Page 30
Chapter 7 Wiring 7-1 Cable trunk and branch lines ① On the illustration of the cable wiring below, a bold line means a trunk and the thin lines branched from the trunk with a “T” shape are called branch lines.
Branch line 400 mm max. Trunk cable
② The length of branch lines branched from the trunk should be within 400 mm.
Branch line
400 mm
Trunk cable
7 ③ Total cable length should be within 1 km.
7-2 Relaying of trunk cables ① To relay trunk cables, use the straight joint (ME-JJ-01). ME-JJ-01
② Relaying of trunk cables should be limited to indispensable cases only. Inadvertent relaying of trunk cables may cause a communication fault such as a weakened signal level due to contact resistance in the junction connector (straight).
Junction
Junction
7·1
Page 31
7-3 Cable wiring procedure in control panel Saddle
JW-20CM
[1] Fixing of the cable In order not to put any force on the cable and the JW-20CM, fasten the cable to an line nearby input of a control panel or a “T” branch point to the JW20CM using saddles etc.
Saddle
[2] Extra length of cable Provide an extra length of the cable of 2 to 3 m inside a control panel for easier processing of the cable end and easier wiring when changing module positions.
[3] Connection to the JW-20CM The connector to the JW-20CM should be turned right to secure locking, not merely inserted.
An extra length of cable of 2 to 3 m
Communication cable connection connector
7
[4] Insulation cover When the connector touches with a high voltage section or external enclosures, communication errors may occur. Make sure to install an insulation cover.
7·2
“T” jacket (insulation cover) “L” jacket (insulation cover)
Page 32
[5] Grounding of power supply module Make sure to connect the GND terminal of the power supply module to a class-3 grounding. • If the power supply module is not grounded, the JW-20CM cannot conduct with the ground after turning “ON” the shield ground switch. In case of AC power supply module (JW-1PU) Power supply module (JW-1PU)
SHORT 200 VAC Input power voltage switching terminal
SHORT 100 VAC
Class-3 grounding
INPUT AC/AC 100V 200V GND HALT OUTPUT
Power input terminal GND (ground) terminal Halt signal output terminal
Detail of the terminal block
7
7·3
Page 33
7-4 Waterproof and insulation processing of connectors In order to prevent water intrusion into the “T” branch connectors and the straight connectors, we recommend to wind a self-adhesive tape and provide waterproof processing for them. For insulation purposes, cover these connectors with jackets. [1] “T” branch connector To wind a self-adhesive tape, cut the tape at about 10 cm each and start winding from position ①. Start winding cut tapes from ② and ③ as well.
②
Self-adhesive tape
①
③ T’s
7
[2] Straight connector To wind the self-adhesive tape, cut the tape at about 15 cm each and start winding from position ① .
Self-adhesive tape ①
Straight
Remarks Prior to adhering the tape, clean the surface of the connectors and stick the adhesive side of the tape on the connector surface. Wind to lightly spread on the connector surface, and overlap with the next wrap to half of the tape width. Wind the tape for each wrap evenly so that the connector metal portion is completely covered with the tape. Be careful not to excessively stretch the tape.
7·4
Page 34
7-5 Wiring of cables at outside control panels ① Do not bundle the coaxial cable (the trunk and branch lines) together with power cables, and separate from power cables at least by 100 mm. Do not put the coaxial cable into a power line wired duct. The best way is to put the communication line in an independent duct. ② Be careful that the coaxial cable does not receive any load by laying under a heavy weight such as other cables. When other cables run in the same duct as the coaxial cable, run the coaxial cable on the top position. ③ Do not run the coaxial cable outdoors as it may cause damage to the JW-20CM due to inductive lightning or atmospheric charge during lightning.
7-6 Check after wiring Check the items below after completion of wiring. Check contents 1
The recommended connector types are used.
2
The connectors are securely locked.
3
The connectors are insulated by T jacket or L jacket.
4
The recommended coaxial cable type is used.
