Page 49

From the previous page

Set LT (termination resistance) switch • When a JW-20CM master module is at either end the communication line, make sure to set the termination resistance switch "ON."

LT (ON) LG (ON)

Turn ON the termination resistance switches on these two stations.

Reference: Function of the termination resistance switch If the communication line does not have a termination resistance, the high frequency signal will be reflected at the ends of the cable. These reflected signals can collide with the original communication signals, so that some stations will not be able to communicate normally. The use of termination resistance suppresses reflected signals. If the termination resistance switch on any of the stations in between the end of the cable is turned ON, the station will generate a reflection wave signal or attenuate the original signal and may not communicate normally.

· When the trunk line has a branch in it, turn ON the termination resistance at the station on the trunk cable.

Termination resistance (ON)

Drop cable (branch line should be less than 400 mm)

"T" branch

Trunk cable

· If you use a terminator (termination resistance made by Toko Denshi: ME-75) at the end of a signal cable, turn OFF the termination resistance at the station on the end of the cable.

Terminator

Terminator

Less than 1 km

Terminator: ME-75

To the next page

8·11

8

Page 50

From the previous page LT (ON)

Set LG (shield ground) switch

LG (ON)

· For communication lines, use a coaxial cable. · As coaxial cable is an unbalanced circuit, ground its shield by turning “ON” the shield ground switch.

Turn “ON” shield ground switch

Coaxial cable

Turn “ON” shield ground switch

• Make sure to provide a class-3 grounding for the GND terminal of the power supply module. Without grounding the power supply module, the JW-20CM cannot become conductive with the ground after turning “ON” the shield ground switch. (See page 7·2.) • Prior to any electric welding around the JW-20CM, take out the coaxial cable from the JW-20CM. While the coaxial cable is connected to the JW-20CM, any electric welding nearby the JW-20CM will cause the welding current to the JW-20CM and may damage part of its circuit pattern. JW-20CM

8

Coaxial cable

JW-20CM

JW-20CM has a fuse element here. Wrap around current

Turn “ON” shield ground switch FG

Turn “ON” shield ground switch

Note: Rack etc.

Note: In case enough conductivity is not established. Electric welder

To the next page

8·12

Page 51

From the previous page

Attach label · Attach the remote I/O master station label to this module, make setting “remote I/O master station function” clear. · Write “FIX” on this label. LINK FUNCTION REMOTE I/O MASTER STATION NO. FIX

Switch setting end of master module

8

8·13

Page 52

(2) Switch setting of slave module (JW-20RS) Operation procedure

All slave module in common for setting method In brackets: See page

Start

Power “OFF” master/slave station

8

Set output hold switch

[8·15]

Remove the setting switch cover.

[8·15]

Set MODE (function) switch

[8·15]

Set STA. NO. (station number) switch

[8·16]

Set LT (termination resistance) switch

[8·16]

Set LG (shield ground) switch

[8·17]

Attach label

[8·18]

End

8·14

Page 53

Power “OFF” master/slave station RST

Set output hold switch

※2 HOLD

Output hold switch

· Set this switch whether to "latch" or "turn OFF all points" of output circuits when the slave module JW-20RS stops operation. · In case of using I/O module of JW model, be sure to setting “HOLD”. Switch setting

Contents

In case of using I/O HOLD "Hold" module of ZW model RST※1 "All points OFF"

[

Keep *2 switch above as delivered condition.

]

In case of using I/O HOLD Setting at "hold" module of JW model ※ 1 When the slave module JW-20RS stopped, the halt output turns “open” and output module sets “all points OFF”. (See page 8·50). Remove the setting switch cover of master module JW-20RS. · With your fingertips over the top and bottom of the switch cover, pull the cover towards you to remove it. · Keep the cover saved as it must be installed after switch setting.

8

I/O module of ZW model

2

I/O module of JW model

67

45

1

23

Model of I/O module

01

Setting value

MODE

BCD

EF

· Select the model of I/O module that installed on respective slave module.

8 9A

Set MODE (function) switch

The mode switch is set to “2” at delivery. Positions "3 to F" will be used only by our service man. Do not set the switch to these positions.

· If the master station PC is JW model, it can connect to the slave modules having "ZW model I/O module" and "JW model I/O module" on the same circuit.

To the next page

8·15

Page 54

4 5 6

2 3

×1

7 8

9 0 1

· Set "STA. NO" (station number) in octal notation in sequential numbers from 01 to 77. Be careful that there is no doubled setting or lacked number setting. (Number of connectable slave stations: See page 8·2)

7 8 2 3

STA.NO. ×10

9 0 1

Set STA. NO. (station number) switch

4 5 6

From the previous page

LT (ON)

Set LT (termination resistance) switch • When a JW-20RS slave module is at either end the communication line, make sure to set the termination resistance switch "ON."

LG (ON)

Turn ON the termination resistance switches on these two stations.

8

Reference: Function of the termination resistance switch If the communication line does not have a termination resistance, the high frequency signal will be reflected at the ends of the cable. These reflected signals can collide with the original communication signals, so that some stations will not be able to communicate normally. The use of termination resistance suppresses reflected signals. If the termination resistance switch on any of the stations in between the end of the cable is turned ON, the station will generate a reflection wave signal or attenuate the original signal and may not communicate normally. · When the trunk line has a branch in it, turn ON the termination resistance at the station on the trunk cable.

