Page 268
Chapter 16. Trial Run 16-1 Check points prior to trial run When installing and wiring are completed, check the following points, prior to supplying power to the JW10.
1
Check installation condition
▼
2
3
4
5
6
Check power lines, input/output lines, and communication lines
▼ Check expansion cables and termination connectors
▼ Check the connection of the grounding line.
• Is the JW10 installed on vertical surface of a control panel? • Whether each module is fixed securely? • Whether the wiring is correct? • Whether the screws in the terminal block are not loose? • Whether the cable size is correct? • Are the power lines twisted? • Do not input/output lines run parallel or close to high voltage or high current lines? • Are output lines equipped with protection fuses? • Are shielded twisted pair cables used for communication lines? • Is number of expansion cables (number of expansion modules) used appropriate? • Is more than two JW-104EC (40 cm cable) not used? • Is a termination connector installed on the end expansion module? • Are cables and connectors securely installed?
• Whether class-3 grounding is correctly grounded? • Whether the grounding is not co-grounded with a high voltage board?
▼ Check the voltage of the power supply source.
• Whether source voltage is within rated voltage (85 to 250 VAC) ?
▼ Check the operation condition of the halt output circuit.
• Whether halt output signal is connected properly with sequence in outside PC?
▼ End
16・1
16
Page 269
16-2 Operation method for trial run Operate the JW10 according to the following process after precautions for operation is checked.
1
Connect support tool.
• Connect a hand-held programmer JW-13PG or the like.
▼
2
Supply power
• Check whether the "POWER" lamp is "ON."
▼
3
All initialize
• Clear system memory, program memory, and data memory by all initialize functions.
▼
4
Set system memory
▼
5
Check the wiring to I/O port
▼
6
Programming
• See the "7-3 System memory."
• Check the input port wiring using the display of the input indication lamp or the monitoring function of the support tool. • Check the output port wiring by forcing the switch set/reset of the output relay in the support tool. • Write program using a hand-held programmer JW13PG or the like. • If a program is stored in a multipurpose programmer JW-50PG or the like, transfer this program onto the JW10.
▼
16
7
Run trial operation
• Confirm whether the "RUN" lamp is "ON." • Check PC motion.
▼
8
Revise the program
▼
9
Save the program
▼ End
• Revise the program, if it is not correct.
• Write the program in a floppy disk or a ROM. Make sure to indicates model name of PC, program capacity, facility name, and date on recorded program. • Print out the program using a printer.
16・2
Page 270
Chapter 17. Maintenance and Check 17-1 Periodical check The following table is the recommended periodical check of used items, so as to keep the JW10 operating normally and in the best condition: ■ General items Check items
Check contents
Standard
Ambient temperature
0 to 55˚C
Ambient humidity Within the specifications Temperature in the control box becomes Atmosphere the ambient temperature when the JW10 is installed in a control box. Vibration
5 to 90% RH
Shock
(
)
Remarks No condensation
No corrosive gas, etc. No No
■ Basic module Check items Power voltage
Check contents
Standard
Remarks
Measure input voltage at the terminal block and check that it is within the specifications.
85 to 250 VAC
Power voltage 24 Measure output voltage on power terminals for senVDC for sensors Input port power sors, and check whether it is within the standard.
24 VDC ±10%
Voltage supplied at cable to input port is with 10 to 26.4 VDC
Terminal 0 to 3 the specifications.
Terminal 4 to
20 to 26.4 VDC
JW-1324K 250 VAC max. Output port power
JW-1424K
Voltage supplied at cable to output port is with 30 VDC max.
JW-1624K the specifications.
JW-1342K 4.5 to 27VDC
JW-1442K JW-1642K
Error lamp of basic module
Visually check error lamp (ERR)
Light OFF
The basic module is fixed firmly.
No looseness
Terminal block screws have not been loosened. No looseness Installed condition Are expansion cables and a termination con- S h o u l d b e s e - JW-1324K/1342K nector securely installed on expansion connec- curely installed are unnecessary tor?
17-1
17
Page 271
■ Expansion module Check items
Standard
Remarks
Voltage supplied at cable to input port is with 20 to 26.4 VDC Input port power the specifications.
30 VDC max.
JW-112N JW-1124NS JW-1324NS JW-114S JW-1124NS JW-1324NS
4.5 to 27VDC
JW-112S
Output port power
Check contents
Voltage supplied at cable to output port is with the specifications.
