Page 258

Chapter.15 Analog input/output module 15-1 Outline [1] JW-14AD ・The analog input module JW-14AD converts an external analog input signal (voltage/current) to 11-bit/12-bit binary data. ・4 channels can be input.

[2] JW-12DA ・The analog output module JW-12DA converts a 11-bit/12-bit binary data to an external analog output signal (voltage/current). ・2 channels can be output.

Notes ★When you use JW-14AD/JW-12DA, please use the JW10 basic module(JW-1424K/1442K/1624K/ 1642K) of which version is 2.0 or more.

★A JW-14AD and a JW-12DA can be connected to above mentioned basic module respectively. ★External power supply (24VDC) is required. ★Set system memory for analog modules. (JW-14AD at #210,#211, JW-12DA at #212) ★The analog modules occupy special I/O register (JW-14AD at コ0200 to コ0207, JW-12DA at コ0240 to コ0243), but input/output relays are not occupied.

★The offset and gain adjustment of analog modules (JW-14AD/JW-12DA) are adjusted at shipping and no need to adjust at customer’s side. When overall adjustment considered wiring resistance is required, adjust them at external circuit.

■ System configuration Basic module

JW-1424K, JW-1442K JW-1624K, JW-1642K

Expansion module (max. 2 sets)

JW-112N, JW-112S, JW-114S JW-1124NS, JW-1324NS

Analog input module

Analog output module

JW-14AD

JW-12DA

Install the termination connector at the terminated module. One expansion cable JW-104EC(40cm) can be used at one system. For others, use the cable (4cm) attached each expansion/analog input/analog output modules.

15-1

15

Page 259

15-2 Name and function of each part [1] Analog input module (JW-14AD) (Each over opened condition) Terminal block cover

① Terminal block ② Expansion connector (IN) ④POWER lamp ③ Expansion connector (OUT) 24V V1 C1 V2 C2 0V I1 SHLD I2 SHLD POWER

Expansion cable(4cm) JW-14AD ・

V3 C3 V4 C4 ・ I3 SHLD I4 SHLD

(Accessories) Expansion connector Rating plate Terminal block cover cover

① Terminal block

DIN rail lever

① Terminal block

: Connects analog input signal line and power line.

②=Expansion connector (IN)

: Connect with expansion connector (OUT) at previous module(Basic /expansion /analog output module) by using expansion cable (use accessory or JW-104EC).

③=Expansion connector(OUT) : Connect with expansion connector (IN) at next module (Expansion/analog output module) by using expansion cable (use accessory or JW-104EC).Install the terminating connector when the analog input modules is the terminated module. ④ POWER lamp

: Green LED is turned on when internal 5VDC is supplied normally.

[2] Analog output module (JW-12DA) (Each cover opened condition) Terminal block cover

① Terminal block ② Expansion connector (IN) ④ POWER lamp ③ Expansion connector (OUT) 24V V1 C1 V2 C2 0V I1 SHLD I2 SHLD POWER

15 Expansion cable(4cm) JW-12DA

(Accessories) Expansion connector cover

Rating plate DIN rail lever

① Terminal block ②=Expansion connector (IN)

: Connects analog output signal line and power line. : Connect with expansion connector (OUT) at previous module(basic /expansion /analog input module) by using expansion cable (use accessory or JW-104EC). ③=Expansion connector(OUT) : Connect with expansion connector (IN) at next module (expansion/analog input module) by using expansion cable (use accessory or JW- 104EC).Install the terminating connector when the analog input modules is the terminated module. ④=POWER lamp

: Green LED is turned on when internal 5VDC is supplied normally. 15-2

Page 260

15-3 Wiring ( 1 ) Separate signal lines and power line of the module from high voltage lines and power lines as far as possible. Do not run signal lines and power lines in parallel with high voltage or power lines. ( 2 ) M3 terminal screws are applied for either of terminal screws.Use crimp-style terminals equiva lent to JIS standard 1.25-3, and securely fix with tightening torque 4 to 8 kgf-cm. 【Recommended crimp-style terminals 】 JAPAN SOLDERLESS TERMINAL MFG. CO., LTD Model name :1.25-B3A 1.25-C3A 1.25-3

3mm(MIN)

1.25-MS3

3mm(MIN) 6mm(MAX)

6mm(MAX)

( 3 ) Use the shieled twisted pair when wiring to the each terminal. Use the cable given below or its equivalent for the shielded twisted pair cable. HITACHI cable : CO-SPEV-SB (A) 0.5mm2

[1]

JW-14AD Terminal CH1 CH2 CH3 CH4

Upper terminal

24V V1 C1 V2 C2 SHLD 0V I1 SHLD I2

Lower terminal

・ ・

V3 C3 V4 C4 SHLD I3 SHLD I4

Contents Voltage input terminal Input voltage signal to terminal V and C for each channels (CH1 to 4) respectively.

