SHARP Programmable Controller New Satellite W series: Network module JW-20CM, Remote I/O slave module JW-20RS User's Manual: Chapter 8: Remote I/O, pages 79 to 88

Pages 79 to 88 of 230, from SHARP Programmable Controller New Satellite W series: Network module JW-20CM, Remote I/O slave module JW-20RS User's Manual

The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Sharp ZW-1PU, Sharp ZW-32IO2 and Sharp ZW-32S2T

Page 79

[Single address and continuous address] · If a slave station's I/O area is not linked to the previous slave station's I/O area, this slave station should be set as a "single address slave station ."

コ0200 コ0217

Slave station 1

}

128 points Need to set address

コ0240

· If a slave station's I/O area is linked to the previous slave station's I/O area, you do not have to set the address this slave station if "continuous address" is selected (turn OFF the D7 bit in the address's upper byte).

Slave station 2

}

Slave station 1

} }

128 points

コ0200 コ0217 コ0220 コ0237

Slave station 2

128 points Select the "continuous address" setting (You do not need to set 128 points addresses for each I/O area.)

· If "continuous address" is selected, the address changes in the previous slave station (the top I/ O address in slave station 1 in the example above) will automatically changes the addresses of the linked slave stations accordingly. If you want to disable automatic address changes, select the "single address" mode, even if the slave station address is in a continuous series with the previous slave station addresses. Then enter the address of the slave station manually.

8·41

8

Page 80

"Only when using manual allocation " ⑥

Enter the number of I/O bytes for each slave station

[DCM (decimal), byte]

(Applied to item ⑥ on pages 8·31 and 8·35) · Enter the number of I/O bytes per slave station at parameter addresses 000201 to 000277(8). · Enter the number of I/O bytes per slave station (1 to 128 bytes) in decimal notation. Entering a value greater than 128 is treated as an error. Slave station number(8)

Address

(8)

Slave station number(8)

Address

(8)

Slave station number(8)

Address

(8)

(8)

Slave station number(8)

-

-

000220

20

000240

40

000260

60

000201

01

000221

21

000241

41

000261

61

000202

02

000222

22

000242

42

000262

62

000203

03

000223

23

000243

43

000263

63

000204

04

000224

24

000244

44

000264

64

000205

05

000225

25

000245

45

000265

65

000206

06

000226

26

000246

46

000266

66

000207

07

000227

27

000247

47

000267

67

000210

10

000230

30

000250

50

000270

70

000211

11

000231

31

000251

51

000271

71

000212

12

000232

32

000252

52

000272

72

000213

13

000233

33

000253

53

000273

73

000214

14

000234

34

000254

54

000274

74

000215

15

000235

35

000255

55

000275

75

000216

16

000236

36

000256

56

000276

76

000217

17

000237

37

000257

57

000277

77

Address

8

Initial value: 00(H) in all addresses Ex. Assign 8 bytes (64 points) to slave station 01 and 10 bytes (80 points) to slave station 02 using the JW-13PG.

Display the contents of address 000201(8)

(

After converting into decimal notation, write the result in 8(D).

)

Screen display of JW-13PG Write 10(D) at address 000202(8).

00200 00201 I PARAM. >00202

DCM DCM

000 008

DCM

010

8·42

Page 81

"Only when the master station is a JW model" ⑦

Enter the I/O type for each slave station

[Bit pattern, bytes]

(Applied to item ⑦ on pages 8·31 and 8·35) · Declare whether the I/O module installed in each slave station (01 to 77(8)) is a "JW model" or a "ZW model" at parameter address 000400 to 000407(8). · Set the bit corresponding each slave station to 0 (OFF) if it is a ZW model, or 1 (ON) if it is a JW model. Set value

Enter the value of the I/O type

0 (OFF)

ZW model

1 (ON)

JW model

Parameter addresses(8)

Corresponding to the slave station number(8) 7

6

5

4

3

2

1

0

000400

07

06

05

04

03

02

01

-

000401

17

16

15

14

13

12

11

10

000402

27

26

25

24

23

22

21

20

000403

37

36

35

34

33

32

31

30

000404

47

46

45

44

43

42

41

40

000405

57

56

55

54

53

52

51

50

000406

67

66

65

64

63

62

61

60

000407

77

76

75

74

73

72

71

70

Initial value: FF(H) in all addresses

Ex. Make slave station 07 a "ZW model" and all the other slave stations JW models, using the JW-13PG.

