The text of a manual · part 10 of 27

SHARP Programmable Controller New Satellite W series: Network module JW-20CM, Remote I/O slave module JW-20RS User's Manual: Chapter 8: Remote I/O, pages 59 to 68

Pages 59 to 68 of 230, from SHARP Programmable Controller New Satellite W series: Network module JW-20CM, Remote I/O slave module JW-20RS User's Manual

The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Sharp ZW-1PU, Sharp ZW-32IO2 and Sharp ZW-32S2T

Page 59

[I/O table registration in case of using JW-I/O] 1. In case of not setting dummy I/O Register I/O table based on the installed I/O module. (Set parameter address 001001(8) = 65(H), the procedure B in the flow chart.) However, in case of parameter address of JW-20RS 001002(8) = 00(H) (default setting), the JW-20CM automatically registers I/O table when the power is input and there is no need to register I/O table. (Procedure A in the flow chart.) 2. In case of setting dummy I/O Set number of dummy I/O points for each slot and registers I/O table based on this setting and the installed I/O module. (Set parameter address 001001(8) = 64(H), procedure C in the flow chart.) Procedure D in the flow chart is special method to set byte of I/O module for each slot. Normally set I/O module type using steps 1 and 2 above.

Not setting dummy I/O Auto setting the kinds of I/O module

Yes

No (Manual I/O registration) ③

(Auto I/O registration)

Set no. of dummy I/O points

Not setting the kinds of I/O module (auto setting)

[8·25] No D ④

Yes

Set the kinds of I/O module

C

B

[8·26]

⑤

⑤

⑤

Registration of I/O table (parameter address 001001(8) = 65(H))

Registration of I/O table (parameter address 001001(8) = 64(H))

Registration of I/O table (parameter address 001001(8) = 64 (H))

[8·27]

⑦ Set max. racks, slot number

[8·28]

① to ⑧ are applied to page 8·24 to 29.

⑧ Set remote I/O top address

[8·29]

8·21

8

Page 60

Turn “ON” the power of slave module

Connect support tools · Connect a support tool with the slave module JW-20RS and prepare the setting parameter. <Usable support tools> JW-13PG/12PG JW-50SP JW-50PG, Z-100LP2S • For operation of each support tool, see the instruction manual attached. The following describes an example of JW-13PG’s key operation. Stop operation of remote I/O

[HEX (hexadecimal), byte]

· Setting of the parameter is only available when the operation of the JW-20RS is stopped. · Write “00(H)” to parameter address 003777(8) and stop operation of the JW-20RS. (Operation example of JW-13PG)

Display the contents of ) parameter ( Parameter setting address 007777 by

8 hexadecimal.

Screen display of JW-13PG

( Write 00 . ) (H)

07775 07776 I PARAM. >07777

HEX HEX

00 1F

HEX

00

Reference Function of JW-13PG • key: Changeover unit of figures

→HEX (hexadecimal) → OCT (octal) → DCM (decimal) →Bit pattern • key: Byte display ←→ Changeover word display

· Please set ① to ⑧ of 8·24 and after when using ZW-I/O or JW-I/O.

To the next page

Remarks Indicates in [ ] of each item mean as follows: (Example) Stop remote I/O operation [HEX (hexadecimal), bytes] This means to set “stop remote I/O operation” by hexadecimal and byte unit.

8·22

Page 61

From the previous page

Writing to the EEPROM, start operation

[HEX (hexadecimal), byte]

· Write “81(H)” into parameter address 003777(8) and write the set parameter contents into the EEPROM. Then start the slave module. · After starting operation, the setting value changes to “01(H).” Setting value (H)

Contents

00

Stop operation

01

Start operation

80

Writing to the EEPROM, stop operation

81

Writing to the EEPROM, start operation

08

Initialize setting values of parameter addresses

(Operation example of JW-13PG)

Display the contents of address 003777(8)

Screen display of JW-13PG

Write 81(H)

03775 03776 I PARAM. >03777

HEX HEX

00 00

HEX

01

Remarks 8 · Writing time to EEPROM is approximately 0.7 sec. When any error is found for parameter settings, lights the error code 9F(H) by the indication lamp. · Written contents into the EEPROM are automatically written to the RAM of the slave module when turning ON the power of the PC. At reading, the PC checks BCC and compares BCC check code of the parameter memory address (003776(8)). When an error is found, the JW-20RS lights the error code 9E(H) by the indication lamp. · After initialized the parameters, the JW-20RS initializes parameter address 000000 to 003776(8).

