Page 21

Chapter 4. Name and Function of Each Part 4-1

Basic module Six models : JW-1324K, JW-1342K, JW-1424K, JW-1442K, JW-1624K, and JW-1642K, are available as basic module of JW10.

JW-1324K

JW-1342K

JW-1424K

Terminal block cover

MMI port cover

JW-1442K

JW-1624K

JW-1642K

MMI port cover (An ROM cover is equipped inside) Terminal block cover

4

Terminal block cover

Terminal block cover

Rating plate

(Each cover opened condition)

(Each cover opened condition) ④ Power terminal for sensor ③ Input terminal ⑩ Input indication lamp ⑫ POWER lamp

④ Power terminal for sensor ⑯ROM socket

⑬ RUN lamp ⑧MMI port

② FG terminal

Rating plate Expansion connector cover

⑭ COMM. lamp

⑧ MMI port

⑮ ERR lamp

② FG terminal

⑪ Ouput indication lamp ⑦ Communication port

① Power terminal

③Input terminal ⑩ Input indication lamp ⑫ POWER lamp ⑬ RUN lamp ⑨ Expansion connector (OUT) ⑰ Termination connector ⑭ COMM. lamp ⑮ ERR lamp ⑪ Output indication lamp ⑦ Communication port ⑤ Output ⑥ Halt output terminal terminal ⑱ DIN rail lever

⑱ DIN rail lever ⑤ Output terminal ① Power terminal

① Power terminal ⑦ Communication port Supply 85 to 250 VAC power. Connect a communication cable when using com② FG terminal puter link, data link, or remote I/O. Connect class-3 grounding. ⑧ MMI port ③ Input terminal Insert a PG connection cable (JW-12KC) to conConnect a cable from an input device. nect with a support tool such as JW-13PG. Terminals 0 to 3 can be used for input of a highOr, insert a communication cable when using speed counter. computer link. ④ Power terminal for sensor ⑨ Expansion connector (OUT) [JW-1424K/1442K/ Can be used for driving power of an external sen1624K/1642K only] sor (24 VDC). Insert an expansion cable (4 cm) supplied with an (JW-1324K/1342K : 0.3A, expansion module or JW-104EC (40 cm) for conJW-1424K/1442K/1624K/1642K : 0.4A) nection with an expansion module for expansion ⑤ Output terminal of I/O. Connect a cable from an output device. In case of the expansion module is not connected, ⑥ Halt output terminal [JW-1424K/1442K/1624K/1642K only] insert termination connector ⑰ in this connector. A relay output terminal which will open when JW10 is stopped operation. 4-1

Page 22

4

⑩ Input indication lamp (amber) Lights is when the connected input devices are functioning. (JW-1324K/1342K: 16 pieces, JW-1424K/1442K: 24 pieces, JW-1624K/1642K: 32 pieces) ⑪ Output indication lamp (amber) Lights when the outputs are functioning. (JW-1324K/1342K: 12 pieces, JW-1424K/1442K: 16 pieces, JW-1624K/1642K: 24 pieces) ⑫ POWER lamp (green) Lights when a power supply inside the basic module is supplying 5 V power. ⑬ RUN lamp (green) • During normal operation: Lights ON • During programming using support tool (stopped PC operation): Blinking • Detecting an error with self diagnosis function: Goes OFF (Lights when battery error is occurred.)

4-2

⑭ COMM. lamp Lights during communication through computer link, data link, or remote I/O using the communication port. ⑮ ERR lamp (red) When an error is detected with self diagnosis function, this lamp lights and PC stops operation. (In case when battery error has occurred, the PC continues operation.) ⑯ ROM socket [JW-1424K/1442K/1624K/1642K only] Inserts a ROM (EPROM, EEPROM) for ROM operation. ⑰ Termination connector Makes sure to insert the termination connector on an expansion connector (OUT) of the end module. ⑱ DIN rail lever Moves up and down to install or detach the module on a DIN rail.

Expansion module Five models: JW-112N, JW-112S, JW-114S, JW-1124NS, and JW-1324NS, are available as expansion module of JW10. JW-112N

JW-112S

JW-114S

Terminal block cover

Terminal block cover

Expansion connector cover

Expansion connector cover

Rating plate

Rating plate Terminal block cover

Terminal block cover

Expansion connector cover

Expansion connector cover

(Each cover opened condition)

(Each cover opened condition)

② Output terminal ① Input terminal

⑦ Address marking section

⑤ Input indication lamp

③ Expansion connector (IN)

④ Expansion connector (OUT)

Expansion cable (4 cm)

⑦ Address marking section ③ Expansion connector (IN)

Expansion cable (4 cm)

⑧ DIN rail lever

⑥ Output indication lamp ④ Expansion connector (OUT)

⑧ DIN rail lever ② Output terminal

① Input terminal (Accessory)

(Accessory)

4-2

Page 23

JW-1124NS

JW-1324NS Terminal block cover

Terminal block cover

Expansion connector cover

Expansion connector cover

Rating plate Terminal block cover

Rating plate Terminal block cover Expansion connector cover

Expansion connector cover

(Each cover opened condition)

(Each cover opened condition) ① Input terminal

① Input terminal

⑦ Address marking section

③ Expansion connector (IN)

Expansion cable (4 cm)

⑦ Address

⑤ Input indication marking section lamp

③ Expansion

④ Expansion connector (IN)

connector (OUT) ⑥ Output indication lamp

⑧ DIN rail lever ② Output terminal

⑤ Input inication lamp

④ Expansion connector (OUT) ⑥ Output indication lamp ⑧ DIN rail lever ② Output terminal

Expansion cable (4 cm)

(Accessory)

(Accessory)

① Input terminal Connects a cable from an input device. ② Output terminal Connects a cable from an output device. ③ Expansion connector (IN) Inserts an expansion cable (4 cm) supplied with an expansion module or JW-104EC (40 cm) for connection with an expansion connector of basic module. When this expansion module is used as the second expansion module, insert an expansion cable for connecting with the first expansion module's expansion connector (OUT). ④ Expansion connector (OUT) Inserts the expansion cable (4 cm) supplied with an expansion module or JW-104EC (40 cm) for connection with the first expansion module (OUT) and second expansion module (IN). When only one expansion module is used, insert a termination connector which is inserted in the expansion connector (OUT) of basic module (JW1424K/1442K/1624K/1642K). 4-3

⑤ Input indication lamp (amber) Lights when the connected input devices are functioning. (JW-112N/1324NS: 16 pieces, JW-1124NS: 8 pieces) ⑥ Output indication lamp (amber) Lights when the outputs are functioning. (JW-112S/114S/1324NS: 16 pieces, JW-1124NS: 8 pieces) ⑦ Address marking section Writes the 2nd and 3rd digits of input relay and output relay using an oil based ink. Ex.: Write "43" for top address "00430." ⑧ DIN rail lever Moves up and down to install or detach the module on a DIN rail.

4