
Analog input
JW-14AD module Analog output module
JW-12DA
Binary 11 bits→0 to 20mA
3-2
Page 16
Module name
Model name
Outline
Expansion cable
JW-104EC
Expansion module connection cable ( 40 cm )
PG connection cable
JW-12KC
A cable (2 m) to connect between basic
Hand-held programmer
JW-13PG
Accessories module and support tool. LCD dot matrix display
(with A , B mark) Instruction words programmer (16 characters 4 lines )
Instruction manual
1
Lock spring
2
Programmer mounting bracket 1 Retention screw of programmer
Multipurpose programmer
JW-50PG
LCD graphic display ( 640 × 480 dots )
(Ver. 5.3 or later) Built in 1 set of 3.5" floppy disk drive mounting bracket (M3x6)
1
Instruction manual
5
Power supply cable
1
Built in 1 set of 2.5" hard disk drive ( 256 JW-52SP(FD)
1
MB)
Ladder software
JW-50SP
Instruction manual
1
(Ver. 5.3I or
Key label
1 later)
Converter
1
JW-52SP
Ladder software for IBM-PC
Ladder software for DOS/V personal Instruction manual
(Ver. 5.3 or later) computer, Japanese display JW-92SP
Key label
1 1
Ladder software for PC-98 series, Japa- Communication adapter II 1
(Ver. 5.3 or later) nese display
3-3
3
Page 17
[3] Example of system configuration System configuration JW-1324K/1342K
Figures in parenthesis are relay numbers (octal)
Input / output Input
Basic module 16 points
Expansion Expansion module 1 module 2
Total
―
―
16 points
―
―
12 points
―
―
24 points
―
―
16 points
―
―
36 points
―
―
24 points
16 points
―
40 points
―
―
16 points
―
―
36 points
16 points
―
40 points
―
44 points
―
32 points
―
40 points
―
32 points
8 points
60 points
(00000 to 00017)
Ouput
12 points (00400 to 00413)
JW-1424K/1442K
Input
24 points (00000 to 00027)
3
Ouput
16 points (00400 to 00417)
JW-1624K/1642K
Input
36 points (00000 to 00043)
Ouput
24 points (00400 to 00427)
JW-1424K
JW-112N
Input
24 points
(00000 to 00027) (00030 to 00047)
Output
16 points (00400 to 00417)
JW-1624K
JW-114S
Input
36 points (00000 to 00043)
Output
24 points
(00400 to 00427) (00430 to 00447)
JW-1624K
JW-1124NS
Input
36 points
8 points
(00000 to 00043) (00050 to 00057)
Output
24 points
8 points
(00400 to 00427) (00430 to 00437)
JW-1424K
JW-1324NS
Input
24 points
16 points
(00000 to 00027) (00030 to 00047)
Output
16 points
16 points
(00400 to 00417) (00420 to 00437)
JW-1624K
JW-112N JW-1124NS
Input
36 points
16 points
(00000 to 00043) (00050 to 00067) (00070 to 00077)
Output
24 points
―
(00400 to 00427)
JW-1424K
JW-1124NS JW-112S
Input
24 points
8 points
(00000 to 00027) (00030 to 00037)
Output
16 points
8 points
32 points
(00430 to 00437)
8 points
―
32 points
16 points
40 points
(00400 to 00427) (00420 to 00427) (00430 to 00447)
JW-1624K
JW-1324NS JW-1324NS
Input
36 points
16 points
16 points
68 points
(00000 to 00043) (00050 to 00067) (00070 to 00107)
Output
24 points
16 points
16 points
56 points
(00400 to 00427) (00430 to 00447) (00450 to 00467)
JW-1424K
JW-14AD JW-12DA JW-1124NS
Input
24 points
8 points
―
32 points
―
24 points
(00000 to 00027) (00030 to 00037)
Output *Note 2
16 points
8 points
(00400 to 00417) (00420 to 00427)
*Note 2
*Note 1 : For allocation of relay number, see page 10・3. *Note 2 : JW-14AD and JW-12DA do not occupy I/O relay area. 3-4
Page 18
3-2
System configuration using communication
[1] Computer link system (1) In case of using communication port
Host computer
JW10 (slave station 001(8)) JW10 (slave station 002(8)) JW10 (slave station 077(8))
RS-232C
3 RS-232C/422 converter (Z-101HE)
RS-422A Total length max. 1 km
Max. 63 stations
(2) In case of using MMI port
ホストコンピュータ Host computer
JW10 JW RS-232C
RS-232C/422 converter (Z-101HE)
RS-422A
• Possible communication between a host computer and JW10, one to one.