8·23

Page 62

"Only when using ZW model I/O module" ① Select "number of I/O byte checking" function

[OCT (Octal), bytes]

(Applied to item ① on pages 8·20 to 22) · Select whether to check or not number of bytes of I/O module used for the remote I/O slave module. Set selection in parameter address 003750(8). If "check" is selected, the I/O module can detect when number of I/O modules is changed by fault or disconnection of the I/O modules. Set value

Contents

00(H)

Do not check

45(H)

Check

Initial value: 00(H) (Do not check)

(To select "check" using JW-13PG)

Display contents of address 003750(8)

Screen display of JW-13PG 03746 03747 I PARAM. >03750

Write 45(H)

HEX HEX

00 00

HEX

45

"Only when using ZW model I/O module" ② Set number of I/O bytes

[DCM (decimal), word]

(Applied to item ② on pages 8·20 to 22)

8

· Set total number of bytes of installed modules when "yes" is selected (address 003750(8) = 45(H)). · If the set number of I/O bytes mismatch with the actual number of bytes of the installed module, the JW-20RS detects as error (error code 92(H)). · Set between 000 to 128 in decimal notation. Address

Contents

003752(8)

Lower bytes

003753(8)

Upper bytes

Initial value: 00(D) for both upper and lower bytes.

Ex.: If one ZW-16N1 (16 points/2 bytes) and one ZW-16S1 (16 points/2 bytes) are installed, (Set 2 bytes + 2 bytes = 4 bytes using the JW-13PG) Screen display of JW-13PG Display the contents of address 003752(8) in decimal notation and words.

03746 03750 I PARAM. >03752

Write data 4

8·24

D D

00000 00037

D

00004

Page 63

"Only when manual I/O registration using the JW model I/O module" ③ Set number of dummy I/O points

[HEX (hexadecimal), bytes]

(Applied to item ③ on pages 8·20 to 22) · Set to allocate addresses (dummy I/Os) on vacant slots in parameter address 000000 to 000017(8). · Set two slots with one byte of parameter address.

Parameter address(8) 000000

Set to 0

Set to 0

Parameter address(8) 000010

000001

Slot 3

Slot 2

000002

Slot 5

000003

Rack No. 0 7

6

5

4

3

2

1

0

Rack No. 1 7

6

5

4

3

2

1

Slot 1

Slot 0

000011

Slot 3

Slot 2

Slot 4

000012

Slot 5

Slot 4

Slot 7

Slot 6

000013

Slot 7

Slot 6

000004

Slot 9

Slot 8

000014

Slot 9

Slot 8

000005

Slot B

Slot A

000015

Slot B

Slot A

000006

Slot D

Slot C

000016

Slot D

Slot B

000007

Slot F

Slot E

000017

Slot F

Slot E

Set value(H)

Contnets

Set value(H)

Contnets

0

0

No dummy I/O point

8

128 points of dummy I/O (16 bytes)

1

16 points of dummy I/O (2 bytes)

9

144 points of dummy I/O (18 bytes)

2

32 points of dummy I/O (4 bytes)

A

160 points of dummy I/O (20 bytes)

3

48 points of dummy I/O (6 bytes)

B

176 points of dummy I/O (22 bytes)

4

64 points of dummy I/O (8 bytes)

C

192 points of dummy I/O (24 bytes)

5

80 points of dummy I/O (10 bytes)

D

208 points of dummy I/O (26 bytes)

6

96 points of dummy I/O (12 bytes)

E

224 points of dummy I/O (28 bytes)

7

112 points of dummy I/O (14 bytes)

F

240 points of dummy I/O (30 bytes)

Ex.: Set 32 points (4 bytes) of dummy I/O in the following vacant slots using JW-13PG.

JW-20RS JW-12N JW-12N Vacant slot JW-12S JW-12S Not used Not used Not used

Power supply module

0 1 2 3 4 5 6 7 8 9 ←Slot No.

↑ Set number of dummy I/Os

(

Display contents of address 000002(8)

)

(Write 02(H))

←Rack No. 0

Screen display of JW-13PG 00000 00001 I PARAM. >00002

8·25

HEX HEX

00 00

HEX

02

8

Page 64

"Only when manual I/O registration using JW model I/O modules" ④ Set type of I/O module

[HEX (hexadecimal), byte]

(Applied to item ④ on pages 8·20 to 22) · Set types of installed I/O module in each slot and number of dummy I/O points set for vacant slot into parameter address 000100 to 000137(8). · Set one slot with one byte of parameter address.

