Page 277
Chapter 18. Specifications 18-1 General specifications Items
Specifications JW-1324K JW-1342K
Power voltage Guaranteed voltage interruption time
JW-1424K JW-1442K
JW-1624K JW-1642K
85 to 250 VAC, 47 to 63Hz Available voltage interruption time of 20 ms max. (In case a support tool is not connected)
Insulation resistance 10 Mohm min. at 500 VDC megger (between AC input terminal and FG terminal) Dielectric strength
1500 VAC, 50/60Hz for 1 minute (between AC input terminal and FG terminal)
Noise immunity
1000Vp-p 1 µs width impulse (by noise simulator between the power line and FG terminal)
Storage temperature
−25 to 70 ˚C
Ambient temperature
0 to 55 ˚C
Ambient humidity
5 to 90 % RH (non-condensing)
Atmosphere
Free from corrosive gas
Vibration resistance
JIS C 0911 or equivalent amplitude 0.15 mm (10 to 58 Hz), 1G (58 to 150 Hz) (2 hours in each of X, Y and Z axis)
Shock resistance
JIS C 0912 or equivalent 15G (3 times in each X, Y and Z axis)
Power consumption
30 VA
Power capacity for sensor
300 mA (24 VDC ±10%)
60 VA 400 mA (24 VDC±10%)
Connect to a terminal block (M3 × 7 mm self lockup). Applied with crimp-style terminal: JIS 1.25-3 or equivalent. Direct installation or using DIN rail (35 mm width)
External wire grounding system Installation Weight
55 VA
460g
580g
700g 860g Class-3 grounding
Grounding
750g
890g
18
18-1
Page 278
18-2 Performance specifications Items Program system Control system Processing speed
Specifications JW-1424K JW-1442K JW-1624K JW-1642K Stored program system Compatible cyclic calculation and interrupt dealing system
JW-1324K JW-1342K
Basic instruction: 1.63 to 1.83µs (except OUT, TMR, CNT)
Basic instruction: 0.81 to 1.02µs (except OUT, TMR, CNT)
Basic instruction: 11 Application instruction: 71 4 k words (RAM) EPROM (27C512) or EEPROM (28C256) No available ROM operation [ROM will be supplied by user.] Memory back-up By build-in lithium battery. (Battery life: 10 years) I/O control system Both block refresh system and refresh system by instruction are applied. 16 points 24 points 36 points Input Basic numbers DC input DC input (high speed) DC input DC input (high speed) DC input DC input (high speed) of I/O points 12 points 16 points 24 points Output Relay output Transistor output Relay output Transistor output Relay output Transistor output 68 points 16 points 56 points Max. numbers Input of I/O points Output 12 points 48 points 56 points 256 points (00000 to 00377) [コ0000 to コ0037] Input relay 256 points (00400 to 00777) [コ0040 to コ0077] Output relay 6656 points (01000 to 15777) [コ0100 to コ1577] (Includes special relay, special register) Auxiliary relay
Data memory
Type and numbers of instruction Program size
Timer / counter
Basic instruction: 11 Application instruction: 69 1.5 k words (RAM)
Total 256 points (TMR 000 to TMR 377, CNT 000 to CNT 377) • Timer set time: 0.1 to 199.9 seconds (TMR 000 to TMR 277) 0.01 to 19.99 seconds(TMR 300 to TMR 377) • Counter setting value: 1 to 1999 Timer/counter current value storage area: 512 bytes [b0000 to b0777]
Register System memory
2048 bytes [09000 to 09777, 19000 to 19777, 29000 to 29777, 39000 to 39777] 256 bytes [#000 to #377]
High-speed counter input
Single phase rising pulse input (2 points) or 90° differential two-phase signal (1 point). Maximum frequency: 10 kHz. Counter measuring range: 0 to 65535 (When the high-speed counter is used, input 00000 to 00003 becomes high-speed counter input.)
