[3] Precautions for connecting output device (1) Countermeasure to surge current of lamp load At turning on an incandescent lamp, there is surge current 10 to 20 times bigger than normal current for several 10 ms. For reduction of the surge current, insert either a bleeder resistance or an electric current limit resistance. ① To insert a bleeder resistance During the OFF state of the output port, keep supplying dark current so small as to turn on the lamp dimly. Bleeder resistance

Output port

② To insert an electric current limit resistance This limits the current within a value determined by the value of the current limit resistance. When the Current limit Output resistance resistance value is high, the voltage on the lamp port decreases. Determine the resistance value by the brightness needed when turning on the lamp.

(2) Countermeasure to surge voltage at opening/closing induced load Some load generates surge voltage of several thousands volt when an induced load is opened or closed its circuit. As the module of relay output type does not have surge absorption circuit, surge countermeasure outside the module is indispensable in case the load generates high voltage. (This surge voltage countermeasure can extend the life time of the contact points of the relay.) The transistor output module has an integrated internal circuit to absorb voltage surges.Howefver, if a load is located far from the relay output and a long wire is used to connect the load, the surge absorption circuit may not function well. In this case, you should provide a surge absorption circuit near the load. Surge voltage countermeasure ① Inserting CR surge killer

② Inserting a diode L load

L load

+ −

Surge killer

Diode

(Relay output)

(Relay output)

L load + −

Diode (Transistor output)

6-11

6

Page 38

CR surge killer:

R

C

C: 0.033 to 0.33 µF (Pressure resistance should be 250 VAC or higher) R: 47 to 120 ohm

Example of CR surge killer For 100 VAC

ECQ-J0186X(0.1 µ + 120 ohm) (made by Matsushita Electric Co., Ltd.)

For 200 VAC

ECQ-J0187X(0.033 µ + 120 ohm) (made by Matsushita Electric Co.,Ltd.)

Diode:

Peak inverse voltage (VRM) should be more than 3 times of the load voltage. Average rectified current (Io) should be more than load current.

In case of AC load, a varistor can be used in place of the CR surge killer for the same effect. (Installation of both of the CR surge killer and the varistor increases the effect.) For 85 to 132 VAC

TNR12G221K (made by Marcon Co., Ltd.), ERZV14D221 (made by Matsushita Electric Co., Ltd.)

For 170 to 264 VAC

TNR12G431K (made by Marcon Co., Ltd.), ERZV14D431 (made by Matsushita Electric Co., Ltd.)

6

Load

C

Though a capacitor is very effective for the arc deletion at shut-off. But charged current to the capacitor may melt the contact point at turning ON a contact point.

Power supply

Power supply

Note 1: Avoid the use of a capacitor only as an arc killer, as shown below:

Load

C

Though a capacitor is very effective for the arc deletion at shutoff. But at the opening of the circuit of a contact point, electricity is accumulated at the capacitor. Therefore, the short circuit current of the capacitor may melt the contact point at turning ON the contact.

(3) When driving miniature load The relay used in the module of relay output type is suitable for power drive, and so with a low voltage and small current such as less than 10 mA, the contact reliability of the contact point drops. In such a case, we recommend to be used module of transistor output type.

6-12

Page 39

(4) Life of relays The life of relays used in output circuit, varies depending on the kind of loads. The following shows characteristic curves of the relay contact point.

; ;;;;;;;;;;; ;;;;;;;;;;; ;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;; ;;;;;;;;;;; ;;;;;;;;;;; ;;;;;;;;;;; ;;;;;;;;;;; ;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;; ;;;;;;;;;;;;;;;;;; ;;;;;;;;;;; ;;;;;;;;;;; ;;;;;;;;;;; ;;;;;;;;;;;;;;;;

Max. 2,000,000 times

No. of switching (x 10,000 times)

200

100 70

30 VDC T = 0

50 120 VAC COSφ=1

30

250 VAC COSφ=1 10 30 VDC T = 7 ms

7

120 VAC COSφ= 0.4 250 VAC COSφ= 0.4

5 3

30 VDC T = 40ms 30 VDC T = 60ms

1

0.1

0.3 0.5 0.7 1

2 3 45

Switching current (A)

