Page 49
From the previous page
Set LT (termination resistance) switch • When a JW-20CM master module is at either end the communication line, make sure to set the termination resistance switch "ON."
LT (ON) LG (ON)
Turn ON the termination resistance switches on these two stations.
Reference: Function of the termination resistance switch If the communication line does not have a termination resistance, the high frequency signal will be reflected at the ends of the cable. These reflected signals can collide with the original communication signals, so that some stations will not be able to communicate normally. The use of termination resistance suppresses reflected signals. If the termination resistance switch on any of the stations in between the end of the cable is turned ON, the station will generate a reflection wave signal or attenuate the original signal and may not communicate normally.
· When the trunk line has a branch in it, turn ON the termination resistance at the station on the trunk cable.
Termination resistance (ON)
Drop cable (branch line should be less than 400 mm)
"T" branch
Trunk cable
· If you use a terminator (termination resistance made by Toko Denshi: ME-75) at the end of a signal cable, turn OFF the termination resistance at the station on the end of the cable.
Terminator
Terminator
Less than 1 km
Terminator: ME-75
To the next page
8·11
8
Page 50
From the previous page LT (ON)
Set LG (shield ground) switch
LG (ON)
· For communication lines, use a coaxial cable. · As coaxial cable is an unbalanced circuit, ground its shield by turning “ON” the shield ground switch.
Turn “ON” shield ground switch
Coaxial cable
Turn “ON” shield ground switch
• Make sure to provide a class-3 grounding for the GND terminal of the power supply module. Without grounding the power supply module, the JW-20CM cannot become conductive with the ground after turning “ON” the shield ground switch. (See page 7·2.) • Prior to any electric welding around the JW-20CM, take out the coaxial cable from the JW-20CM. While the coaxial cable is connected to the JW-20CM, any electric welding nearby the JW-20CM will cause the welding current to the JW-20CM and may damage part of its circuit pattern. JW-20CM
8
Coaxial cable
JW-20CM
JW-20CM has a fuse element here. Wrap around current
Turn “ON” shield ground switch FG
Turn “ON” shield ground switch
Note: Rack etc.
Note: In case enough conductivity is not established. Electric welder
To the next page
8·12
Page 51
From the previous page
Attach label · Attach the remote I/O master station label to this module, make setting “remote I/O master station function” clear. · Write “FIX” on this label. LINK FUNCTION REMOTE I/O MASTER STATION NO. FIX
Switch setting end of master module
8
8·13
Page 52
(2) Switch setting of slave module (JW-20RS) Operation procedure
All slave module in common for setting method In brackets: See page
Start
Power “OFF” master/slave station
8
Set output hold switch
[8·15]
Remove the setting switch cover.
[8·15]
Set MODE (function) switch
[8·15]
Set STA. NO. (station number) switch
[8·16]
Set LT (termination resistance) switch
[8·16]
Set LG (shield ground) switch
[8·17]
Attach label
[8·18]
End
8·14
Page 53
Power “OFF” master/slave station RST
Set output hold switch
※2 HOLD
Output hold switch
· Set this switch whether to "latch" or "turn OFF all points" of output circuits when the slave module JW-20RS stops operation. · In case of using I/O module of JW model, be sure to setting “HOLD”. Switch setting
Contents
In case of using I/O HOLD "Hold" module of ZW model RST※1 "All points OFF"
[
Keep *2 switch above as delivered condition.
]
In case of using I/O HOLD Setting at "hold" module of JW model ※ 1 When the slave module JW-20RS stopped, the halt output turns “open” and output module sets “all points OFF”. (See page 8·50). Remove the setting switch cover of master module JW-20RS. · With your fingertips over the top and bottom of the switch cover, pull the cover towards you to remove it. · Keep the cover saved as it must be installed after switch setting.
8
I/O module of ZW model
2
I/O module of JW model
67
45
1
23
Model of I/O module
01
Setting value
MODE
BCD
EF
· Select the model of I/O module that installed on respective slave module.
8 9A
Set MODE (function) switch
The mode switch is set to “2” at delivery. Positions "3 to F" will be used only by our service man. Do not set the switch to these positions.
· If the master station PC is JW model, it can connect to the slave modules having "ZW model I/O module" and "JW model I/O module" on the same circuit.
To the next page
8·15
Page 54
4 5 6
2 3
×1
7 8
9 0 1
· Set "STA. NO" (station number) in octal notation in sequential numbers from 01 to 77. Be careful that there is no doubled setting or lacked number setting. (Number of connectable slave stations: See page 8·2)
7 8 2 3
STA.NO. ×10
9 0 1
Set STA. NO. (station number) switch
4 5 6
From the previous page
LT (ON)
Set LT (termination resistance) switch • When a JW-20RS slave module is at either end the communication line, make sure to set the termination resistance switch "ON."
LG (ON)
Turn ON the termination resistance switches on these two stations.
8
Reference: Function of the termination resistance switch If the communication line does not have a termination resistance, the high frequency signal will be reflected at the ends of the cable. These reflected signals can collide with the original communication signals, so that some stations will not be able to communicate normally. The use of termination resistance suppresses reflected signals. If the termination resistance switch on any of the stations in between the end of the cable is turned ON, the station will generate a reflection wave signal or attenuate the original signal and may not communicate normally. · When the trunk line has a branch in it, turn ON the termination resistance at the station on the trunk cable.