Interrupt program Password function Clock feature Halt output Expansion module
18 Communication port
MMI port
10 ms timer interruption (Execute subroutine having LB0177 label every 10 ms.) Yes None Yes None 1 point (Relay output 250 VAC/30VDC, 1A) OFF at error or stop mode, ON at normal operation Max.2 expansion module and 1 analog input/output module Unconnectable Selectable from computer link, data link, or remote I/O. 1) Computer link: SHARP's computer link protocol 38400/19200/9600/4800/2400/1200/600/300 bits/s. Maximum 63 stations. 1 km. 2) Data link: JW10 data link protocol 76800/38400 bits/s. Maximum number of slave stations: 7. 16 bytes/station. 500 m/1 km. 3) Remove I/O: JW10 remote I/O protocol 76800/38400 bits/s. Maximum number of slave stations: 4. 60 points/station. 500 m/1 km. Selectable from PG mode and computer link mode 1) PG mode: Connection of support tool • Hand-held programmer: JW13PG: multipurpose programmer: JW-50PG • Ladder software: JW-92SP, JW-50SP, JW-52SP. 2) Computer link: SHARP's computer link protocol 38400/19200/9600/4800/2400/1200/600/300 bits/s. One by one connection. 1 km.
18-2
Page 279
18-3 Specifications of I/O port (DC input : 16 points, relay output : 12 points)
Input port
Terminal 0 to 3 Terminal 4 to 17
Input OFF level
5 V (1.5mA) min.
Response OFF→ ON 1 ms max. time ON→ OFF 1 ms max.
0 1 2 3
Input display lamp
Output display lamp
5 6 7 10 11 12
10 ms max.
13 14
10 ms max.
15
Terminal 400 to 413 12 points No. of output Output system Relay Max. open-close 250 VAC/30 VDC voltage and current 2 A/point 2 A/common Min. load 5 VDC, 10 mA Operation Mechanical 20,000,000 times min.
16 17 COM.A
Power
COM.A
Circuit diagram
Load
400 401 402
1. Max. open-close voltage/current load: 100,000 times min. 2. Inductive load (250 VAC, 0.5 A Electrical (COS ø = 0.4)): 200,000 times min. 3. Inductive load (30 VDC, 0.5 A (T = 7 ms): 200,000 times min.
403 404
Relay
405 406 407
Power
Fuse
→ ON 10ms max. Response OFF→
COM.B
410 time ON→ OFF 10ms max. Operation indication LED lights at ON condition
411 412 413
Insulation system By relay Power
Insulation
500 VDC, 10 Mohm min.
resistance
(between output terminal and secondary circuit)
Dielectrical strength
1500 VAC for 1 minute
Common system
Photo coupler
4
8 V (1.5mA) min.
Operation indication LED lights at ON condition Insulation system By photo coupler Insulation 500 VDC, 10 Mohm min. resistance (between input terminal and secondary circuit) Dielectrical 500 VAC for 1 minute strength (between input terminal and secondary circuit) Common system 1 common line for 16 points (no polarity)
Output port
Circuit diagram
4 points 12 points No. of input 24 VDC Rated input voltage 12/24 VDC 20 to 26.4VDC Input voltage range 10 to 26.4VDC 3.6 mA TYP.(12V) 4.8 mA TYP.(24 V) Rated input 7.6 mA TYP.(24V) current 3.2 kohm TYP. 5 kohm TYP. Input impedance 10 V (3mA) max. 20 V (3.5mA) max. Input ON level
Internal circuit
JW-1324K
Internal circuit
[1]
(between output terminal and secondary circuit) 1 common line for 8 points (400 to 407) 1 common line for 4 points (410 to 413)
18・3
Fuse
COM.C
18
Page 280
(DC input : 16 points, transistor output : 12 points)
Input port
Terminal 0 to 3 Terminal 4 to 17
Circuit diagram
4 points 12 points No. of input 24 VDC Rated input voltage 12/24 VDC 20 to 26.4VDC Input voltage range 10 to 26.4VDC 3.6 mA TYP.(12V) 4.8 mA TYP.(24 V) Rated input 7.6 mA TYP.(24V) current 3.2 kohm TYP. 5 kohm TYP. Input impedance 10 V (3mA) max. 20 V (3.5mA) max. Input ON level
Input OFF level
5 V (1.5mA) min.
Response OFF→ ON 1 ms max. time ON→ OFF 1 ms max.