The expansion module is fixed firmly.
250 VAC max.
No looseness
No looseness Installed condi- Terminal block screws have not been loosened. Are expansion cables and a termination con- Should be setion nector securely installed on expansion connec- curely installed tor? ■ Analog input module/ analog output module Check items 24 VDC power voltage
Check contents Measure output voltage on 24 VDC power terminal, and check whether it is within the stan-
Standard
Remarks
24 VDC ±10% dard. The analog input module, analog output module are fixed firmly. Installed condi- Terminal block screws have not been loosened. tion Are expansion cables and a termination connector securely installed on expansion connec-
No looseness No looseness Should be securely installed tor?
■ Others Verify that the program stored in a ROM (EPROM or EEPROM) or a floppy diskette (FD) is the same as the currently operating program.
17
17-2
Page 272
17-2 Troubleshooting In the event of abnormality, check the lamp (RUN, ERR) of the basic module, and remedy according to the check flow depending on the state.
[1] State of LED RUN
ERR
Remarks
OFF ○
ON ●
Detectable error for self-diagnosis
→
Check flow 1
OFF ○
OFF ○
Power supply OFF
→
Check flow 2
Blink ◎
OFF ○
Halt mode
→
Check flow 3
Disable detection error by self-diagnosis (input relation) →
Check flow 4
ON ●
OFF ○
Disable detection error by self-diagnosis (output relation) →
Check flow 5
ON ●
ON ●
→
Check flow 1
Others
[2] Precondition of check flow This check flow describes the countermeasure method (replacement of defective module and subsequent restoring method) in the event the system running normally so far suddenly breaks down. Therefore, the following cases are excluded. ① Momentary failure due to transient abnormality due to noise or other effect (irreproducible trouble). ② Trouble due to effect of ladder program (customer's application).
[3] Prepare for causing trouble 1. Back-up for program memory and system memory When the CPU board is abnormal, the current program memory and the like may not be saved by the support tool, or the saved data may be incorrect. Therefore, store the latest program memory and back-up of system memory always in the floppy disk (FD). In the case of ROM operation, store the back-up in the FD with spare ROM, too. 2. Prepare for support tool Prepare the support tool that can load/save of hand-held programmer or program. 3. Prepare for spare parts Prepare always a spare of each module to be ready for abnormality. 4. Prepare for setting system memory table, I/O relay allocation table For prompt trouble shooting, prepare the "system memory setting table" and "I/O relay allocation table."
17-3
17
Page 273
[4] Check flow Check flow 1
Monitor system memory #160 using a hand-held programmer JW-13PG <Operation procedure of JW-13PG> 6
Value of #160 20 22 27 31 26 21
24
17 25
23
44
Contents
Treatment
System ROM error Reinput the power and if this error occurs, replace the basic module. Battery error Reinput the power and if this error occurs, initialize all memory. Then load the RAM error program and system memory again. If the error is still not cleared, replace the Watchdog timer error basic module. Reinput the power and if this error occurs, initialize all memory. Then load the User ROM error program and system memory again, and rewrite onto a ROM. If the error is still not cleared, replace the basic module. User program error Reinput the power and if this error occurs, check user program address having 1 the error with #052 and #053. Then, rewrite the program. If the error is not still (instruction code cleared, initialize all memory and load the program and system memory again. If the situation is still not changed, replace the basic module. check) Note 1: If JW10 has grammatical error on the program (doubled use of OUT instruction or the like), be careful as "user program error 1" occurs and it cannot operate. After inputting the program, check the program using a hand-held programmer, and check grammatical error of the program. User program error 《Operation of JW-13PG》 2 (Program mode) (parity check) If 55(H) is stored in register #055 in the system memory, the JW10 will continue operation without halting in a "user program error 1" status when it detects grammatical error.