Programmable controller New Satellite JW, Model name JW50H/70H/100H, User's Manual/Hardware version: Chapter4. Name and function of each part, pages 119 to 128

Pages 119 to 128 of 254, from Programmable controller New Satellite JW, Model name JW50H/70H/100H, User's Manual/Hardware version

The original document is the PDF (8.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Sharp ZW-32IO2 and Sharp ZW-32S2T

Page 119 read from a scan by OCR; it may hold reading errors

Control module tk 1EA 2EA .

2EA |, _

|

| Support tool Support tool

Unacceptable o - - - Gy tf 1ca 2EA 2EA

Support tool Support tool

4-91

Page 120 read from a scan by OCR; it may hold reading errors

[4] Outline dimension drawings

JW-TEA gp re

R = oo si Caan S > 18.5112 80

95 95

[5] Specifications

Applicable rack panels JW-4BU/6BU/8BU/13BU _| Total cable length 50 m max. from JW-1EA (per system)

JW-OS5SEC (50cm long) JW-1EC(1 m long) JW-3EC(3 m long) JW-10EC(10 m long

Applicable I/O expansion JW-20EC(20 m long) ) )

cables

JW-30EC(30 m long JW-50EC(50 m long Internal current consumption 550 mA (5 VDC)

Weight 0.4kg Accessories Two termination connector | None

4-92

Page 121 read from a scan by OCR; it may hold reading errors

4-10 ZW-10EU I/O expansion module

[1] Outline and features (1) Outline The ZW-10EU I/O expansion module is used to expand the system by allowing additional ZW-series I/O modules to be included. It allows up to 32 ZW-series I/O modules to be added to the basic system, although the number of available I/O points supported is unaffected by the addition of I/O modules past the specified maximum.

‘No. of all /O modules vodules | when using the ZW-10EU

~ SW-50CU, JW-50CUH 512 32 64(Noie 1)

oe PC model n

JW-70CU, JW-70CUH 1024 32 64(Note 1) JW-100CU, JW-100CUH 2048 32 64(Note 1)

Note: While the ZW-10EU allows the system to be expanded from a 32-module into a 64-module system, the maximum number of I/O points available is not increased by additional I/O modules.

(2) Features 1) The ZW-10EU expands the PC system from being able to support 32 modules to being able to support 64 modules. (Note) Basic system Expansion system

2wSOZE | 2eSZ8 | | za-meze ! (T fi |

EL 0 G 0

(7

Hi ih

20-28 20a

ZW-108Z8 A 2W-BZ8 ww BS

Zw bad 2e-188U | : | BWEY 1 aware 1 \ gu gee | '

B ~~, _, _ TSignal cable for system expansion (ZW-1KC) (Basic) (Using the I/O expansion module)

Note: A 64-module system consists of 32 HO modules in the basic system and 32 YO modules in the expansion system.

Hi-Z 8 24-08BU

Daze DW-88U

Hfenfees_t

2) One dummy area be defined without the need for a dummy module. The interval between the last address of the basic system and the top address of the expansion system is defined as a dummy area (see the following figure):

/O address (byte address) joooo

Last address of basic system

]0123 Dummy area (]0124 to ]0177) Top address of expansion system I/O area corresponding to ]o200 the I/O expansion module

10377

4-93

Page 122 read from a scan by OCR; it may hold reading errors

[2] Name and function of each part

@Module retention screws

@RUN indicator

@ Address switches

(6:Address switch cover “Rating plate

()/O expansion connector (OUT)

te @)Module retention screws

LY

@ Module retention screws Use these screws to secure the I/O expansion module to the rack panel frame.

(2) RUN indicator When lit, this indicates that the control module is controlling the I/O modules in the expansion port.