0 1 2 3
6 7 10
8 V (1.5mA) min.
11 12
10 ms max.
13 14
10 ms max.
15
Terminal 400 to 413
16 17
Output port
COM.A
Power
COM.A
Circuit diagram
No. of output 12 points Output system NPN transistor output (sink output) Rated load voltage 5/12/24 VDC Load voltage range 4.5 to 27VDC
Load
400 401
Rated max. load 0.3A/1 point 1.6A/8 points common (400 to 407) current
402
0.8A/4 points common (410 to 413)
405
403 404
406
Leak current at OFF 0.2mA max.
407
Voltage breakdown at ON 1.2V max. Surge killer Zener diode
+
Power
Fuse C(–)B − 410
→ ON 1ms max. (resistance load) Response OFF→ time ON→ OFF 1ms max. (resistance load)
411 412 413
Operation indication LED lights at ON condition Insulation system By photo coupler Insulation resistance Dielectrical strength Common system
Input display lamp
5
Operation indication LED lights at ON condition Insulation system By photo coupler 500 VDC, 10 Mohm min. Insulation (between input terminal and secondary circuit) resistance 500 VAC for 1 minute Dielectrical (between input terminal and secondary circuit) strength Common system 1 common line for 16 points (no polarity)
18
Photo coupler
4
Internal circuit
JW-1342K
+
500 VDC, 10 Mohm min. (between output terminal and secondary circuit) 500 VAC for 1 minute (between output terminal and secondary circuit) 1 common line(-) for 8 points (400 to 407) 1 common line(-) for 4 points (410 to 413)
18・4
Power
Fuse −
C(–)C
Photo coupler
Internal circuit
[2]
Output indicatior
Page 281
(DC input : 24 points, relay output : 16 points)
Input port
Terminal 0 to 3 Terminal 4 to 27 4 points 20 points No. of input 24 VDC Rated input voltage 12/24 VDC 20 to 26.4 VDC Input voltage range 10 to 26.4VDC 3.6 mA TYP.(12V) 4.8 mA TYP.(24 V) Rated input 7.6 mA TYP.(24V) current 3.2 kohm TYP. 5 kohm TYP. Input impedance 10 V (3mA) max. 20 V (3.5mA) max. Input ON level 8 V (1.5mA) min. Input OFF level 5 V (1.5mA) min. 10 ms max. Response OFF→ ON 1 ms max. 10 ms max. time ON→ OFF 1 ms max. Operation indication LED lights at ON condition Insulation system By photo coupler Insulation 500 VDC, 10 Mohm min. resistance (between input terminal and secondary circuit) Dielectrical 500 VAC for 1 minute strength (between input terminal and secondary circuit) Common system 1 common line for 24 points (no polarity)
Terminal 400 to 417 No. of output
0 1 2 3
Photo coupler
4
Input display lamp
Output display lamp
7 10
17 20
27
Power
COM.A COM.A
Circuit diagram
16 points
Output system Relay Max. open-close 250 VAC/30 VDC voltage and current 2 A/point 2 A/common Min. load 5 VDC, 10 mA Operation Mechanical 20,000,000 times min.
Output port
Circuit diagram
Internal circuit
JW-1424K
Internal circuit
[3]
Load
Power
1. Max. open-close voltage/current load: 100,000 times min. 2. Inductive load (250 VAC, 0.5 A Electrical (COS ø = 0.4)):200,000 times min. 3. Inductive load (30 VDC, 0.5 A (T = 7 ms):
400
Fuse COM.B 401
Power
COM.C
Relay
402 Power
COM.D 403
Power
COM.E 404
200,000 times min. 407
Response OFF→ ON 10ms max.
