Page 24

Chapter 5. Installation 5-1

Setup environment Avoid keeping the JW10 in the following conditions: ① Ambient temperature exceeds the range of 0 to 55˚C. ② The relative humidity exceeds the range of 5 to 90%. ③ Much dusts, salty and iron powders conditions. ④ Direct sunlight ⑤ Strong vibration and shock may be received. ⑥ Location where corrosive, combustible, or flammable gases are generated. ⑦ Location where organic solvent such as benzene, thinner, or alcohol, or strong base such as ammonia, or caustic soda may be adhered, and these atmospheric conditions. ⑧ Location which is not well ventilated, and does not provide enough space from surrounding objects or heating devices.

5-2

5

Installation of basic module/expansion module Install the module as far away as possible from high-voltage wires, high-voltage devices, power lines, power devices, radio equipment with transmitters, and other devices that generate large power surges.

;y;y ;;;; yyy ;;; yyyy ;y;y;y;y

Good : Vertical installation

No good : Horizontal installation

[1] Direct installation

When the module is installed directly to a panel surface, use M4 screws with a length of 15 mm or more to secure the module. JW-1324K, JW-1342K, JW-1324NS Wiring duct

90 80

20 min.

Two M4 threaded holes or two 4.5 mm dia. holes 8

JW-1324K JW-1342K JW-1324NS

20 min. Wiring duct 100 110 [Unit: mm]

5-1

M4×15 screw

Page 25

JW-1124NS, JW-112N, JW-112S, JW-114S, JW-14AD, JW-12DA

JW-1424K, JW-1442K JW-1624K, JW-1642K Wiring duct

Wiring duct

20 min.

20 min.

JW-1424K JW-1442K JW-1624K JW-1642K

90 80

90 80

Four M4 threaded holes or four 4.5 mm dia. holes

20 min.

JW-1124NS JW-112N JW-112S JW-114S JW-14AD JW-12DA

20 min. Wiring duct 170 180

Wiring duct 54 64 [Unit: mm]

5

Two M4 threaded holes or two 4.5 mm dia. holes

[Unit: mm]

Installation dimensions between modules [using the cable (4 cm) supplied with the expansion module] 10 to 30

[Unit: mm]

JW-1324K or the like

JW-1124NS or the like

;y;y ;y;y 20 to 40

[2] Installation using DIN rail

Use a DIN rail having rail width 35 mm and fix using the end plates.

Installation

Removal

②

Lever raised condition

DIN rail lever

Lever lowered condition

Slot screwdriver ①

Lower the DIN rail and lever's groove using a slot screwdriver, and then hold up entire module to remove.

Fix the grooved section of module at the rear side on the DIN rail, and press down in the direction of the arrow. After the installation, push the lever of the DIN rail upward.

Make sure to use the end plate to fix the module. Fixing

End plate

End plate

DIN rail

5-2

Page 26

5-3

Installation of expansion cable and termination connector • Basic module JW-1424K, JW-1442K, JW-1624K, and JW-1642K can be connected two expansion modules at maximum, one analog input module JW-14AD, and analog output module JW-12DA. • Use the cable (4 cm) supplied with the expansion/analog input/analog output module or JW-104EC (40 cm) for connection to the expansion cable. • JW-104EC can be used only one for one system. (Ex. 2) • Install a termination connector on the end module's expansion connector (OUT).

Basic module Termination connector

(Ex.1)

Note: Connect the termination connector even an expansion module is not connected (this is not required for model JW-1324K/1342K).

Expansion module 1

Basic module

5

Expansion module 2 Termination connector

(Ex. 2) Expansion cable (JW-104EC: 4 cm)

Basic module

Expansion module 1

Expansion cable (Accessory : 4cm) Expansion Analog input Analog output module module module 2 Termination connector

(Ex. 3)

Note: Do not run the expansion cable inside a wiring duct.

■ Installation procedure of the expansion cable ① Open the expansion connector cover. ② Remove the termination connector which is inserted in the expansion connector (OUT) of the basic module (JW-1424K/ 1442K/1624K/1642K). ③ Insert the expansion cable in the expansion connector (OUT). ④ Insert the expansion cable in the expansion connector (IN) of the expansion module. ⑤ Insert the termination connector, which was removed in item ② above, in the expansion connector (OUT) of the end expansion module. ⑥ Close the expansion connector cover.

Expansion connector (OUT)

Termination connector

Expansion cable Expansion connector cover String

Note 1: To remove the expansion cable or termination connector, pull the strings of each connector. Note 2: Do not connect between IN sides of the expansion connectors, or between OUT sides of the expansion connectors.

5-3