(3) Address switches Use these switches to set the last address of the basic port and top address of the expansion port. Basic system's last address switches: (1) Use these switches to set the last address of the I/O module included in the basic port, using byte address representation. (Default setting at delivery : ]OO0). Expansion system's top address switches: (2) Use these switches to set the top address of the I/O module included in the expansion port, using byte address representation (Default setting at delivery : ]200)

4) Ratings plate (5) VO expansion connector (OUT) © Use this connector to connect an expansion signal cable for the expansion port. (6) Address switch cover Remove this cover to gain access to the address switches. eo

4-94

Page 123 read from a scan by OCR; it may hold reading errors

[3] Using the ZW-10EU I/O expansion moduie The ZW-10EU is installed in a basic rack panel (ZW-28KB/ZW-46KB) or a rack panel (ZW-08BU used as an expansion I/O rack panel).

(1) Installation configurations 1) Standard installation When the ZW-10EU its installed in a basic rack panel ZW-28KB/ZW-46KB. 1. Install the ZW-10EU in any one of the option siots in the basic rack panel. (Example: Installing the ZW-10EU in the ZW-28KB basic rack panel)

Option slots ra be rl INside {i6t |

3 cull E ZW-10E Ueto iL | VO modules SS = ZW-10EU I/O expansion module . Control module Signal cable for expansion Expansion rack panel (ZW-1KC) b of, - - ZW-1PU Power supply module

2. Use the optional ZW-1KC signal cable for system expansion for connection to and within the expansion system.

3. The total length of the signal cable for system expansion connected to the ZW-10EU should not exceed 4m (dotted line in the figure below).

4. Use a separate power supply module (+5V) to supply the expansion system. Do not supply the expansion port from the basic system’s power supply module.

Basic system Expansion system | ZW - 508ZB ro i} zw - 5082 8 1 H H 1 HY fT ~ I] Zw - 1082 8 4 i ZW - 1082.8 * 2w-0BU || | 2w - 0BU i pi kaw 7 1 TTT 2w - oeze ZW-1087B |] 4 ZW-088U 1 ‘al . 2W-08SU | i Lammy ZW-46KB 1! [| ZW-1087 8 ZW - -2BKB 4 j 2W - 08BU "Power supply module

Basic rack panel / \ Signal, cable for expansion {ZW-1KC)

Note : If no module other than the ZW-10EU is to be installed in the option slots, the ZW-2CC position cable is not needed.

4-95

Page 124 read from a scan by OCR; it may hold reading errors

2) Special installation For special installation, the ZW-10EU is installed in a rack panel in the basic system when all of the option slots in the basic rack panel are occupied. 1. The ZW-10EU is installed in a ZW-O8BU rack panel.

"| ca a

IN side ~ 5 = ZW - 10EU connector | t }, ~ VO module ; . ~ I/O expansion module (ZW-10EU) a Expansion rack panel : Vacant or power supply module, Signal cable for of (2W-1PU) expansion (ZW-1KC)

2. Install the ZW-10EU into the slot next to the second slot from left slot (which normally holds the control module).

3. The ZW-10EU may be installed in any ZW-O8BU rack panel within the basic port.

4. Use the optional ZW-1KC signal cabie for system expansion for connection to and within the expansion port.

5. The total tength of the signal cable for system expansion connected to the ZW-10EU should not exceed 4m (dotted line in the figure below).

6. Use a separate power supply module (+5V) to supply the expansion port. Do not supply the expansion port from the basic port's power supply module.

Basic system Expansion system

., ~ 1 SRE ” 1 ZW-5082.B | | f --+ ZW-50828 1 i H l H : | a | 0828, a zw) 2 RE aa By meee | CTT FW 0B O 0 I Oo H 1 I i (Se ey ryt 7 6 4 W - 108Z 1 Re ci i Sheu Po H ', - » ! 2 - ZW-1082 B ZW- 46KB ZW-O88U ZW-28KB H Power supply module

' Signal cable for expansion (ZW-1 KC)

4-96

Page 125 read from a scan by OCR; it may hold reading errors

(2) Installing the ZW-10EU and setting the address switches The following describes how to install the ZW-10EU into the basic rack panel and how to set address switches.