Max. km 最大1km
3-5
Page 19
[2] Data link system (1) In case of using the JW10 as master station
JW10 (master station 000)
JW10 (slave station 001(8)) JW10 (slave station 002(8))
JW10 (slave station 007(8))
RS-422A
3
Total length max. 1 km
Max. 7 slave stations
• Possible communication between one JW10 master station and maximum seven JW10 slave stations, one to N modules communication. (Communication between slave stations is not available.) • Transmitting and receiving data capacity per station is 8 bytes. • Total extendible length is determined by setting communication speed. Communication Total length No. of connected slave stations distance speed 76800 bits/s 500m 7 stations 7 stations 38400 bits/s 1 km
(2) In case of using the JW20H/30H as master station
JW20H/30H (master station) JW-25CM
JW10 (slave station 001(8)) JW10 (slave station 002(8)) JW10 (slave station 077(8)) UNIT NO.
L1 L2 SHIELD FG
Total length max. 1 km
Max. 63 slave stations
JW-25CM
• Possible communication between one JW20H/30H master station and JW10 slave stations, one to N modules communication. (Communication between slave stations is not available.) • Transmitting and receiving data capacity per station is 8 bytes. • Total extendible length and maximum number of connectable slave stations are determined by setting communication speed. Communication Total length No. of connected slave stations distance speed 76800 bits/s 500m 31 stations 63 stations 38400 bits/s 1 km
• See "JW-25CM instruction manual" in detail for this system.
3-6
Page 20
[3] Remote I/O system (1) In case of using the JW10 as master station
JW10 (master station 000) JW10 (slave station 001(8)) JW10 (slave station 002(8)) JW10 (slave station003 (8)) JW10 (slave station 004(8))
RS-422A Total length max. 1 km
Max. 4 slave stations
• No. of I/O points per station is max. 60 points (input 36 points, output 24 points) • Connection of an expansion module to a slave station is not available • Data exchage between a master station and slave stations synchronize with master station's operation speed. • Total extendible length is determined by setting communication speed. Communication Total length No. of connected slave stations distance speed 76800 bits/s 500m 4 stations 4 stations 38400 bits/s 1 km
(2) In case of using the JW20H/30H as master station
JW20H/30H (master station) JW-25CM
JW10 (slave station 001(8)) JW10 (slave station 002(8)) JW10 (slave station 077(8)) UNIT NO.
L1 L2 SHIELD FG
Total length max. 1 km
Max. 63 slave stations
JW-25CM
• No. of I/O points per station is max. 60 points (input 36 points, output 24 points) • Connection of an expansion module to a slave station is not available. • Data exchage between a master station and slave stations can be selected from synchronous or asynchronous with the operation. • Total extendible length and maximum number of connectable slave stations are determined by setting communication speed and selection between synchronous and asynchronous. Communication Operation synchronous/ Total length No. of connected slave stations asynchronous speed distance Synchronous/ 76800 bits/s 31 stations 500 m Asynchronous Synchronous 1 km 16 stations 38400 bits/s 63 stations Asynchronous 1 km
•See "JW-25CM instruction manual" in detail for this system.
3-7
3