Display the contents of address 000400(8)

Write a 0 in bit 7 (slave station 07) after converting to bit pattern

Screen display of JW-13PG 00376 □□□□□□□□ 00377 □□□□□□□□ I PARAM. >00400 □■■■■■■■

8·43

8

Page 82

"Only when the master station PC is a JW model and a JW model special I/O module is used as a slave station" ⑧

Enter the data register address

Station number: OCT (octal), bytes of the special I/O module

Rack and slot numbers: HEX (hexadecimal), bytes

(Applied to item ⑧ on pages

Number of data bytes: DCM (decimal), bytes

8·31 and 8·35)

Register top address: OCT (octal), bytes

· Since the special I/O module uses an I/O relay area and a data memory area, you have to enter slave station numbers, rack/slot numbers, the number of data bytes, and the top register addresses of the slave station which contains the special I/O module at parameter address 000600 to 000777(8). · Use 4 bytes of memory to assign one special I/O module. Parameter address (8)

Set contents

000600

Slave station number (00 to 77(8))

000601

Upper 4 bits: Rack number (0 or 1) Lower 4 bits: Slot number (00 to 0F(H))

000602

Number of data bytes (01 to 64(D))

000603

Top register address (file address) D7 bit: 1 for set, 0 for not set.

to

8

Special I/O number to

No.1 to

000774

Slave station number (00 to 77(8))

000775

Upper 4 bits: Rack number (0 or 1) Lower 4 bits: Slot number (00 to 0F(H))

000776

Number of data bytes (01 to 64(D))

000777

Top register address (file address) D7 bit: 1 for set, 0 for not set.

No.32

Initial value: 00(H) in all addresses ■ Number of data bytes Enter the number of bytes that the special I/O module uses for data exchange. A maximum of 128 bytes can be assigned per station. A maximum of 512 byes can be assigned to all stations.

Special I/O module model name

Number of data bytes

JW-8AD (analog input)

36 bytes

JW-2DA (analog output)

8 bytes

JW-2HC (high speed counter)

8 bytes

JW-31LM (I/O link master station)

2 to 6 bytes

JW-11DU/12DU (ID control module)

64 bytes max.

JW-12PM (positioning module)

16 bytes

8·44

Page 83

■ Top register address Enter top address of each special I/O module, which can be allocated up to 64 points per unit, at file addresses 000000 to 017700(8). Bit contents of the parameter address 000603(8) etc. 7 6 5 4 3 2 1 0 4th digit 3rd digit

0

0

2nd digit 1st digit

5th digit 1: Enter top register address 0: Do not enter top register address Lower 2 digits are always 00.

Ex.: Set a JW-2DA (8 data bytes and a top register address of 490000) installed in "slave station number 01," "rack number 0," "slot number 2" and assigned as No. 1 (1st module) using the JW-13PG. Remote I/O master station

Slave station 01

Slave station 02

Slave station 03

JW-2DA

After converting into octal notation, write station number 01(8)

Display the contents of address 000600(8)

8

Write rack number 0 and slot number 2 at parameter address 000601(8). After converting it into decimal notation at parameter address 000602(8), write the number of bytes 8. Screen display of JW-13PG 00601 00602 I PARAM. >00603

After converting the number into octal notation at parameter address 000603(8), write it at 300(8).

3 Parameter address 000603(8)

0

0

1 1 0 0 0 0 0 0 0 0 1

0 0 0 0

Set File address 10000(8) = Register address 49000

8·45

OCT OCT

003 010

OCT

300

Page 84

8-4 Error and treatment Operation status of the JW-20CM can be check by indication lamps, flags, or system memory. (1) Indication lamp ① JW-20CM

JW–20CM COMM○ SD○ RD○ CD○ LT○ TEST○ ERROR○ FAULT○

○S0 ○S1 ○S2 ○S3 ○S4 ○S5 ○S6 ○S7

Indication lamp

8 Name

Operation

Recovery

COMM

Lights while the remote I/O is operating

--------------------------------------------------

SD

Flickers while sending data

--------------------------------------------------

RD

Flickers while receiving data

--------------------------------------------------

CD

Flickers while detecting a carrier

--------------------------------------------------

LT

Lights when the termination resistance switches turned ON

--------------------------------------------------

TEST

Lights while testing

--------------------------------------------------

ERROR

· Check disconnection of communication cable Lights while an error is detected (Indicate · Check settings of switches · Check settings of parameter error code by S0 to S7 LEDs) · Check power supply voltage.