Power time ON→ OFF 10ms max. Operation indication LED lights at ON condition Insulation system By relay 500 VDC, 10 Mohm min. Insulation (between output terminal and secondary circuit) resistance Dielectrical strength Common system
1500 VAC for 1 minute (between output terminal and secondary circuit) 1 common line for 1 point × 4 (400 to 403) 1 common line for 4 points × 3 (404 to 417)
18・5
COM.F 410 413
Power
COM.G 414 417
Power
COM.H
18
Page 282
(DC input : 24 points, transistor output : 16 points)
Input port
Terminal 0 to 3 Terminal 4 to 17
Circuit diagram
4 points 12 points No. of input 24 VDC Rated input voltage 12/24 VDC 20 to 26.4VDC Input voltage range 10 to 26.4VDC 3.6 mA TYP.(12V) 4.8 mA TYP.(24 V) Rated input 7.6 mA TYP.(24V) current 3.2 kohm TYP. 5 kohm TYP. Input impedance 10 V (3mA) max. 20 V (3.5mA) max. Input ON level
Input OFF level
5 V (1.5mA) min.
Response OFF→ ON 1 ms max. time ON→ OFF 1 ms max.
0 1 2 3
6 7 10
8 V (1.5mA) min.
11 12
10 ms max.
13 14
10 ms max.
15
Terminal 400 to 417
16 17
0.3A/1 point
Output port
Rated max. load 0.8A/4 points common (404 to 417) current
COM.A
Circuit diagram Load
Voltage breakdown at ON 1.2V max. Zener diode Surge killer
400
Photocoupler
+
+
Leak current at OFF 0.2mA max.
COM.A
Power
No. of output 16 points Output system NPN transistor output (sink output) Rated load voltage 5/12/24 VDC Load voltage range 4.5 to 27VDC
+
+
Response OFF→ ON 1ms max. (resistance load) time ON→ OFF 1ms max. (resistance load)
Power
Power
Power
Power
Fuse C(–)B −
401 C(–)C
−
402 C(–)D
−
403 C(–)E
−
404 407
+
Operation indication LED lights at ON condition
Power
C(–)F −
410 413
Insulation system By photo coupler
18
Input display lamp
5
Operation indication LED lights at ON condition Insulation system By photo coupler 500 VDC, 10 Mohm min. Insulation (between input terminal and secondary circuit) resistance 500 VAC for 1 minute Dielectrical (between input terminal and secondary circuit) strength Common system 1 common line for 24 points (no polarity)
Insulation resistance Dielectrical strength Common system
Photo coupler
4
Internal circuit
JW-1442K
500 VDC, 10 Mohm min.
+
Power
C(–)G −
(between output terminal and secondary circuit) 500 VAC for 1 minute
417 +
(between output terminal and secondary circuit) 1 common line(-) for 1 point × 4(400 to 403) 1 common line(-) for 4 points × 4(404 to 417)
18・6
414
Power
C(–)H −
Internal circuit
[4]
Output indicator
Page 283
[5]
JW-1624K
(DC input : 36 points, relay output : 24 points)
Input port
Terminal 400 to 427 No. of output Relay Output system Max. open-close voltage 250 VAC/30 VDC 2 A/point 2 A/common and current 5 VDC, 10 mA Min. load Operation Mechanical 20,000,000 times min.
0 1 2 3
Photo coupler
4
Internal circuit
Terminal 0 to 3 Terminal 4 to 43 Circuit diagram 4 points 32 points No. of input 24 VDC Rated input voltage 12/24 VDC 20 to 26.4 VDC Input voltage range 10 to 26.4VDC Rated input cur- 3.6 mA TYP.(12V) 4.8 mA TYP.(24 V) 7.6 mA TYP.(24V) rent 3.2 kohm TYP. 5 kohm TYP. Input impedance 10 V (3mA) max. 20 V (3.5mA) max. Input ON level 8 V (1.5mA) min. Input OFF level 5 V (1.5mA) min. 10 ms max. Response OFF→ ON 1 ms max. 10 ms max. time ON→ OFF 1 ms max. Operation indication LED lights at ON condition Insulation system By photo coupler Insulation 500 VDC, 10 Mohm min. (between input terminal and secondary circuit) resistance 500 VAC for 1 minute Dielectrical (between input terminal and secondary circuit) strength Common system 1 common line for 36 points (no polarity)
Input display lamp
7 10
17 20
27 30
37 40
43 Power
COM.A COM.A
Circuit diagram
Output port
Load
Power
Power
COM.C
Relay
Output display lamp
402 Power
COM.D 403
Power
COM.E 404
200,000 times min.