Switch the system power OFF. Mounting screw hole for power supply module

* Mounting screw hole for control module

Yv. 2D Install the ZW-10EU a into one of the option slots in the basic rack

Phillips screwdriver panel. Note: The ZW-10EU requires no option cable. Vv Remove the address Remove the cover by pulling its top edge forward. power OFF. Vv

Set the last address Set the last address of the basic system using the upper three address

(byte address) of the:, switched A, B and C (address range: 000 to 376) Note 2. basic system.

>

@

O

Example) If the last address of the basic system is

-01237, it becomes j0123 in byte address representation. Set the lower three digits, 123, of the address using the switches (see the figure at right).

Last address of the basic system

Note 1: Use a slot screwdriver to set the switches. Note 2: The address range is 000 to 176 if the JW- 7OCU, JW-70CUH control module ts used.

Screwdriver v

To next page. Applicable screwdriver

4-97

Page 126 read from a scan by OCR; it may hold reading errors

From previous page

Define dummy Predefining a dummy area is convenient for future system expansion. address area. The difference between the basic port's last address and expansion port's top address is defined as a dummy area.

I/O address (byte address) ]oo00

Last address of basic system j0123 Dummy area (J0124 to J0177} Top address of expansion system I/O area corresponding to ]o200 the I/O expansion module j0377

Vv

Set the top addres} Set the top address of the expansion port using the lower three rotary (byte address) of the switches: ; expansion port. : Setting Basic port's Expansion < 377 (Note 2) - area---.. | last address P top address

Example) To set the top I/O address of the expansion port to 02000 (JO200 byte address), set the lower 3 digits "200" of ]0200 as shown at right:

Note 1: Whenever possible, use an even number for the top address of the expansion port. This will make the PC's word instructions easier to use.

First address of expansion system

Note 2: The allowable address range is 001 to 177 (octal) for the W70H, and 001 to 377 (octal) for the W70H.

v To next page.

4-98

Page 127 read from a scan by OCR; it may hold reading errors

From previous page

Connect the signal cable for system Basic system Expansion system expansion. - - - - _ Ld ZW-5RZB Z2W-506ZB i H ' LH F F [J i ba 7 aun ye ~ BNE. al H D 0 } il rT it E a a a U ZW-10EU. { 2 Ei 1] th Bee H a ey on

\ Signal cable for expansion (ZW-1KC)

Turn the system power ON.

IN side connecotor ei

Expansion rack panel lp of

Signal cable for expansion (ZW-iKCY

To next page.

4-99

Page 128 read from a scan by OCR; it may hold reading errors

From previous page

Set system memory address #0252

Set system memory address #0252 q

End

Set the I/O address self-diagnosis function

Specify whether the I/O address self diagnosis feature is to be used or not:

000): Self diagnosis is not used.

105i): Self diagnosis is used.

Write the total number of !/O points (through the last I/O address of the expansion system) into system memory address #0250.

The I/O address self diagnosis feature checks the number of bytes used for I/O in the basic system, dummy area, and expansion system. It is implemented if the value 105) is written into system memory address #0252 (Note 1).

(Example) When using 1056 points of I/O relays up to address ]0203, write 204 into system memory address #0250. ]0203(1056 points): 132 bytes : 204,e)

Note 1: For more details, see the programming manual, section 2-4, system memory.

Note 2: If you write 000() into system memory location #0252, location #0250 does not need to be set.

(3) Checking system run (RUN indicator)

When the ZW-10EU I/O expansion module is functioning normally, the green RUN indicator on the module comes on. The RUN indicator goes OFF in any of the following cases :

*The power to the ZW-10EU I/O expansion module is turned OFF. The indicator also goes OFF if the power to the top rack panel attached to the module is turned OFF.

«The last address of the basic port is improperly set.

*The ZW-10EU is not connected to the expansion port with a signal cable for system expansion, or no VO module is installed on the first rack panel in the expansion port attached to the module.

RUN O

RUN indicator (green)

4-100