FAULT

Lights when the watchdog timer is time up (JW-20CM is faulty)

Replace the JW-20CM

S0 to S7

Indicates error codes by hexadecimal when an error is occurred

See the next page

8·46

Page 85

(Error code) Error LED name code S0 S7 6 5 4 3 2 1 (HEX)

Cause

Measure

○○ ○ ○ ○○ ○● ○○ ○ ○ ○○ ●○

01(H) ROM error, upper CPU 02(H) RAM error, upper CPU

○○ ○ ○ ○○ ●● ○○ ○ ○ ○● ○○

Replace the JW-20CM 03(H) 2 port RAM error against PC, upper CPU 2 port RAM error against communication CPU, upper CPU 04(H)

○○ ○ ● ○○ ○● ○○ ○ ● ○○ ●○

11(H) ROM error, communication CPU 12(H) RAM error, communication CPU

○○ ○ ● ●○ ○○

18(H) Communication LSI error, communication CPU 1F(H) No response, communication CPU

• Check the communication cable • Check for doubled allocation of slave station number • Replace the JW-20CM

20(H) More than one token detected 21(H) Doubled address detected

Check the parameter setting and switch setting.

○○ ○ ● ●● ●● ○○ ● ○ ○○ ○○ ○○ ● ○ ○○ ○● ○○ ● ○ ○○ ●○ ○○ ● ○ ○○ ●●

22(H) Fault of sending section • Replace the JW-20CM Token does not return within the rated interval • Check the communication cable 23(H)

○○ ● ○ ●○ ●○

2A(H)

○○ ● ○ ●○ ●● ○○ ● ○ ●● ○○

2B(H) Flame length error • Occurs because of a media execution cable error or noise from outside. 2C(H) Media error

○○ ● ● ○○ ○○

30(H) EEPROM error

●○ ● ● ●● ●○ ●○ ● ● ●● ●●

BE(H) BCC error BF(H) Parameter setting error

●● ○ ○ ○○ ○●

※ to ●● ● ● ●● ●●

Check the communication • After converting into octal, the lower two digits represent the slave station number of the current cable and slave module ※ FF(H) error. (Ex. 01(H) = 301(8) = slave station 01)

Overflow of receiving buffer. Occurs when the upper CPU processing is delayed. Check the communication

Check the communication cable Replace the JW-20CM Check the parameter contents.

C1(H) Communication error to

● : ON, ○ : OFF

Remarks • Error codes “23” and “2A(H)” may occur when applying power. This is not an error. • To check the communication cable, remove both connectors and short the connector terminals at one end. Then measure the conductivity using a tester. • Check the parameter and switch settings for all stations. If the settings are correct, replace the JW-20CM or JW-20RS.

8·47

8

Page 86

② JW-20RS

JW–20RS COMM○ SD○ RD○ CD○ LT○ TEST○ ERROR○ FAULT○

○S0 ○S1 ○S2 ○S3 ○S4 ○S5 ○S6 ○S7

Indication lamp

8

Name

Operation

Recovery

COMM

Lights while the remote I/O is operating

--------------------------------------------------

SD

Flickers while sending data

--------------------------------------------------

RD

Flickers while receiving data

--------------------------------------------------

CD

Flickers while detecting a carrier

--------------------------------------------------

LT

Lights when the termination resistance switches turned ON

--------------------------------------------------

TEST

Lights while testing

--------------------------------------------------

ERROR

· Check disconnection of communication cable Lights while an error is detected (Indicate · Check settings of switches error code by S0 to S7 LEDs) · Check settings of parameter · Check power supply voltage.

FAULT

Lights when the watchdog timer is time up (JW-20RS is faulty)

Replace the JW-20RS

S0 to S7

Indicates error codes by hexadecimal when an error is occurred

See the next page

8·48

Page 87

(Error code) LED name S7 6 5 4 3 2 1 S0

Error code (HEX)

○○ ○ ○ ○○ ○●

01(H) ROM error, upper CPU

○○ ○ ○ ○○ ●○

02(H) RAM error, upper CPU

○○ ○ ○ ○○ ●●

03(H) 2 port RAM error against PC, upper CPU

○○ ○ ○ ○● ○○

04(H) 2 port RAM error against communication CPU, upper CPU

○○ ○ ● ○○ ○●

11(H) ROM error, communication CPU

○○ ○ ● ○○ ●●

13(H) RAM error, communication CPU 18(H) Communication LSI error, communication CPU

Cause

Measure

Replace the JW-20RS

○○ ● ○ ○○ ○●

20(H) More than one token detected 21(H) Doubled address detected

• Check the communication cable • Check for doubled allocation of slave station number • Replace the JW-20RS

○○ ● ○ ○○ ●○

22(H) Fault of sending section

Replace the JW-20RS

○○ ● ○ ○○ ●●

23(H) Token does not return within the rated interval

○○ ● ○ ●○ ●○

2A(H)

○○ ● ○ ●○ ●●

2B(H) Flame length error • Occurs because of a media execution cable

○○ ● ○ ●● ○○

2C(H) Media error

○○ ● ○ ●● ●○

2E(H)

○○ ● ● ○○ ○○

30(H) EEPROM error

●○ ○ ● ●● ●○

90(H) I/O bus error

●○ ○ ○ ○○ ○●

91(H) I/O signal error

●○ ○ ● ○○ ●○

92(H) Mismatch number of I/O points

○○ ○ ● ●○ ○○ ○○ ● ○ ○○ ○○

• Check the communication cable • Replace the JW-20RS

Overflow of receiving buffer. Occurs when the upper CPU processing is delayed. Check the communication error or noise from outside.