407
Response OFF→ ON 10ms max.
Power
COM.F 410 time ON→ OFF 10ms max. Operation indication LED lights at ON condition Insulation system By relay 500 VDC, 10 Mohm min. Insulation (between output terminal and secondary circuit) resistance strength
Fuse COM.B 401
1. Max. open-close voltage/current load: 100,000 times min. 2. Inductive load (250 VAC, 0.5 A Electrical (COS ø = 0.4)):200,000 times min. 3. Inductive load (30 VDC, 0.5 A (T = 7 ms):
Dielectrical
400
Internal circuit
24 points
413 Power
COM.G 414 417
Power
COM.H 420 427
1500 VAC for 1 minute Power
(between output terminal and secondary circuit) 1 common line for 1 point × 4(400 to 403)
Common system 1 common line for 4 points × 3 (404 to 417) 1 common line for 8 points × 1 (420 to 427)
18・7
COM.I
18
Page 284
(DC input : 36 points, transistor output : 24 points) Terminal 0 to 3 Terminal 4 to 17
No. of input
4 points
Input port
Rated input voltage 12/24 VDC
Circuit diagram
12 points 24 VDC
20 to 26.4VDC Input voltage range 10 to 26.4VDC 3.6 mA TYP.(12V) 4.8 mA TYP.(24 V) Rated input 7.6 mA TYP.(24V) current 3.2 kohm TYP. 5 kohm TYP. Input impedance 10 V (3mA) max. 20 V (3.5mA) max. Input ON level
Input OFF level
5 V (1.5mA) min.
Response OFF→ ON 1 ms max. time ON→ OFF 1 ms max.
0 1 2 3
6 7 10
8 V (1.5mA) min.
11 12
10 ms max.
13 14
10 ms max.
15
Terminal 400 to 427
16 17 Power
Circuit diagram
Load
Output port
1.6A/8 points common (420 to 427)
+
+
+
Leak current at OFF 0.2mA max. Voltage breakdown at ON 1.2V max. Surge killer Zener diode
400
Photocoupler
0.3A/1 point
Rated max. load 0.8A/4 points common (404 to 417) current
COM.A COM.A
No. of output 24 points Output system NPN transistor output (sink output) Rated load voltage 5/12/24 VDC Load voltage range 4.5 to 27VDC
+
Power
Power
Power
Power
Fuse C(–)B −
401 C(–)C
−
402 C(–)D
−
403 C(–)E
−
404 407
Response OFF→ ON 1ms max. (resistance load)
+ time ON→ OFF 1ms max. (resistance load) Operation indication LED lights at ON condition
Power
C(–)F −
410 413
+
Power
C(–)G −
Insulation system By photo coupler Insulation resistance Dielectrical strength Common system
Input display lamp
5
Operation indication LED lights at ON condition Insulation system By photo coupler 500 VDC, 10 Mohm min. Insulation (between input terminal and secondary circuit) resistance 500 VAC for 1 minute Dielectrical (between input terminal and secondary circuit) strength Common system 1 common line for 36 points (no polarity)
