Page 198

Chapter 12 Specifications 12-1 JW-20CM (1) General specifications Item

Specifications

Storage temperature

– 20 to + 70° C

Ambient temperature

0 to + 55° C

Ambient humidity

35 to 90%RH (without moisture condensation)

Vibration resistance

JIS-C-0911 equivalent (X,Y, Z, 2 hours in each)

Shock resistance

JIS-C-0911 equivalent

Internal power consumption

465 mA (5VDC)

Weight

Approx. 450g

Accessories

One instruction manual , One setting label

[Outline dimension drawings] (Unit : mm) JW-20CM SO S1 S2 S3 S4 S5 S6 S7

250

COMM SD RD CD LT TEST ERROR FAULT

MODE STA.NO ×10 ×1 LT (ON) →

12

LG (ON) →

LINK FUNCTION STATION NO.

33.5

105

12·1

Page 199

(2) Communication specifications Item Communication method Transmission rate Transmission format Coding method Check method Sync method Modulation method Communication network system Connectors

Transmission line

Specification Token/passing 1.25M bits/s JIS X-5014 high level data link control procedure (HDLC) frame configuration compatible NRZI (Non Return To Zero Inverted) CRC Bit synchronous Continuous frequency phase modulation (FSK) Bus type Module side: BNC receptacle (jack) Line side: BNC plug Coaxial cable: 5C-2V (JIS · C-3501) Characteristics impedance: 75 ohm Total cable distance: 1 km max.

12

12·2

Page 200

(3) Specifications of each function ① Specifications of remote I/O slave station Item

Specification

No. of remote I/O slave station 63 sets max. Total no. of remote I/O points

4096 points max. Per station 64 points : Total of 63 stations 4032 points

Fix allocation

Per station 128 points : Total of 32 stations 4096 points

No. of remote I/O points

Synchronous method with PC operation

Manual allocation

Per station 8 to 1024 points : Total of 4096 points

Operation synchronous

Communicates synchronously with the PC's I/O processing cycle.

Operation asynchronous

Communicates separate with the PC's I/O processing cycle.

② Data link specifications Item No. of data link stations ZW-PC Link area JW-PC Total no. of link points

Specification Relay link

Register link

64 sets max. File 0 (000000 to 005777(8)) File 0 (000000 to 015777(8)) File 1 to 7 (000000 to 177777(8)) File 0 (000000 to 007777(8)) 2048 points max. (256 bytes)

2048 bytes max.

2048 points max. Total no. of Standard function (256 bytes) sending/receiving points per slave Memory capacity 512 points max. station save function (64 bytes) Communication mode

2048 bytes max. 512 bytes max.

N:M communication

12

③ Computer link specifications

Item

Specification

No. of link stations

64 sets max.

Communication data size

1024 bytes max./packet *

Communication control

According to the host computer command

Control contents

Read/write of data memory Read/write of program memory PC control

* The amount of data attributed to the command, or response. The term "packet" refers to the value for each station.

12·3

Page 201

12-2 JW-20RS (1) General specifications Item

Specifications

Storage temperature

– 20 to + 70° C

Ambient temperature

0 to + 55° C

Ambient humidity

35 to 90%RH (without moisture condensation)

Vibration resistance

JIS-C-0911 equivalent (X,Y, Z , 2 hours in each)

Shock resistance

JIS-C-0911 equivalent

Internal power consumption

600 mA (5VDC)

Weight

Approx. 570g

[Outline dimension drawings] (Unit : mm) ZW-20RS SO S1 S2 S3 S4 S5 S6 S7

250

COMM SD RD CD LT TEST ERROR FAULT

MODE STA.NO ×10 ×1 LT (ON) → LG (ON) →

STATION NO.

12 33.5

105

(2) Communication specifications Communication specifications is same as JW-20CM. (See page 12·2)