8

Parameter address (8)

Contents in rack No. 0

Parameter address (8)

Contents in rack No. 1

Set value(H)

000100

Set to 00(H)

000120

Slot 0

91

JW-12S, JW-13S

000101

Set to 00(H)

000121

Slot 1

92

JW-32S JW-32SC, JW-33S JW-34S, JW-35S

94

JW-62SC

00 to 0F

Vacant slot 00 ↑ Lower bits are number of dummy I/O points

A1

JW-11N, JW-12N JW-13N

A2

JW-31N, JW-32N JW-34N, JW-34NC

A4

JW-64NC

D1

JW-2DA, JW-8AD JW-31LM

F1

JW-2HC, JW-11DU JW-12DU

000102

Slot 2

000122

Slot 2

000103

Slot 3

000123

Slot 3

000104

Slot 4

000124

Slot 4

000105

Slot 5

000125

Slot 5

000106

Slot 6

000126

Slot 6

000107

Slot 7

000127

Slot 7

000110

Slot 8

000130

Slot 8

000111

Slot 9

000131

Slot 9

000112

Slot A

000132

Slot A

000113

Slot B

000133

Slot B

000114

Slot C

000134

Slot C

000115

Slot D

000135

Slot D

000116

Slot E

000136

Slot E

000117

Slot F

000137

Slot F

Model name of the installed module

Set 00(H) for a slot having power supply module or slave module JW-20RS. Ex.: Set the I/O module in the previous page using the JW-13PG

Display contents of address 000102(8)

Write A1(H) in address 000103(8)

Write A1(H)

(

Write 02(H) in address 000104(8)

)

Write 91(H) in address 000105(8)

Screen display of JW-13PG Write 91(H) in address 000106(H)

00104 00105 I PARAM. >00106

HEX HEX

02 91

HEX

91

8·26

Page 65

"Only when using JW model I/O modules" ⑤ Registration of I/O table

[HEX (hexadecimal), byte]

(Applied to item ⑤ on pages 8·20 to 22) · Set in parameter address 001001(8) Set value(H)

Contents

60

Set both number of dummy I/O points and type of I/O module with operation described in page 8·25 and 26

64

Manual setting number of dummy I/O points and automaticl setting of I/O module type.

Number of dummy I/O points is 00 (number of dummy I/O points set by operatoin in page 8· 25 will be 00), and set I/O module type automatically. When setting is complete normally, set value will be 00(H). · When manual I/O table registration is selected, the JW-20RS automatically registers I/O address table for each rack slot into parameter address 004000 to 004077(8). It also stores sum check code of parameter address 000000 to 000277(8) into parameter address 000300(8). 65

Ex.: Set number of dummy I/O points and I/O module type set in page 8·25 and 26 using the JW13PG. Screen display of JW-13PG

Display contents of address 001001(8)

Write 60(H)

00777 01000 I PARAM. >01001

HEX HEX

00 00

HEX

60

8

"Only when using JW model I/O module" ⑥ Prohibit automatic registration of I/O table at inputting power

[HEX (hexadecimal), bytes]

(Applied to item ⑥ on pages 8·20 to 22) · Set 03(H) in parameter address 001002(H) to prohibit "automatic registration of I/O table" during inputting power to the slave station module. (In case of setting using the JW-13PG) Screen display of JW-13PG

(

Write 03(H) in address 001002(8)

01000 01001 I PARAM. >01002

)

HEX HEX

00 60

HEX

03

Note: If 00(H) is set to parameter address 001002(8), the JW-20RS automatically register I/O at inputting power. If the power is reinput when an I/O module is faulty, the I/O address will automatically be registered. If the I/O module is faulty, reinput of power may register wrong I/O address. In this case use this function to prohibit wrong registration.

8·27

Page 66

"Only when using JW model I/O module" ⑦ Set maximum rack and slot numbers

[HEX (hexadecimal), bytes]

(Applied to item ⑦ on pages 8·20 to 22) · Set maximum rack and slot numbers in parameter address 001000(8) and shorten I/O processing time. · If this is left 00(H) (default value), the JW-20RS processes from rack No. 1 and slot number F so that it takes approximately 8 ms. · Set rack number in upper 4 bits and slot number in lower 4 bits. 7 001000(8)

6

5

Rack No.

4

3

2

1

0

Slot No.

· Maximum amount of usable racks is 2 and a rack having slave module JW-20RS is rack No. 0. Even the rack panel JW-13BU is used, number of slots will be up to "C."