Note 1: The above chart shows standard values. Depending on the environment of usage (ambient temperature, etc.), different life may result. Note 2: When the signal to the contact point is DC, the life of relays varies according to the load rise characteristics (time constant: T) of the load. The load rise characteristics of the load after the contact point is turned ON are determined by inductance: L and resistance: R

T=

R L

For the time constant of the load used, see below: In case of resistance load: T < 1ms In case of small size relay: T = 7 ms In case of large current L load and magnet: T = 40 ms In case of a L load with a diode for surge countermeasure, the life may be similar to the case of T < 1ms. Note 3: Use the contact switching life of more than 100,000 times and within the switching current of less than 2A.

6-13

6

Page 40

6-5

Wiring with noise countermeasures For your safe usage of the JW10, observe the "6-1 Precaution for wiring" carefully. Wiring to prevent the JW10 from malfunction caused by noise is shown below. Besides, some malfunctions by noise come from complex causes or a cause which cannot be analyzed in quantity. Use the following noise countermeasures as your reference, when you take measures for each actual situation.

[1] Grounding Grounding has two purposes; to protect operators from electric shock and to prevent malfunction by noise. The grounding for noise prevention is shown here. Don't use a common ground for the JW10 and other device. When the FG cable of the JW10 is also used for grounding for other device, noise might come into the JW10 from other device.

6

Other device

JW10

Common grounding

Bad example: Don't use the FG line of the JW10 for grounding of a motor or an inverter. Control panel Motor (heavy load) JW10 ground

Inverter ground

Ground

Terminal block

Class-3 grounding

Countermeasure 1: Separate grounding for each of the JW10, the motor and the inverter. Motor (heavy load) JW10 ground

Inverter ground

Terminal block

Less than 5 m

Note 1: Use a twisted wire of over 2 mm2 sectional area and less than 5 m long in grounding the JW10 for the noise prevention purpose.

6-14

Page 41

Countermeasure 2: When separate grounding is not available. • If a separate grounding for the JW10 cannot be made, ground directly from the FG terminal of the JW10 to the chassis on which the JW10 is mounted.

Ground directly to chassis

Motor (heavy load) JW10 ground

Inverter ground

Ground

Terminal block

Note 1: Observe the following points for direct grounding of the FG cable of the JW10 to the chassis: • Connect the grounding cable from the FG terminal of the JW10 to the chassis in the minimum distance. • Where the control panel itself is grounded, do not wire between the grounding point and the FG terminal of the JW10. Do not wire here. Ground point of the control panel

Reference:

6

JW10 ground

Note for fitting the JW10 on the control panel door. Ground from the FG terminal of the JW10 to the door. Use a twisted wire of over 2 mm2 sectional area for grounding cable of the control panel from its door (less than 50 cm.) JW10 Control panel

Door Connect the JW10 ground cable with the door. Connect the door ground cable with the control panel chassis.

6-15

Page 42

[2] Countermeasure of noise from power supply line The AC power supply input noise resistance capacity of the JW10 is 1000 Vp-p. When any noise over this limit is possible to come through the power supply line, install an insulation transformer. Countermeasure 1: Install an insulation transformer Noise has a high frequency of 100 KHz to 2 MHz, which should be blocked by a transformer. Insulation transformer

JW10 AC power supply

6

AC input

Note 1: When using an insulation transformer, note the following points: • An insulation transformer with static electricity shield can also prevent noise by static coupling. • Install an insulation transformer near the power supply input of the control panel in order to block noise at the entrance of the control panel. Control panel Insulation transformer

JW10

AC power supply

Terminal block

Twisting

• Use two twisted wires in the primary and secondary sides of the transformer. • Choose the insulation transformer of the capacity of more than 20% higher than that of the rated load. When a transformer of the same capacity as that of the rated load is used, a primary input voltage might exceed the transformer rated capacity and become dangerous state such as emitting smoke. Basic module

Power consumption

JW-1324K/1342K

30 VA max.

JW-1424K/1442K

55 VA max.

JW-1624K/1642K

60 VA max.

• When a large-capacity transformer with higher voltage in the secondary side is chosen, we recommend to install a intermediate voltage tap. 110V 100V 90V

Primary side

0V

• With particularly large noise, several transformers can be installed, not only to the power supply input of the JW10 but also to the load. Breaker

Breaker For JW10 power supply

AC power supply

For load

6-16

Page 43

[3] Safeguard from lightning Below are countermeasures in case when the factory facilities are located far from residential areas and that effects from induced lightning (induced voltage by lightning strikes) are expected. Note, however, that they are not the measures for direct strikes of lightning. In some cases, the voltage of the induced lightning may go beyond 4,000 KV. Therefore, the purpose of these countermeasures is just to minimize the damage on the device.

