Manual · Sharp
SHARP Programmable Controller New Satellite W series: Network module JW-20CM, Remote I/O slave module JW-20RS User's Manual
Manual230 pagesPDF 2.5 MB
User's manual for the Sharp JW-20CM network module and JW-20RS remote I/O slave module for Sharp programmable controllers.
Filed with · 3 models
Also filed with these models on the old site
Summary
What is in it
Sharp's user's manual for the JW-20CM network module and JW-20RS remote I/O slave module of the New Satellite W series programmable controllers. It explains the three network functions (remote I/O, data link and computer link), names each part, and covers installation, cable processing and crimping, wiring including the power supply module, switch and parameter settings, communication timing, errors and their treatment, support tools, specifications and parameter and memory tables.
Its parts
- Outline
- Safety Precautions
- System Configuration
- Name and Function of Each Part
- Installation
- Processing of Cables
- Wiring
- Remote I/O
- Data Link
- Computer link
- Support Tools
- Specifications
From the manual
Key facts from this manual
Each line names its page in the PDF.
User's manual (version 2.2, October 1997) for the Sharp New Satellite W series network module JW-20CM and remote I/O slave module JW-20RS. It covers those two modules, not the ZW-1PU, ZW-32IO2 or ZW-32S2T the site files it under. It explains the lamps and switches, installation, wiring, remote I/O, data link and computer link setup, error codes and specifications.
- What it is
- JW-20CM network module and JW-20RS remote I/O slave module for Sharp programmable controllers p. 1
- Compatible PCs
- W70H/100H, JW50/70/100 and JW50H/70H/100H p. 9
- Network size
- Data link up to 64 stations; remote I/O up to 63 slave stations; 1 km total cable p. 13
- Remote I/O points
- 4096 points max. across up to 63 slave stations p. 200
- Transmission
- Token passing at 1.25 Mbit/s, bus network p. 199
- Connector
- BNC receptacle (jack) on the module, BNC plug on the line p. 199
- Cable
- 5C-2V coaxial cable, 75 ohm impedance p. 199
- Power draw
- JW-20CM 465 mA at 5 VDC; JW-20RS 600 mA at 5 VDC p. 198, 201
- Weight
- JW-20CM approx. 450 g; JW-20RS approx. 570 g p. 198, 201
- Operating temperature
- 0 to +55 C (storage -20 to +70 C), 35 to 90% RH without condensation p. 198
- Station numbers
- Set by switches, 00 to 77 (octal) p. 202
- JW-20RS rack panels
- ZW-08BU, ZW-04KB, ZW-02KB for ZW I/O; JW-4BU, JW-6BU, JW-8BU, JW-13BU for JW I/O p. 21
- Computer link
- 64 stations max., 1024 bytes max. per packet p. 200
- Error display
- Error codes shown in hexadecimal on the S0 to S7 lamps p. 84
What this manual walks you through
- Installing the option module cable on the basic rack panel p. 18
- Choosing a basic rack panel for the JW-20RS p. 21
- Wiring the JW-1PU and JW-2PU power supply modules p. 37, 38
- How a slave station behaves on a power interruption p. 45
- Finding the cause of an error from the lamp error codes p. 84, 85, 86, 87, 88
- Monitoring communication with the flag area p. 89
- Maintenance and wiring checklist p. 202
Good to know
- Applying 200 V with the clip left on the 100 V side may damage the power supply module. p. 37
- Error codes 23 and 2A may appear when power is applied; the manual says this is not an error. p. 85
- With JW model I/O, the JW-20RS output hold switch must be set to HOLD. p. 17
- With JW model I/O, at most two basic rack panels per slave module, and the JW-1EA/JW-2EA expansion adapter cannot be used. p. 21
- Branch (drop) cables must stay within 400 mm and the total length under 1 km. p. 202
Questions this manual answers
Which Sharp PLCs can use the JW-20CM?
The W70H/100H, JW50/70/100 and JW50H/70H/100H. p. 9
What cable does the JW-20CM network use?
5C-2V coaxial cable with 75 ohm impedance and BNC connectors, up to 1 km in total. p. 199
How many JW-20RS remote I/O slaves can one JW-20CM control?
Up to 63 slave stations. p. 9
What does the FAULT lamp on the JW-20CM mean?
The watchdog timer has timed out and the module is faulty; the manual says to replace the JW-20CM. p. 84
What is JW-20RS error code 9C?
A blown fuse in a JW model I/O module; the manual says to replace the fuse. p. 88
Contents
Chapters and sections
Each line opens the PDF at its page.
- Safety Precautions3
- Chapter 1: Outline9
- Chapter 2 : Safety Precautions10
- Chapter 3 : System Configuration13
- Chapter 4 : Name and Function of Each Part14
- Chapter 5 : Installation18
- Chapter 6 : Processing of Cables24
- Chapter 7 : Wiring30
- 7-1 Cable trunk and branch lines30
- 7-2 Relaying of trunk cables30
- 7-3 Cable wiring procedure in control panel31
- 7-4 Waterproof and insulation processing of connectors33
- 7-5 Wiring of cables at outside control panels34
- 7-6 Check after wiring34
- 7-7 Wiring method for adding a communication station35
- 7-8 Wiring to power supply module37
- Chapter 8 : Remote I/O39
- Chapter 9 : Data Link99
The whole text · 27 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Safety Precautions1-6
- Pages 7 to 97-9
- Chapter 2: Safety Precautions10-12
- Pages 13 to 1713-17
- Chapter 5: Installation18-23
- Chapter 6: Processing of Cables24-29
- Chapter 7: Wiring30-38
- Chapter 8: Remote I/O, pages 39 to 4839-48
- Chapter 8: Remote I/O, pages 49 to 5849-58
- Chapter 8: Remote I/O, pages 59 to 6859-68
- Chapter 8: Remote I/O, pages 69 to 7869-78
- Chapter 8: Remote I/O, pages 79 to 8879-88
- Chapter 8: Remote I/O, pages 89 to 9889-98
- Chapter 9: Data Link, pages 99 to 10899-108
- Chapter 9: Data Link, pages 109 to 118109-118
- Chapter 9: Data Link, pages 119 to 128119-128
- Chapter 9: Data Link, pages 129 to 138129-138
- Chapter 9: Data Link, pages 139 to 148139-148
- Chapter 9: Data Link, pages 149 to 158149-158
- Chapter 9: Data Link, pages 159 to 168159-168
- Chapter 10: Computer link, pages 169 to 178169-178
- Chapter 10: Computer link, pages 179 to 187179-187
- Chapter 11: Suuport Tools188-197
- Chapter 12: Specifications198-201
- Chapter 13: Appendix, pages 202 to 211202-211
- Chapter 13: Appendix, pages 212 to 221212-221
- Chapter 13: Appendix, pages 222 to 230222-230
The file