V1

V2

V3

V4

C1

C2

C3

C4 Common terminal

I1

I2

I3

I4

SHLD SHLD SHLD SHLD

Electric current terminal Input current signal to terminal I and C for each channels (CH1 to 4) and connect between terminal V and I respectively. Shield terminal (SHLD of each channel are connected each other at internal circuit) Connects to flame ground (FG).

24V 0V

24 VDC power supply input terminal (+) 24 VDC power supply input terminal (−)

External device Shielded twisted pair cable

7.5K

Voltage V1 input

+15V

I1

250

15K

-

15K

C1

VDD1

+15V CH1

+ -15V

SHLD

CH2 CH3

7.5K External device Shielded twisted Current pair cable input

V4

+15V 250

I4 C4

15K 15K

SHLD

OUT

ADC IN

+15V -

CH4

+ -15V

Constant-voltage Shielded twisted supply pair cable

24V 0V

24V 0V

+15V Three -15V terminal VDD1 regurator VDD2

Filter

Notes ・Keep the wire from the shield as short as possible (30mm or less). ・Connect shield line to SHLD terminal and flame ground (FG) using twisted wire of apx. 1.25mm2 via SHLD terminal. ・Use this module dedicated constant-voltage supply or 24VDC power supply of basic module for the 24VDC input power supply. ・Short the I terminal and V terminal for current input. 15-3

15

Page 261

[2] JW-12DA Terminal CH1 CH2

Upper 24V V1 C1 V2 C2 terminal 0V I1 SHLD I2 SHLD

V1

V2

Voltage output terminal Output voltage signal to terminal V and C for each channels (CH1 to 4) respectively.

C1

C2

Common terminal (C1 and C2 are connected each other at internal circuit)

I1

I2

Electric current terminal Output current signal to terminal I and C for each channels (CH1 to 4) respectively.

SHLD Shield terminal (SHLD of SH1 and SH2 are connected each other at internal circuit)

SHLD

Connects to flame ground (FG).

24V 0V

External device Shielded twisted pair cable

Voltage output

62.5

SHLD V2 output

24 VDC power supply input terminal (−)

VDD1 30K

V1

I1 pair cable

24 VDC power supply input terminal (+)

+15V

C1

External device Shielded twisted Current

Contents

62.5

I2 C2

360

-15V +15V 30K

+15V

-15V

-15V

DAC 1 VDD1

+15V

30K

360

-15V +15V 30K

+15V

-15V

-15V

DAC 2

SHLD Constant-voltage Shielded twisted supply pair cable

24V 0V

24V 0V

+15V Three -15V terminal VDD1 regurator VDD2

Filter

Notes ・Keep the wire from the shield as short as possible (30mm or less). ・Connect shield line to SHLD terminal and flame ground (FG) using twisted wire of apx. 1.25mm2 via SHLD terminal.

15

・Use this module dedicated constant-voltage supply or 24VDC power supply of basic module for the JW-12DA 24VDC input power supply. 1kohm 1/4W External device terminal block ・If the input impedance of the external device is high, the V effect of AC induction becomes larger for voltage inputs. C In this case, connect a load resistor of about 1k ohm SHLD across the input terminals of the external device. JW-12DA terminal block

External device

・The maximum load resistance of the current output is 500 ohm. If the sum of the input resistance of the external device and the line resistance exceeds 500 ohm, the linear accuracy of the output current deteriorates.

Input resistance Rx

Line resistancer

I C

Line resistancer

SHLD JW-12DA

External device

・If the 0V terminals of external devices are connected, a circuit will form through the outputs for CH1 and CH2. If the external devices are affected as a result, either provide a commercially available isolating amplifier for one channel. 15-4

External device

Isolating amplifier

Page 262

15-4 How to use JW-14AD [1] Operation mode Select one of the below three modes by setting system memory #210.

#210(HEX) Analog input Operation Set value Initial value Voltage input Current input mode

Digital value

01

Mode 1

0 to10VDC

−

0 to 4000 (12 bits binary)

02

Mode 2

0 to 5VDC

0 to 20mADC

0 to 2000 (11 bits binary )

03

0 to 2000 (11 bits binary) 1 to 5VDC 4 to 20mADC JW-14AD does not work. (can not convert analog to digital) Mode 3

○

00

Note : JW-14AD has 4 channels, but above setting is applied 4 channels all.