Factory

Countermeasure 1: Install a surge absorber on the receiver panel of commercial electric power as protection from induced lightning. Different models should be chosen according to the facilities load and power supply voltage. For your reference, below is a wiring diagram of the outdoor type cubicle for 1.7 KVA. Main breaker 30A Breaker U

Transformer (for voltage reduction) AC100V

250 VAC input V

For other device

JW10 AC input

FG

Surge absorber E Class-3 grounding Special class-3 grounding (less than 10 Ω)

Note 1: Note the following when wiring. • The ground of the surge absorber is the special class-3 ground (less than 10 ohm ground resistance) and should be separated from the ground of the JW10. (class-3 grounding.) • Install the main breaker before the surge absorber. • The followings are known surge absorbers in the market. Different types for different power supply voltages. Commercial power voltage

100 VAC

200 VAC

Model name

ERZ-A20PK251

ERZ-A20PK501

Specifications Varistor voltage: 250 V ± 10% Surge resistant volume: 5,000 A (8/20 µs) Energy resistant volume: 90 Joule Varistor voltage: 500 V ± 10% Surge resistant volume: 5,000 A (8/20 µs) Energy resistant volume: 70 Joule

• Use the ground wire of over 3.5 mm2 section area for the surge absorber.

6-17

Manufacturer

Matsushita Electric Co.,Ltd.

6

Page 44

Countermeasure 2: Underground wiring as a countermeasure of lightning. When communication cables and input cables of the JW10 go out of a building, place them underground. Provide junction for input/output signals using relays. 1) Underground cabling In a lightning weather condition, the atmosphere is electrically charged and a wiring in the air induces a voltage of over 24 VDC. Therefore, place the wiring under the ground.

Outside panel

60 cm or 120 cm below ground level

As for the depth of cable installation, refer to local regulations.

6

2) Relay connection for the input/output signals using relays. The relay isolates the effects of lightning and minimizes the damage.

JW10 Relay

Input

CR1

COM Output Load

CR2

COM

[4] Wire of expansion cable When turning ON/OFF of the magnet switch installed near the JW10 and expansion cable, high noise and high voltage may occur to give bad effects on the operation of the JW10. Therefore, for prevention of the noise occurrence, insert a noise killer, such as a varistor, at the contact point of the magnet switch. Do not place the expansion cable, through which input/output signal lines and power lines are running. Magnet switch Varistor

Wiring duct

Input/output signal lines

6-18

JW10

Expansion cable

Page 45

[5] Note for external wiring to I/O port (1) Wiring to input port When extending the external line to the input port for more than 100 m, use shielding wire. Even in case of less than 100 m extension, shielding wires should be used under certain conditions. Do not forget to connect the shield of the shielding wire with the FG terminal of the JW10. JW10 Input COM FG

(2) Wiring to output port Since the output port does not have a built-in surge absorbing circuit, do not forget to install a surge killer, such as a varistor, in the output side. Operation without a surge killer might give bad effects on other modules by spark noises from the relay. As for the surge killer, see 6・10, "Precaution for connecting output device." (3) Wiring with power line Do not run the input signal, output signal and communication cables of the JW10 near and in parallel with the power line. • When input and output signal cables are extended for long distance, make separate wiring for the input signal and the output signal of JW10.

Separate wiring

Input

JW10

Output

• Make separate wiring for the input signal and the output signal of the JW10 from the power line. Particularly with the power line for the inverter and the servo driver, do not place signal wires inside the same duct or cable with the power line, even if the distance is short.

In the same duct

JW10

Inverter

JW10

Inverter

In separate duct

6-19