The text of a manual · part 3 of 27
SHARP Programmable Controller New Satellite W series: Network module JW-20CM, Remote I/O slave module JW-20RS User's Manual: Chapter 2: Safety Precautions
Pages 10 to 12 of 230, from SHARP Programmable Controller New Satellite W series: Network module JW-20CM, Remote I/O slave module JW-20RS User's Manual
The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Sharp ZW-1PU, Sharp ZW-32IO2 and Sharp ZW-32S2T
Page 10
Chapter 2 Safety Precautions 2-1 Installation ● Do not install or store the JW-20CM in the following conditions. • Direct sunlight • Ambient temperature exceeding the range of 0 to 55 ˚C (Storage temperature : -20 to 70 ˚C) • The relative humidity exceeding the range of 35 to 90%. • Sudden temperature changes which may cause condensation. • Corrosive or inflammable gas • Vibration or hard jolts ● Prior to installing or detaching the JW-20CM, make sure to turn OFF the power supply to the PCs. ● All screws must be tightened firmly.
2-2 Wiring ● Make sure to use only the recommended types (see page 6 · 1) for cables, connectors, and crimping tools. ● When using connectors for branch or joint lines, provide jackets to protect connectors. (When a connector touches with an external enclosure or the like, a communication error may occur.)
“T” jacket (insulation cover) “L” jacket (insulation cover)
● Do not connect the ground terminal of the power supply module together with other equipment’s ground lines. Make sure to provide class-3 grounding. When the JW-20CM is used without connecting a class-3 grounding, malfunctions by noise may occur. ● Communication cables should be arranged as far from any high voltage lines and strong power lines as possible. Do not lay the communication cable parallel or proximate to these lines.
2·1
2
Page 11
● Communication cables should be laid from the master station to the slave station one by one. Multiple wiring from one point or wiring without terminators may cause communication errors.
Joint using a connector
2
● Arrange total cable length within 1 km. ● Arrange branch cable line from a trunk within 400 mm. ● Prior to any electric welding around the JW-20CM, take out the coaxial cable from the JW-20CM. While the coaxial cable is connected to the JW-20CM, any electric welding nearby the JW-20CM will cause the welding current to enter the JW-20CM and may damage part of its circuit pattern.
JW-20CM
Coaxial cable
JW-20CM
JW-20CM has a fuse element here
Wraparound current
Turn “ON” shield ground
Turn “ON” shield ground FG
FG Rack etc.
Note: In case enough conductivity is not established. Electric welder
2·2
Page 12
2-3 Treatment ● For ventilation, holes are provided in the cabinet to prevent a temperature rise. Do not block the ventilation holes. Good ventilation is necessary. ● Never allow a liquid such as water and chemical solution and a metallic object like a copper wire inside the JW-20CM to avoid a possible hazard. Otherwise, it may be a cause of machine trouble. ● When a trouble or abnormal condition such as overheat, fume, or smoke is met, stop the operation immediately, and call your dealer or our service department.
2-4 Static electricity
2
In extremely dry circumstances, the human body may have excessive static current. This excessive static current may damage parts in the JW-20CM’s PC board. Therefore, prior to accessing the JW20CM, touch your hand to a grounded piece of metal to discharge the static current in your body.
2-5 Maintenance Use a clean, dry cloth when cleaning the JW-20CM. Do not use volatile chemicals such as thinner or alcohol as it may result in deformation and color fading.
2·3