Termination resistance (ON)

Drop cable (branch line should be less than 400 mm)

"T" branch

Trunk cable

· If you use a terminator (termination resistance made by Toko Denshi: ME-75) at the end of a signal cable, turn OFF the termination resistance at the station on the end of the cable. Terminator

Terminator

Less than 1 km

Terminator: ME-75

To the next page

8·16

Page 55

From the previous page LT (ON)

Set LG (shield ground) switch

LG (ON)

· For communication lines, use a coaxial cable. · As coaxial cable is an unbalanced circuit, ground its shield by turning “ON” the shield ground switch.

Turn “ON” shield ground switch

Coaxial cable

Turn “ON” shield ground switch

• Make sure to provide a class-3 grounding for the GND terminal of the power supply module. Without grounding the power supply module, the JW-20CM cannot become conductive with the ground after turning “ON” the shield ground switch. (See page 7·2.) • Prior to any electric welding around the JW-20CM, take out the coaxial cable from the JW20CM. While the coaxial cable is connected to the JW-20CM, any electric welding nearby the JW-20CM will cause the welding current to the JW-20CM and may damage part of its circuit pattern. JW-20CM

Coaxial cable

JW-20CM

JW-20CM has a fuse element here

Wrap around current

Turn “ON” shield ground

Turn “ON” shield ground FG

Note:

FG Rack etc.

Note: In case enough conductivity is not established. Electric welder

To the next page

8·17

8

Page 56

From the previous page

Write in label · Write “FIX” and “STA. NO.” on label of remote I/O slave station, make setting contents clear.

STATION NO. 01 FIX

Switch setting end of slave module

8

8·18

Page 57

(3) Parameter setting of slave module (JW-20RS) Set the following parameter address after setting switch. Setting item varies with using I/O module (JW model or ZW model). O: Necessity for setting Item

Setting no. of dummy I/O points · Use 1 byte per vacant 2 slots · Set at only manual I/O table registration

Set kinds of I/O module · Use 1 byte per slot · Set at only manual I/O table registration

Address Initial value (8) (H)

000000 to

00

000017

000100 to

00

000137

Set max.racks and slot number

001000

00

Set manual I/O table registration

001001

00

Register automatically or not I/O table at power input. Set remote I/O top address

001004 001005

00

Check no. of I/O bytes

003750

00

003752

00

JW-I/O ZW-I/W See page

○

−

8・25

○

−

8・26

○

−

8・28

○

− 8・27

00 : Auto registration 001002

00 03 : Prohibit the auto registration

Set no. of I/O bytes

Writing to the EEPROM, start operation/stop setting.

Setting contents 0 : No. of dummy I/O points : No points 1 : No. of dummy I/O points : 16 points (2 bytes) 2 : No. of dummy I/O points : 32 points (4 bytes) 3 : No. of dummy I/O points : 48 points (6 bytes) 4 : No. of dummy I/O points : 64 points (8 bytes) 5 : No. of dummy I/O points : 80 points (10 bytes) 6 : No. of dummy I/O points : 96 points (12 bytes) 7 : No. of dummy I/O points : 112 points (14 bytes) 8 : No. of dummy I/O points : 128 points (16 bytes) 9 : No. of dummy I/O points : 144 points (18 bytes) A : No. of dummy I/O points : 160 points (20 bytes) B : No. of dummy I/O points : 176 points (22 bytes) C : No. of dummy I/O points : 192 points (24 bytes) D : No. of dummy I/O points : 208 points (26 bytes) E : No. of dummy I/O points : 224 points (28 bytes) F : No. of dummy I/O points : 240 points (30 bytes) 91 : 16 points output 92 : 32 points output 94 : 64 points output 00 : Vacant slot (lower is dummy I/O points) A1 : 16 points output A2 : 32 points output A4 : 64 points output D1 : Special I/O module F1 : Special I/O module Upper 4 bits : Rack number Lower 4 bits : Slot number 60 : Manual setting for both dummy I/O points and kinds of I/O module 64 : Manual setting for dummy I/O points and auto setting for kinds of I/O module 65 : 00 for dummy I/O points and auto setting for kinds of I/O module 00 : When setting is normal end

003753

00

003777

01

Set file address in octal when only using search module (SU) lamp. 00 : No check the no. of I/O bytes 45 : Check the no. of I/O bytes If "checking number of I/O bytes to be used by the I/O module" function is selected to "not to check" using decimal notation 000 to 128, this setting is not needed. 00 : Stop remote I/O operation 01 : Start remote I/O operation 80 : Writing to the EEPROM, stop operation 81 : Writing to the EEPROM, start operation 08 : Initialize the parameter

○

−

○

−

−

○

−

○

○

○

8・24

· There is no difference of parameter setting between "fixed allocation" and "manual allocation."

8·19

8・29

8・22 8・23

8

Page 58

Operation procedure In brackets : See page Turn “ON” the power of slave station PC

Connect support tools

[8·22]

Stop remote I/O operation [8·22] (parameter address 003777(8) = 00(H)

In case of using ZW-I/O

In case of using ZW-I/O

Use the slave module having set to default condition at delivery (initialized the parameters), and use it as automatic I/O registration function.

No

Yes

A

8 ⑥ Set of prohibit the auto I/O table registration at power “ON” [8·27] (parameter address 001002(8) = 03 (H))

No

No check the no. of I/O bytes

①

①

Set of check no. of I/O bytes (parameter address 003750(8) = 45(H))

Set of check no. of I/O bytes (parameter address 003750(8) = 00(H))

Yes

Not short for I/O processing time

Yes

[8·24]

②

Not use I/O search

Set no. of I/O bytes

Yes

[8·24]

Writing to the EEPROM, start operation (parameter address 003777(8) = 81(H))

End

8·20

No

No