Slot number

0 1 2 3 4 5 6 7 8 9 A B C

Rack 1

Slot number

8

0 1 2 3 4 5 6 7 8 9 A B C

Rack 0

Slave module (JW-20RS) Ex.: Set the configuration in page 8·25 (rack No. 0 and slot No. 6) using the JW-13PG. Screen display of JW-13PG Display contents of address 001000(8)

(Write 06(H))

8·28

00776 00777 I PARAM. >01000

HEX HEX

00 00

HEX

06

Page 67

"Only when using JW model I/O module" ⑧ Setting remote I/O top address

[OCT (octal), word]

(Applied to item ⑧ on pages 8·20 to 22) · In order to light a search module (SU) lamp, set remote I/O top address of each slave station which are allocated in the master station using file address into parameter address 001004 and 001005(8). Display on the JW-13PG 001000(8)

Lower bits

001000(8)

Upper bits

01000 01002 I PARAM. >01004

0 0

000006 000003

0

000200

(When to set file address 000200(コ0200) using the JW-13PG)

Display contents of address 00104(8)

(Octal) ( Word display )

Write file address 000200(8)

Remarks · Though input output relays, auxiliary relays etc. of the PC are allocated their byte addresses for each item, allocate the file address which are allocated throughout the memory register range.

File address 000000

Byte address コ0000 Input/output relays

000377 000400

Auxiliary relay

000677 000700 000777 001000

Latch relay

コ0377 コ0400 コ0677 コ0700 コ0777 コ1000

8

General purpose relay コ1577

001577

[Operation method of I/O search (slave station): In case of JW-13PG] Connect the JW-13PG to the slave module JW-20RS in which an I/O shall be searched. · Assign byte address シフト SHIFT

D

3

Select I/O search mode

B

A

1

0

,

Set byte address in octal

SET 8 RESET

Select byte address assignment

9

(Light)

Continous search

(Light OFF)

· Assign rack number and slot number シフト SHIFT

D

3

Select I/O search mode

B

B

1

1

Set rack number in octal

Select rack and slot No. assignment

,

Set slot number in hexadecimal SET 8 RESET 9

8·29

(Light)

,

Continous search

(Light OFF)

,

,

Page 68

(4) Parameter setting of master module (JW-20CM) Set the following parameter address after setting switch. Setting item varies with using PC (JW model or ZW model). O: Necessity for setting Item

Set remote I/O operation mode

Set number of connected slave stations Set remote I/O top address Enter the remote I/O top address of slave station 02 to 77 Enter the number of slave I/O points Enter the number of I/O bytes for each slave station Set blank between stations

8

Enter I/O type for each slave station Enter the data register address of the special I/O mode Set top address of flag area Writing to the EEPROM, start operation/stop setting

Initial value (H)

Setting contents

000000

000001

Address (8)

000002 000003 000004 to 000177 000200 000201 to 000277 000301 to 000376 000400 to 000407 000600 to 000777 003764 to 003767

003777

JW-PC

ZW-PC

Fixed

Manual

Fixed

Manual

See page

00

001(8): Fixed allocation, asynchronous, error mode 1 002(8): Fixed allocation, asynchronous, error mode 2 004(8): Fixed allocation, synchronous, error mode 0 005(8): Fixed allocation, synchronous, error mode 1 006(8): Fixed allocation, synchronous, error mode 2 011(8): Manual allocation, asynchronous, error mode 1 012(8): Manual allocation, asynchronous, error mode 2 014(8): Manual allocation, synchronous, error mode 0 015(8): Manual allocation, synchronous, error mode 1 016(8): Manual allocation, synchronous, error mode 2

○

○

○

○

8· 34

00

Set number of connected modules by decimal notation (01 to 63)

○

○

○

○

8· 35

00

Set file address by octal notation

○

○

○

○

8· 35

00

Enter the file address by octal notation

−

○

−

○

8· 40

00

00(H): 64 points (8 bytes), number of slave station; 63 01(H): 128 points (16 bytes), number of slave station; 32

○

−

○

−

8· 38

00

Enter the number of bytes of each slave station in decimal notation (0 to 128)

−

○

−

○

8· 42

00

Enter the number of blank bytes between stations in decimal notation (0 to 255)

○

−

○

−

8· 39

Set each station in bit unit 0: ZW model I/O module 1: JW model I/O module Set using 4 bytes per module (Set slave station number, rack number, slot number, number of data bytes, and register top address.)

○

○

−

−

8· 43

○ ※

○ ※

−

−

8· 44

00

Set file address with octal notation.

○

○

○

○

8· 36

01

00(H) : Stop remote I/O operation 01(H) : Start remote I/O operation 80(H) : Writing to the EEPROM, stop operation 81(H) : Writing to the EEPROM, start operation 08(H) : Initialize the parameter

○

○

○

○

8· 37

FF

00

· If a special I/O module is not set in a slave station, the setting is not required.

8·30