The text of a manual · part 16 of 27
SHARP Programmable Controller New Satellite W series: Network module JW-20CM, Remote I/O slave module JW-20RS User's Manual: Chapter 9: Data Link, pages 119 to 128
Pages 119 to 128 of 230, from SHARP Programmable Controller New Satellite W series: Network module JW-20CM, Remote I/O slave module JW-20RS User's Manual
The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Sharp ZW-1PU, Sharp ZW-32IO2 and Sharp ZW-32S2T
Page 119
From the previous page
Attach label · Attach the data link label to this module, make setting “data link function” clear. · Write “STATION NO.” on this label. In case of master module
In case of slave module
LINK FUNCTION DATA LINK
LINK FUNCTION DATA LINK
STATION NO. PC00
STATION NO. PC01
Switch setting end.
9
9·21
Page 120
9-6
Setting contents of slave station parameters When the JW-20CM is used as a slave station, set the following items for parameters. Initial
Setting item
※1
①
Setting time-out item of SEND/ RECEIVE instruction
007500 to 007577
00
②
Setting PC model of each station in SEND/RECEIVE function
007600 to 007677
91
Select system of each channel in SEND/RECEIVE function V5
007700 to 007703
00
④
Top addresses in communication information storage area when using data memory starting system of SEND/RECEIVE V5 functions
007710 to 007713
⑤
Number of receiving bytes of relay link in memory capacity save function V5
007720 007721
⑥
Number of receiving bytes of register link in memory capacity save function V5
③
※2
⑦
9
⑧ ⑨
⑩
⑪
Top address of relay link area
V5 Top address of register link area
V5 Whether the station number information should be output or not V2
Top address of flag area (communication and PC operation condition monitor flag) Communication error detection interval
Corresponding signs on pages 11·7 and 11·8
Contents
Address(8) value (H)
For using SEND/RECEIVE instruction, set the time out time by decimal. [001 (0.1 sec..) to 255 (25.5 sec.)]
91(H): The PC is JW type and ZW-20CM has JW mark or JW-20CM or JW-22CM 81(H): The PC is ZW type and ZW-20CM has JW mark or JW-20CM. 00/81(H):ZW-20CM without JW mark Select instruction system or data memory starting system in CH0 to CH3
00
Setting by file number and file address. · Setting within communication information storage area (64 bytes) File 0: 000000 to 015777(8) File 1 to 7: 000000 to 177777(8)
00
Set the number of bytes by decimals. (0 to 64) · If 0 is set, the number of bytes will be the same as the number of the sending bytes which is set in the master station h1 to hn
007722 007723
00
Set the number of bytes by decimals. (0 to 512) · If 0 is set, the number of bytes will be the same as the number of the sending bytes which is set in the master station i1 to in
007730 to 007733
00
007734 to 007737
00
007763
00
Store the number of own station in the data memory when setting on 01(H). (storage area of 1 byte follows flag area of 24 bytes, valid when 007767(8) is 80(H))
007764
E0
Lower of file address
Initial value: 01E0(H)
007765
01
Upper of file address
007767(8) (コ0740)
007766
00
File number
007767
80
Flag output (Yes: 80(H) No: 00(H))
007771
00
Settable detection interval with 100 ms pitch
Set by file number and file address. (See page 13·20 and 13·21)
f1 to fn
Set by file number and file address. (See page 13·20 and 13·21)
g1 to gn
↓ e1 to en
00(H): Stop remote I/O operation 01(H): Start remote I/O operation
⑫
Writing to the EEPROM, start operation/stop setting
007777
01
80(H): Writing to the EEPROM, stop operation 81(H): Writing to the EEPROM, start operation 08(H): Initialize the parameter
※ 1 Set only any of JW50/70/100 or JW50/70H/100H is used as PC, and using SEND/RECEIVE instruction. ※2 Set only any of JW50/70/100 or JW50/70H/100H is used as PC, and using the memory capacity save function. ① to ⑫ correspond to numbers in the next page.
9·22
Page 121
In brackets: See page in chapter
When not using memory capacity save function
When not using SEND/RECEIVE function
9 Operation procedure Turn “ON” the power of master station PC
[ 24 ]
Connect support tools
[ 24 ]
Stop PC operation
[ 24 ]
Stop operation of data link (007777(8) =00(H))
[ 24 ]
①
Set time-out time of SEND/RECEIVE instruction
[ 25 ]
②
Set PC model of each station in SEND/RECEIVE function
[ 26 ]
③ V5
Select system of each channel in SEND/RECEIVE function
[ 27 ]
④ V5
Set top address in communication storage area when using data memory starting system of SEND/RECEIVE functions
[ 28 ]
⑤ V5
Set number of receiving bytes of relay link in memory capacity save function
[ 28 ]
⑥ V5 Set number of receiving bytes of register link in memory capacity save function
[ 28 ]
⑦ V5
Set top address of relay link area
[ 29 ]
⑧ V5
Set top address of register link area
[ 29 ]
⑨ V5
Select whether to output station number data
[ 30 ]
⑩
Set top address of flag area
[ 30 ]
⑪
Writing to EEPROM, start operation (007777(8) =81(H))
[ 31 ]
⑫
Start write to EEPROM and operation
[ 32 ]
PC operation
[ 32 ]
End ① to ⑨ correspond to numbers in the previous page.