18
Photo coupler
4
Internal circuit
JW-1642K
414 417
500 VDC, 10 Mohm min.
+
Power
C(–)H −
(between output terminal and secondary circuit) 500 VAC for 1 minute
427 +
(between output terminal and secondary circuit) 1 common line(-) for 1 point × 4(400 to 403) 1 common line(-) for 4 points × 3(404 to 417) 1 common line(-) for 8 points × 1(420 to 427)
18・8
420
Power
C(–)I −
Internal circuit
[6]
Output indicator
Page 285
(DC input : 16 points) Terminal 0 to 7 × 2
Input port
No. of input
Circuit diagram
16 points
Rated input voltage 24 VDC Input voltage range 20 to 26.4 VDC Rated input current 4.8 mA TYP. (24 V) 5 Kohm TYP. Input impedance Input ON level 20 V (3.5 mA) max. Input OFF level 8 V (1.5 mA) min. Response OFF→ ON 10 ms max. time ON→ OFF 10 ms max. Operation indication LED lights at ON condition Insulation system By photo coupler 500 VDC, 10 Mohm min. Insulation
0 1 2 3
Photo coupler
4
Internal circuit
[7] JW-112N
Input display lamp
5 6 7 Power
COM.A COM.A 0 1 2 3 4 5 6 7
Power
COM.B COM.B resistance Dielectrical strength Common system Weight Accessories
(between input terminal and secondary circuit)
[8] JW-112S
(Transistor output : 16 points)
500 VAC for 1 minute (between input terminal and secondary circuit) 1 common line for 8 points × 2 (no polarity) 160 g Expansion cable (4 cm) × 1
Circuit diagram
Load
0 1 2
Rated max. load 0.3A/1 point 0.8A/4 points common current
3
Output port
Leak current at OFF 0.2mA max.
+
Power
Output indicator
Fuse C(–)A −
Voltage breakdown at ON 1.2V max. Zener diode Surge killer
4 7
+
Response OFF→ ON 1ms max. (resistance load) time ON→ OFF 1ms max. (resistance load)
Power
C(–)B −
0 3
Operation indication LED lights at ON condition +
Insulation system By photo coupler Insulation resistance Dielectrical strength Common system Weight Accessories
Photocoupler
Internal circuit
Terminal 0 to 7 × 2 No. of output 16 points Output system NPN transistor output (sink output) Rated load voltage 5/12/24 VDC Load voltage range 4.5 to 27VDC
Power
C(–)C −
500 VDC, 10 Mohm min.
4 7
(between output terminal and secondary circuit) 500 VAC for 1 minute (between output terminal and secondary circuit) 1 common line(-) for 4 points × 4 230g Expansion cable (4 cm) × 1
18・9
+
Power
C(–)D −
18
Page 286
(Relay output : 16 points) Terminal 0 to 7 × 2
Circuit diagram
16 points No. of output Output system Relay Max. open-close 250 VAC/30 VDC voltage and current 2 A/point 2 A/common 5 VDC, 10 mA Min. load Operation Mechanical 20,000,000 times min.
Load
0 1 2
1. Max. open-close voltage/current load: 100,000 times min. 2. Inductive load (250 VAC, 0.5 A Electrical (COS ø = 0.4)):200,000 times min. 3. Inductive load (30 VDC, 0.5 A (T = 7 ms):
3 Relay Power
4 7 Power
200,000 times min.
Fuse COM.B
COM.C 0
Response OFF→ ON 10ms max.
3 time ON→ OFF 10ms max. Operation indication LED lights at ON condition Insulation system By relay 500 VDC, 10 Mohm min. Insulation (between output terminal and secondary circuit) resistance 1500 VAC, 1 minute Dielectrical (between output terminal and secondary circuit) strength Common system 1 common line for 4 points × 4 (no polarity) 220 g Expansion cable (4 cm) × 1
18
18・10
Power
COM.D 4 7
Power
COM.E
Internal circuit
[9] JW-114S
Output display lamp
Page 287
(DC input : 8 points, relay output : 8 points) Circuit diagram
8 points No. of input Rated input voltage 24 VDC Input voltage range 20 to 26.4 VDC Rated input current 4.8 mA TYP. (24 V) 5 Kohm TYP. Input impedance 20 V (3.5 mA) max. Input ON level Input OFF level 8 V (1.5 mA) min. Response OFF→ ON 10 ms max. time ON→ OFF 10 ms max. Operation indication LED lights at ON condition Insulation system By photo coupler 500 VDC, 10 Mohm min. Insulation (between input terminal and secondary circuit) resistance
Dielectrical
1 2 3
Photo coupler
4
Input display lamp
Output display lamp
5 6 7
Power
COM.A COM.A
500 VAC for 1 minute
(between input terminal and secondary circuit) strength Common system 1 common line for 8 points (no polarity) Terminal 0 to 7 8 points No. of output Relay Output system Max. open-close 250 VAC/30 VDC voltage and current 2 A/point 2 A/common 5 VDC, 10 mA Min. load Operation Mechanical 20,000,000 times min.