[2] Allocation of data memory The converted digital data from analog data are stored at special register for JW-14AD.

Special register for JW-14AD

Channel

Byte address

CH1 CH2 CH3 CH4

D7 D6 D5 D4 D3 D2 D1 D0

コ0200

27

26

25

24

23

22

21

20

コ0201

0

0

0

0

211 210

29

28

コ0202

27

26

25

24

23

22

21

20

コ0203

0

0

0

0

211 210

29

28

コ0204

27

26

25

24

23

22

21

20

コ0205

0

0

0

0

211 210

29

28

コ0206

27

26

25

24

23

22

21

20

コ0207

0

0

0

0

211 210

29

28

The stored data is binary value, but you can handle them as decimal data by adding each bit’s weight as blow shown. (0 to 4095) 210 29 28 211 2048

1024

512

256

27

26

25

24

23

22

21

20

128

64

32

16

8

4

2

1

15 JW-14AD does not occupy I/O relay area (00000 to 00777). (Example)

JW-1424K

JW-14AD JW-1124NS

Allocation of input/output relay number Input relay

Output relay

JW-1424K 00000 to 00027 00400 to 00417 JW-14AD Input:24 points Output:16 points

Input:8 points Output:8 points

15-5

−

−

JW-1124NS 00030 to 00037 00420 to 00427

Page 263

[3] Averaging function When input value change rapidly, averaging function average input values and outputs an average value in specific period. It average prior five analog input data and get an average value following below procedure. Average data = Delete maximum and minimum value in prior five data and average remained three data. Data refresh

N−4

N−2

N−3

N−1

N

1 scan time

(Example) N-4th. data = 161 N-3rd. data = 120, - - Minimum value N-2nd. data = 154 N-1st. data = 160 N th. data = 190- - - - Maximum value In case of above data Average value at Nth. = (161+154+160)/3=158 (rounds to integral number)

The first four scanned data after operation start are output without averaging. Set system memory #211 for averaging function as below

#211(HEX) Set value Initial value 00

○

01

Contents Averaging disable Averaging enable

Note : JW-14AD has four channels, but above setting applies all channels.

15 [4] Module status in error PC status External 24VDC power supply is disconnected PC stop #210=00 Except for #210=00、01、02、03

RUN STOP RUN STOP *Note

Digital value (at コ0200 to コ0207) Maximum value(4095 at mode1, 2047 at mode 2 or 3) Holds prior data before PC stop HOLD:JW-14AD does not execute (not convert analog to digital)

*Note : Store error code 23(H) at system memory #160 to #167 and PC stop. (23(H) : System memory setting error)

15-6

Page 264

15-5 How to use JW-12DA [1] Operation mode Select one of the below three modes by setting system memory #212.

#212(HEX) Operation Set value Initial value mode

Analog output Voltage output Current output

Digital value

01

Mode 1

0 to 4000 (12 bits binary)

0 to10VDC

02

Mode 2

0 to 2000 (11 bits binary)

0 to 5VDC 0 to 20mADC

03

Mode 3

0 to 2000 (11 bits binary)

1 to 5VDC 4 to 20mADC

00

○

−

JW-12DA does not work. (can not convert digital to analog)

Note : JW-12DA has 2 channels, but above setting is applied 2 channels all.

[2] Allocation of data memory The converted analog data from digital data are stored at special register for JW-12DA.

Special register for JW-12DA

Channel

Byte address

CH1 CH2

D7 D6 D5 D4 D3 D2 D1 D0

コ0240

27

26

25

24

23

22

21

20

コ0241

0

0

0

0

211 210

29

28

コ0242

27

26

25

24

23

22

21

20

コ0243

0

0

0

0

211 210

29

28

The stored data is binary value, but you can handle them as decimal data by adding each bit’s weight as blow shown.(0 to 4095) 211 210 29 28 27

26

25

24

23

22

21

20

2048 1024

64

32

16

8

4

2

1

512

256

128

JW-14AD does not occupy I/O relay area (00000 to 00777). (Example)

JW-1424K

Allocation of input/output relay number

JW-12DA JW-1124NS

Input relay JW-1424K JW-12DA

Input:24 points Output:16 points

Input:8 points Output:8 points

Output relay

00000 to 00027 00400 to 00417 −

−

JW-1124NS 00030 to 00037 00420 to 00427

[3] Module status in error External 24VDC power supply is disconnected PC stop #212=00 Except for #212=00、01、02、03

