The text of a manual · part 4 of 27
SHARP Programmable Controller New Satellite W series: Network module JW-20CM, Remote I/O slave module JW-20RS User's Manual, pages 13 to 17
Pages 13 to 17 of 230: Chapter 3: System Configuration; Chapter 4: Name and Function of Each Part
The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Sharp ZW-1PU, Sharp ZW-32IO2 and Sharp ZW-32S2T
Page 13
Chapter 3 System Configuration (Example of system configuration)
Personal computer slave station 02(8) Master station 00(8) Slave station 01(8) JW-20CM JW-20CM PC
PC
Slave station JW20 Slave station 77(8) 03(8) JW20H JW-22CM J-board V5 JW30H Network module
Z-335J
3
Data link system (64 stations max., Total extension length: 1km max.) Compuer link system
Slave station 01(8) JW-20RS
Slave station 02(8) ZW-20RS
Slave station 77(8) JW-20RS
Remote I/O system (slave station : 63 stations max., Total extension length: 1km max.)
“PC” indicates W70H/100H, JW50/70/100, and JW50H/70H/100H.
3·1
Page 14
Chapter 4 Name and Function of Each Part 4-1
JW-20CM ①
②
⑦
③
4
④ (View removing the cover on the setting section)
⑤ ⑥
① Indication lamps Lamps light ON/OFF indicates operation condition. Name
JW–20CM COMM○ SD○ RD○ CD○ LT○ TEST○ ERROR○ FAULT○ 30Hn
○S0 ○S1 ○S2 ○S3 ○S4 ○S5 ○S6 ○S7
Operation
COMM
Lights during communicating
SD
Lights when data sending
RD
Lights when data receiving
CD
Lights when detecting carrier
LT
Lights when turning "ON" the termination resistance
TEST
Lights during testing
ERROR
Lights at a communication error
FAULT
Lights at time up of the watchdog timer
S0 to S7
Lights error code when error occurs.
② 30Hn mark (Applied to JW30H) JW-20CMs having 30Hn mark can communicate with JW30H. JW-20CMs having 30H can communicate with conventional modules of JW30H (JW-31CUH/32CUH/ 33CUH). However, when they will communicate with new modules of JW30H (JW-31CUH1/32CUH1/ 33CUH1/33CUH2/33CUH3), they recognizes these new modules as conventional modules.
4·1
Page 15
③ Support tool connection connector Connect a support tool and set parameter etc. ④ Setting switch Set functions of JW-20CM. · MODE switch .... Select functions
67
2 3 2 3
4 5 6
45
7 8
LG (ON)
Set at delivery
1
Remote I/O
0 3 OFF
Function
0
2 9 0 1
4 5 6
0
23
7 8
LT (ON)
4
0
9 0 1
×1
01
STA.NO. ×10
Number
BCD
EF
MODE
8 9A
Set at delivery
4 to F
Data link (standard function) Computer link Data link (memory capacity save function) Computer link Do not set.
ON
· S T A . N O. .... Set station number × 10, × 1 · L T .... Set ON/OFF of termination resistance · L G .... Set shield ground ON/OFF of communication cable
⑤ Communication cable connection connector BNC type receptacle (jack) ⑥ Connector protective cap ⑦ Rating plate
4·2
Page 16
4-2
JW-20RS ①
②
⑦
③
④
4 ⑤ ⑥
① Indication lamps Lamps light ON/OFF indicates operation condition.
JW–20RS COMM○ SD○ RD○ CD○ LT○ TEST○ ERROR○ FAULT○ 30Hn
○S0 ○S1 ○S2 ○S3 ○S4 ○S5 ○S6 ○S7
Name
Operation
COMM
Lights during communicating
SD
Lights when data sending
RD
Lights when data receiving
CD
Lights when detecting carrier
LT
Lights when turning "ON" the termination resistance
TEST
Lights during testing
ERROR
Lights at a communication error
FAULT
Lights at time up of the watchdog timer
S0 to S7
Indicates error code.
② 30Hn mark (Applied to JW30H) JW-20RSs having 30Hn mark can communicate with JW30H. JW-20RSs having 30H can communicate with conventional modules of JW30H (JW-31CUH/32CUH/ 33CUH). However, when they will communicate with new modules of JW30H (JW-31CUH1/32CUH1/ 33CUH1/33CUH2/33CUH3), they recognizes these new modules as conventional modules.
4·3
Page 17
③ Support tool connection connector Connect a support tool and set parameter etc. ④ Setting switch Set functions of JW-20RS. · MODE switch .... Select functions
67
0
23
45
7 8 2 3
7 8 2 3
4 5 6
0
9 0 1
4 5 6
2
9 0 1
LT (ON)
ON
LG (ON)
Output hold switch
0
Do not set.
1
Remote I/O (ZW-I/O)
2
Remote I/O (JW-I/O)
3 to F
OFF
HOLD
Do not set.
· S T A . N O. .... Set station number × 10, × 1 · L T .... Set ON/OFF of termination resistance · L G .... Set shield ground ON/OFF of communication cable
⑤ Communication cable connection connector BNC type receptacle (jack) ⑥ Connector protective cap ⑦ Rating plate ⑧ Output hold switch Set the status of the output module when the JW-20RS stops operation. ※ RST
Output hold switch ⑧
HOLD
4
Function
RST
×1
01
STA.NO. ×10
Number
BCD
EF
MODE
8 9A
Set at delivery
· In case of using ZW-I/O HOLD: Holds operation condition RST: All points is OFF · In case of using JW-I/O Be sure to setting at HOLD.
Keep the switch marked with ※ as the setting at delivery (condition in the figure above).
4·4