5
Curved radius of the coaxial cables are more than 45 mm.
6
No heavy load is on the coaxial cables. The coaxial cable is not bundled with a power line cable.
7 (Away from power line cables more than 100 mm.) 8
Length of branch lines is shorter than 400 mm.
9
Total length of the cable is less than 1 km. Settings of the termination resistance switch and the shield ground switch are as per
10 the drawings.
7·5
7
Page 35
7-7 Wiring method for adding a communication station [1] Branching method When branching a line for an additional station, be sure to branch from the trunk using a T connector. Never branch from a branch line.
Station number 0 2 (8)
Station number 0 2 (8) Trunk cable
Station number 0 3 (8)
Branch Trunk line cable
Station number 0 6 (8)
Station number 0 3 (8)
Addition
Junction Station number 0 6 (8) Station number 0 2 (8)
Station number 0 3 (8)
Branch line
7
[2] Station number of the additional station Station number of the newly added station should be next largest number from the current largest numbered station. Each station should not be required to be arranged in order of each station’s number.
00(8)
01(8)
03(8)
02(8)
04(8)
05(8)
Addition Sequential number 00(8)
01(8)
02(8)
06(8)
03(8)
04(8) means the termination resistance switch being turned “ON.”
7·6
05(8)
Page 36
[3] Notes When adding a communication station, follow the items below. No. 1 2 3 4 5 6
7
8
Item Branch from the trunk cable. Don’t use the same station number twice. Check the termination resistance switch. Provide extra length for the expansion cable. Do not exceed the 1 km limit for total length of the cable. Change the layout drawing for installation. Do not overlap with any PC’s communication area. Set the parameter memory of the master station and that of the newly added station.
Reason Another branch line from a branch line may not give appropriate communication by reflection wave. The use of the same station number twice may cause communication errors. When the newly added station becomes a termination of the circuit, change the setting of the LT switch. Have enough cable length in order to provide easy wiring. Longer wiring may cause communication error by signal attenuation. Maintain the added work data for future maintenance use. When the communication area or the flag area of the added station overlaps with other addresses in use, communication errors may occur. Without setting the parameter memory of the master station and that of the slave station, the added station cannot communicate.
7·7
7
Page 37
7-8
Wiring to power supply module [1] JW-1PU · Open the terminal block cover, fasten with the screw with torque of less than 12kg·cm. · A maximum of three halt output lines can be connected serial. To use more than three sets, use a relay for interconnection. In case of 100 VAC input In case of 100 VAC input Terminal block cover
1
SHORT 200 VAC
2
SHORT 100 VAC
3
INPUT
4
100 VAC or 200 VAC
5 GND
Terminal block cover
6 7 halt output line
8
DC relay The coil rating must conform to the power supply voltage.
7
In case of using DC output module, connect the AC relay in the halt output line and insert the contact with the emergency stop circuit. In case of 200 VAC input · In case of using 200 VAC, switched to the 200 V side in terminal block of power supply module. · If 200 V is added with the clip connected to the 100 V side, it may damage the power supply module. In case of 100 VAC input
SHORT 200 VAC SHORT 100 VAC 200 VAC input
1 2
7
1A SSR
3 4
8
5
GND
6
Halt output internal circuit
7·8
Page 38
[2] JW-2PU · Open the terminal block cover, fasten with the screw with torque of less than 12kg·cm. · Halt output lines can not be connected serial. To use more than two sets, use a relay for interconnec-tion. Terminal block In case of 24 VDC input cover
1
Do not use.
2 3
INPUT
4
24 VDC
5 GND +
Terminal block cover
6 7
Halt output line
8
DC relay The coil rating must conform to the power supply voltage.
Connect the DC relay in the halt output line and insert the contact with the emergency stop circuit.
Remarks 留 意 点 · Connect without confusing polarities of input power supply and halt output signal. · Wrong polarity connection may damage the power supply module when charged. 7
1A
8
Halt output internal circuit
7·9
7