Synchronization between master and slave • Reinput the power station is deviated

●○ ○ ● ○○ ●●

93(H) Interrupted data from master station

●○ ○ ● ○● ○○

94(H) Defected power failure at I/O processing

• Decrease load of slave station • Check the communication cable • Replace the JW-20RS • Check I/O module, option cables

8 Check the communication cable and master module Check power supply Check master station PC,

●○ ○ ● ○● ○●

95(H) Master station PC error

• master module, or communication cable

●○ ○ ● ●● ●○

9E(H) BCC error

●○ ○ ● ●● ●●

9F(H) Parameter setting error

Check parameter contents

● : ON, ○ : OFF

Remarks • Error codes “23” and “2A(H)” may occur when applying power. This is not an error. • To check the communication cable, remove both connectors and short the connector terminals at one end. Then measure the conductivity using a tester. • Check the parameter and switch settings for all stations. If the settings are correct, replace the JW-20CM or JW-20RS.

8·49

Page 88

(I/O error code of JW model) LED name 80 40 20 10 8 4 2 1

Error code (HEX)

● ○ ○ ● ○ ● ● ● 97(H)

Cause

Measure

I/O table error

Register I/O table Replace the JW-20RS

● ○ ○ ● ● ○ ○ ○ 98(H) Input data parity error

Replace basic rack panel,

● ○ ○ ● ● ○ ○ ● 99(H) Output data error extension cable, I/O

● ○ ○ ● ● ○ ● ○ 9A(H) I/O table registration error module, or register I/O

● ○ ○ ● ● ○ ● ● 9B(H) Special I/O module error ● ○ ○ ● ● ● ○ ○ 9C(H) Blown fuse table. Replace the fuse

• When error numbers 98 through 9C(H) occur, the module will store “rack No.” and “slot No.” in the parameter address 005000(8) in the JW-20RS. Parameter address D7 D6 D5 D4 D3 D2 D1 D0

005000(8)

Rack No.

Slot No.

When more than one module has and error, the lowest “rack No.” and “slot No.” will be stored. • A special I/O module error (9B(H)) can be detected by the JW-2DA/8AD/11DU/12DU/12PM. When the JW-2DA/12PM detects this error, you can also assume that there is a problem in the 24 V power supply. • A fuse blown error (9C(H)) can be detected by JW-12S/13S/32S/33S/35S. If the error cannot be eliminated after replacing the module in which the error occurred, check the modules in the JW-20RS and then in the rack panel.

8

③ PC body and JW-20CM, JW-20RS The operating status of the remote master station and slave stations will vary according to the operation, stop, error, and power failure conditions in the PC as follows. For output hold switch in detail, see page 8·15 ●: Light ON, ×: Blinks, No mark: Lights OFF PC body operational condition

Power supply module

Indicator Halt Power output lamp Operating Error HALT POWER RUN FAULT

Operating at normal Close Stop at normal Open Error Open Remote master Open station error

PC body operational condition

PC body

System memory #170 to COMM SD RD CD ERROR TEST FAULT S0 to S7 #177

Flag relay

●

●

ON ON Not fixed

●

●

Not fixed

●

●

●

×

Power supply module Halt Power output lamp HALT POWER

Operating at normal Close Open Stop at normal Open Error Remote master Open station error PC power in OFF Open

JW-20CM Indication lamps

Hold Hold Hold

●

× × ×

●

× × ×

●

× × ×

Hold

●

JW-20RS Indication lamps

Output hold switch “HOLD”

Output hold switch COMM SD RD CD ERROR TEST FAULT S0 to S7 “RST”

●

− Reset Reset

●

Reset

●

Reset

●

●

Condition of output module

− Hold Reset

●

●

●

× × ×

●

※

× × ×

●

●

Error code

Reset

Not fixed

●

●

Error code

Reset

Not Fixed

●

●

Error code

× × ×

※ When the JW-20RS fault lamp is lit and no error code is displayed, it might be the case that the PC has stopped operation (in the program mode).

8·50