Circuit diagram
Load
0 1 2
1. Max. open-close voltage/current load: 100,000 times min. 2. Inductive load (250 VAC, 0.5 A Electrical (COS ø = 0.4)):200,000 times min. 3. Inductive load (30 VDC, 0.5 A (T = 7 ms):
Output port
0
Internal circuit
Input port
Terminal 0 to 7
Internal circuit
[10] JW-1124NS
3 Relay Power
Fuse COM.B
200,000 times min. 4
Response OFF→ ON 10ms max.
time
5
ON→ OFF 10ms max.
6
Operation indication LED lights at ON condition Insulation system By relay Insulation 500 VDC, 10 Mohm min. resistance (between output terminal and secondary circuit) Dielectrical 1500 VAC for 1 minute strength (between output terminal and secondary circuit) Common system 1 common line for 4 points × 2 (no polarity) Weight Accessories
190 g Expansion cable (4 cm) × 1
18・11
7
Power
COM.C
18
Page 288
(DC input : 16 points, relay output : 16 points)
16 points No. of input Rated input voltage 24 VDC Input voltage range 20 to 26.4 VDC Rated input current 4.8 mA TYP. (24 V) 5 Kohm TYP. Input impedance Input ON level 20 V (3.5 mA) max. Input OFF level 8 V (1.5 mA) min. Response OFF→ ON 10 ms max. time ON→ OFF 10 ms max. Operation indication LED lights at ON condition Insulation system By photo coupler 500 VDC, 10 Mohm min. Insulation (between input terminal and secondary circuit) resistance 500 VAC for 1 minute Dielectrical (between input terminal and secondary circuit) strength Common system 1 common line for 16 points (no polarity)
Terminal 0 to 7 × 2
Output port
No. of output 16 points Output system Relay Max. open-close 250 VAC/30 VDC voltage and current 2 A/point 2 A/common 5 VDC, 10 mA Min. load Operation Mechanical 20,000,000 times min.
Circuit diagram
0 1 2 3
7 0 1 2 3 4 5 6 7 Power
COM.A COM.A COM.A
Circuit diagram
0
2 3 Relay Power
Fuse COM.B 4 7
Power
200,000 times min.
Weight Accessories
COM.A
1
COM.C 0 3 time ON→ OFF 10ms max. Operation indication LED lights at ON condition Insulation system By relay 500 VDC, 10 Mohm min. Insulation (between output terminal and secondary circuit) resistance 1500 VAC for 1 minute Dielectrical (between output terminal and secondary circuit) strength Common system 1 common line for 4 points × 4 (no polarity) 320 g Expansion cable (4 cm) × 1
18・12
Output display lamp
6
Load
1. Max. open-close voltage/current load: 100,000 times min. 2. Inductive load (250 VAC, 0.5 A Electrical (COS ø = 0.4)):200,000 times min. 3. Inductive load (30 VDC, 0.5 A (T = 7 ms):
Input display lamp
5
Response OFF→ ON 10ms max.
18
Photo coupler
4
Internal circuit
Input port
Terminal 0 to 7 × 2
Internal circuit
[11] JW-1324NS
Power
COM.D 4 7
Power
COM.E
Page 289
18-4 Outline dimension drawings [1] Basic module
(1) JW-1324K, JW-1342K
(At connecting with JW-12KC) MMI cover
80 90
JW-12KC
76
100 110
76 100 Approximately 150
(2) JW-1424K, JW-1442K, JW-1624K, JW-1642K
(At connecting with JW-12KC) MMI cover
80 90
JW-12KC
76
170 180
76 124 Approximately 150
[2] Expansion module (2) JW-1324NS
80 90
80 90
(1) JW-112N, JW-112S, JW-114S, JW-1124NS
54 64
76
100 110
76
18
[Unit: mm]
18・13