(The option is available in version 1.4 or later ROM code.) Note 2: Some support tools can be used with the JW10 by partly limiting functions of the JW10 (see page 14・2 for details). If any of these support tools is used with the JW10, instructions and data memory which are not available with the JW10 may be input to the JW10. Be careful that if these instructions or data memory are input, "user program error 1" occurs at start operation and the JW10 cannot start operation. User program error Reinput the power and if this error occurs, check that there is no endless program or a program having long operation time (more than 200 ms). If the error 3 (endless program cannot be cleared, initialize all memory and load the program and system memory again. If the problem is not solved, replace the basic module. check) System memory er- Reinput the power and if this error occurs, check system memory address, having the error with #054. Then, revise the value of the system memory. If the error ror cannot be cleared, initialize all memory and load the program and system memory again. If the problem is still not solved, replace the basic module. Note 1: Be careful that if value exceeding the specified range is set on a system memory, "system memory error" occurs at startup of the JW10 and the JW10 cannot be operated. Reinput the power and if this error occurs, check installation condition of termiI/O bus error nation connector and expansion cable. If the error cannot be cleared, replace the termination connector or expansion cable. If the problem still exists, replace the basic module, and then if not solved, replace the expansion module, too. 17-4
Page 274
Value of Contents #160(H)
Treatment
C o m m u n i - • In case of #234 = 02 (remote I/O) Reinput the power and if this error occurs, check wiring condition of the communication cation error cable which is lead to a slave station having turned OFF its communication flag. If the error cannot be cleared, replace the slave station with the communication flag OFF. If the problem still exists, replace the basic module. • In case of #234 ≠ 02 Reinput the power and if this error occurs, initialize all memory, and load the program and system memory, again. If the error cannot be cleared, replace the basic module. Reinput the power and if this error occurs, initialize all memory. Then load the program Other code and system memory again. If the error is still not cleared, replace the basic module. Note 1: Power error (error code 13) is always written at inputting the power. This is not abnormal. If the JW10 cannot Reinput the power and if this error occurs, replace the basic module. communicate with a hand-held programmer ("PC KIND?" is displayed) 53
Check flow 2
Confirm POWER lamp ▼ Y
▼
Is POWER lamp ON?
Replace basic module
N ▼ Check power voltage of power terminal on the basic module ▼ Y
▼
85 to 250 VAC
Replace basic module
17
N ▼ Check external wiring or external power supply, etc.
Check flow 3 Enter operation mode (monitor or change mode) using a hand-held programmer ▼ Y
▼
Does the JW10 enter operation mode? ▼N To check flow 1
17-5
Recovery
Page 275
Check flow 4 This flow shows the checking procedure in the event of abnormality of input signal not detected by the self-diagnosis of the CPU. Example of the error • All inputs of specific basic/expansion module fail to be turned ON. • Specific input fails to be turned ON (OFF). • Among input signals of a same basic/expansion module, operation of a certain input signal affects other input signal.
Countermeasure
Error input signal
① Measure the voltage between the corresponding input terminal of the basic/expansion module and the common terminal using a tester. • If supply voltage is applied between terminals: ON • If supply voltage is not applied between terminals: OFF ② Check the state of input indication lamp of basic/expansion module. ③ Connect hand-held programmer, and check ON/OFF by monitoring the data memory (input relay) corresponding to the abnormal input.
▼ In case of ① = ② = ③
▼ In case of the others
▼ Check the external wiring and power supply.
▼ Exchange the basic/expansion module
OK ▼ Exchange the basic/expansion module [The flow of input signal]
17 Input indication lamp
② Data memory
CPU+I/O I/F circuit
③
Common terminal Power supply
① Input terminal Hand-held programmer
③
17-6
Page 276
Check flow 5 This flow shows the checking procedure in the event of abnormality of output signal not detected by the self-diagnosis of the CPU. Example of the error • All outputs of specific basic/expansion module fail to be turned ON. (In this case, it is highly possible that the fuse of load power output is melted down.) • Specific output fails to be turned ON (OFF). • Among output signals of a same basic/expansion module, operation of a certain output signal affects other output signal. Countermeasure
Error output signal
① Connect hand-held programmer, and check ON/OFF by monitoring the data memory (output relay) corresponding to the abnormal output. ② Check the state of output indication lamp of basic/expansion module. ③ Measure the voltage between the corresponding output terminal of the basic/expansion module and the common terminal using a tester. When the inter-terminal voltage is output ON voltage (about 1 V or less): ON When the inter-terminal voltage is load supply voltage: OFF Note 1: When the load power source is OFF and wiring to the load is disconnected, it is abnormal if the output is normal.
▼ In case of ① = ② = ③
▼ In case of ① = ② ≠ ③
▼ In case of the others
▼ Connecting load is error
▼ Check the external wiring and power supply.
▼
▼
OK
[The flow of output signal] Output indication lamp
②
Data memory
CPU+I/O I/F circuit
17 Output terminal
①
Load Power supply
③ 〜
Common terminal Hand-held programmer
①
17-7