Termination resistance (ON)
Drop cable (branch line should be less than 400 mm)
"T" branch
Trunk cable
· If you use a terminator (termination resistance made by Toko Denshi: ME-75) at the end of a signal cable, turn OFF the termination resistance at the station on the end of the cable. Terminator
Terminator
Less than 1 km
Terminator: ME-75
To the next page
8·16
Page 55
From the previous page LT (ON)
Set LG (shield ground) switch
LG (ON)
· For communication lines, use a coaxial cable. · As coaxial cable is an unbalanced circuit, ground its shield by turning “ON” the shield ground switch.
Turn “ON” shield ground switch
Coaxial cable
Turn “ON” shield ground switch
• Make sure to provide a class-3 grounding for the GND terminal of the power supply module. Without grounding the power supply module, the JW-20CM cannot become conductive with the ground after turning “ON” the shield ground switch. (See page 7·2.) • Prior to any electric welding around the JW-20CM, take out the coaxial cable from the JW20CM. While the coaxial cable is connected to the JW-20CM, any electric welding nearby the JW-20CM will cause the welding current to the JW-20CM and may damage part of its circuit pattern. JW-20CM
Coaxial cable
JW-20CM
JW-20CM has a fuse element here
Wrap around current
Turn “ON” shield ground
Turn “ON” shield ground FG
Note:
FG Rack etc.
Note: In case enough conductivity is not established. Electric welder
To the next page
8·17
8
Page 56
From the previous page
Write in label · Write “FIX” and “STA. NO.” on label of remote I/O slave station, make setting contents clear.
STATION NO. 01 FIX
Switch setting end of slave module
8
8·18
Page 57
(3) Parameter setting of slave module (JW-20RS) Set the following parameter address after setting switch. Setting item varies with using I/O module (JW model or ZW model). O: Necessity for setting Item
Setting no. of dummy I/O points · Use 1 byte per vacant 2 slots · Set at only manual I/O table registration
Set kinds of I/O module · Use 1 byte per slot · Set at only manual I/O table registration
Address Initial value (8) (H)
000000 to
00
000017
000100 to
00
000137
Set max.racks and slot number
001000
00
Set manual I/O table registration
001001
00
Register automatically or not I/O table at power input. Set remote I/O top address
001004 001005
00
Check no. of I/O bytes
003750
00
003752
00
JW-I/O ZW-I/W See page
○
−
8・25
○
−
8・26
○
−
8・28
○
− 8・27
00 : Auto registration 001002
00 03 : Prohibit the auto registration
Set no. of I/O bytes
Writing to the EEPROM, start operation/stop setting.
Setting contents 0 : No. of dummy I/O points : No points 1 : No. of dummy I/O points : 16 points (2 bytes) 2 : No. of dummy I/O points : 32 points (4 bytes) 3 : No. of dummy I/O points : 48 points (6 bytes) 4 : No. of dummy I/O points : 64 points (8 bytes) 5 : No. of dummy I/O points : 80 points (10 bytes) 6 : No. of dummy I/O points : 96 points (12 bytes) 7 : No. of dummy I/O points : 112 points (14 bytes) 8 : No. of dummy I/O points : 128 points (16 bytes) 9 : No. of dummy I/O points : 144 points (18 bytes) A : No. of dummy I/O points : 160 points (20 bytes) B : No. of dummy I/O points : 176 points (22 bytes) C : No. of dummy I/O points : 192 points (24 bytes) D : No. of dummy I/O points : 208 points (26 bytes) E : No. of dummy I/O points : 224 points (28 bytes) F : No. of dummy I/O points : 240 points (30 bytes) 91 : 16 points output 92 : 32 points output 94 : 64 points output 00 : Vacant slot (lower is dummy I/O points) A1 : 16 points output A2 : 32 points output A4 : 64 points output D1 : Special I/O module F1 : Special I/O module Upper 4 bits : Rack number Lower 4 bits : Slot number 60 : Manual setting for both dummy I/O points and kinds of I/O module 64 : Manual setting for dummy I/O points and auto setting for kinds of I/O module 65 : 00 for dummy I/O points and auto setting for kinds of I/O module 00 : When setting is normal end
003753
00
003777
01
Set file address in octal when only using search module (SU) lamp. 00 : No check the no. of I/O bytes 45 : Check the no. of I/O bytes If "checking number of I/O bytes to be used by the I/O module" function is selected to "not to check" using decimal notation 000 to 128, this setting is not needed. 00 : Stop remote I/O operation 01 : Start remote I/O operation 80 : Writing to the EEPROM, stop operation 81 : Writing to the EEPROM, start operation 08 : Initialize the parameter
○
−
○
−
−
○
−
○
○
○
8・24
· There is no difference of parameter setting between "fixed allocation" and "manual allocation."
8·19
8・29
8・22 8・23
8
Page 58
Operation procedure In brackets : See page Turn “ON” the power of slave station PC
Connect support tools
[8·22]
Stop remote I/O operation [8·22] (parameter address 003777(8) = 00(H)
In case of using ZW-I/O
In case of using ZW-I/O
Use the slave module having set to default condition at delivery (initialized the parameters), and use it as automatic I/O registration function.
No
Yes
A
8 ⑥ Set of prohibit the auto I/O table registration at power “ON” [8·27] (parameter address 001002(8) = 03 (H))
No
No check the no. of I/O bytes
①
①
Set of check no. of I/O bytes (parameter address 003750(8) = 45(H))
Set of check no. of I/O bytes (parameter address 003750(8) = 00(H))
Yes
Not short for I/O processing time
Yes
[8·24]
②
Not use I/O search
Set no. of I/O bytes
Yes
[8·24]
Writing to the EEPROM, start operation (parameter address 003777(8) = 81(H))
End
8·20
No
No