PC status RUN STOP RUN STOP *Note 2

Analog output value(between terminal V and C or I and C) 0V or 0mA Holds prior output value before PC stop *Note 1 HOLD:JW-12DA does not execute (not convert digital to analog)

*Note 1 : Holds output value when system memory #206=0 (reset output when PC stop). *Note 2 : Store error code 23(H) at system memory #160 to #167 and PC stop. (23(H) : System memory setting error) 15-7

15

Page 265

15-6 Specifications [1] JW-14AD Performance specifications Specifications

Item

Volatge input

Current input

No. of input channel

4 channels

Analog input range

0 to 10VDC

0 to 20mADC

Absolute maximum input signal

−1V, +15V

0mA, +25mA

Input impedance

30k ohm

250 ohm

Digital output

0 to 4000(12 bits binary value)

0 to 2000(11 bits binary value)

Resolution

2.5mV (10V/4000)

10μA (20mA/2000)

Overall accuracy

±0.5% or less (full scale at 25℃) ±1% or less (full scale at 0 to 55℃)

A/D conversion time

1 scan time/ 4 channels [Mode 1] 4095 4000

2000

0 I/O characteristics

15

5V

10V

[Mode 2]

[Mode 2]

2047 2000

2047 2000

0

5V

0

[Mode 3]

[Mode 3]

2047 2000

2047 2000

0 1V

5V

0 4mA

20mA

20mA

Opearaion display

POWER lamp(Green LED is turned on when internal 5VDC is supplied normally.)

External power supply

24VDC±10%(includes ripple) Spike noise 50mVP-P or less (max.100mA)

Insulation system

Photocoupler isolation (Each channels are not isolated.)

Insulation resistance

500VDC for 10M ohm or more (between input terminal and secondary circuit)

Dielectrical strength

500VAC for one minute (between input terminal and secondary circuit)

15-8

Page 266

[2] JW-12DA Performance specifications Specifications

Item

Voltage output

Current output

No.of output channels

2 channels

Analog output range

0 to 10VDC

0 to 20mADC

External load resistance

500 ohm or more

500 ohm or less

Digital input

0 to 4000 (12 bits binary value)

0 to 2000 (11 bits binary value)

Resolution

2.5mV (10V/4000)

10μA (20mA/2000)

Overall accuracy

±0.5% or less (full scale at 25℃) ±1% or less (full scale at 0 to 55℃)

D/A conversion time

1 scan time/ 2 channels [Mode 1]

10V

5V

I/O characteristics

0

2000

[Mode 2]

4000 4095 [Mode 2]

5V

20mA

0

2000 2047

[Mode 3]

0

2000 2047

15

[Mode 3]

5V

20mA 4mA

1V 0

2000 2047

0

2000 2047

Operation display

POWER lamp(Green LED is turned on when internal 5VDC is supplied normally.)

External power supply

24VDC±10%(includes ripple) Spike noise 50mVP-P or less (max.200mA)

Insulation system

Photocoupler isolation (Each channels are not isolated.)

Insulation resistance

500VDC for 10M ohm or more (between output terminal and secondary circuit)

Dielectrical strength

500VAC for one minute (between output terminal and secondary circuit)

15-9

Page 267

[3] General specifications Specifications

Item

JW-14AD

JW-12DA

Storage temperature

-25 to 70℃

Ambient temperature

0 to 55℃

Ambient humidity

5 to 90%RH(non-condensing)

Vibration resistance

JIS C 0911 or equivalent , Amplitude 0.15mm(10 to 58Hz), 1G(58 to 150Hz) (2 hours in each of X,Y and Z axis) JIS C 0912 or equivalent

Shock resistance

15G (3 times in each X, Y and Z axis)

Connect to a terminal block(M3×7mm self lockup screw)

External wire grounding system

Applied with crimp-style terminal : JIS 1.25-3 or equivalent

Installation

Direct installation or using DIN rail (35mm width)

Outline dimension

64mm(W)×90mm(H)×76mm(D)

Weight Grounding

Approx. 180g

Approx. 195g

Accessories

Instruction manual × 1

Class-3 grounding Expansion cable(4cm) × 1

[4] Outline dimension drawings (JW-14AD and JW-12DA in common) [Unit : mm] (Mounting dimensions to panel) Gap between modules :

90

80 90

10 to 30 (when attached cable is used)

15 64

76

54 64

2-M4 tap or 2-φ4.5

15-10