9·23
9
Page 122
Turn “ON” the power of slave module
Connect support tools · Connect a support tool with the JW-20CM and prepare the setting parameter. <Usable support tools> JW-13PG/12PG JW-50SP JW-50PG, Z-100LP2S • For operation of each support tool, see the instruction manual attached. The following describes an example of JW-13PG’s key operation. Stop PC operation · Turn to program mode (stop PC operation). Setting of parameters is only available when the PC is in program mode. (Operation example of JW-13PG) Stop PC operation Select parameter setting mode. Select initial mode
9
Stop operation of data link
)
(
Parameter setting
[HEX (hexadecimal), byte]
· Setting of the parameter is only available when the operation of the JW-20CM is stopped. · Write “00(H)” to parameter address 007777(8) and stop operation of the JW-20CM. (Operation example of JW-13PG) Screen display of JW-13PG Display the contents of parameter address 007777 by hexadecimal.
( ) Write 00(H).
07775 07776 I PARAM. >07777
HEX HEX
00 00
HEX
00
Reference Function of JW-13PG • key: Changeover unit of figures
→ HEX (hexadecimal) → OCT (octal) → DCM (decimal) → Bit pattern • key: Byte display ←→ Changeover word display
To the next page
9·24
Page 123
From the previous page “When PC is JW model and the SEND/RECEIVE function is used” Set time-out time of SEND/RECEIVE function [DCM (decimal), byte] When the own station uses the SEND/RECEIVE instructions, set the time-out time on each communication target station. Setting range is 001 (0.1 sec.) to 255 (25.5 sec.) by decimal. 00(H) of initial value is 1 second.
(8)
Station number (8)
007500
Station number (8)
Address (8)
Station number (8)
Address
(8)
(8)
Station number (8)
Master station
007520
20
007540
40
007560
60
007501
01
007521
21
007541
41
007561
61
007502
02
007522
22
007542
42
007562
62
007503
03
007523
23
007543
43
007563
63
007504
04
007524
24
007544
44
007564
64
007505
05
007525
25
007545
45
007565
65
007506
06
007526
26
007546
46
007566
66
007507
07
007527
27
007547
47
007567
67
007510
10
007530
30
007550
48
007570
70
007511
11
007531
31
007551
51
007571
71
007512
12
007532
32
007552
52
007572
72
007513
13
007533
33
007553
53
007573
73
007514
14
007534
34
007654
54
007574
74
007515
15
007535
35
007555
55
007575
75
007516
16
007536
36
007556
56
007576
76
007517
17
007537
37
007557
57
007577
77
Address
Address
Initial value: All address 00(H) (1 second) (In case of setting 020(D) (2 sec.) in parameter addresses 007500(8) (master station) and 007501(8) (slave station 01).) アドレス ADRS
7
F
5
A
0
A
0
A
モニタ MNTR
C
A
2
0
C
0
After converting into decimal notation,write the setting value.
Display the contents of address 007500 (8) STEP (+)
2
書 込 ENT
Screen display of JW-13PG Write setting value in address 007501 (8)
07477 07500 I PARAM. >07501
To the next page
9·25
DCM DCM
000 020
DCM
020
書 込 ENT
9
Page 124
From the previous page “When PC is JW model and the SEND/RECEIVE function is used” Set PC model of each station [HEX (hexadecimal), byte] · Assign model type of the communication target station from ZW and JW PCs, ZW-20CM with JW applied or not, or JW-22CM (JW20/20H, JW30H). PC of target station Communication module of target station
ZW model
JW model
ZW-20CM (without JW applied sign)
00, 80
00, 80
ZW-20CM (with JW applied sign)
81
91
JW-20CM
81
91 91(H)
JW-22CM
Station number (8)
Address (8)
Station number (8)
Address
(8)
(8)
Station number (8)
007620
20
007640
40
007660
60
01
007621
21
007641
41
007661
61
007602
02
007622
22
007642
42
007662
62
007603
03
007623
23
007643
43
007663
63
007604
04
007624
24
007644
44
007664
64
007605
05
007625
25
007645
45
007665
65
007606
06
007626
26
007646
46
007666
66
007607
07
007627
27
007647
47
007667
67
007610
10
007630
30
007650
48
007670
70
007611
11
007631
31
007651
51
007671
71
007612
12
007632
32
007652
52
007672
72
007613
13
007633
33
007653
53
007673
73
007614
14
007634
34
007654
54
007674
74
007615
15
007635
35
007655
55
007675
75
007616
16
007636
36
007656
56
007676
76
007617
17
007637
37
007657
57
007677
77
Address
007760
Station number (8) Master station
007601
Address (8)
9
Setting value(H)
1. Initial value: All address 91(H). 2. Entering both 00(H) and 88(H) will produce the identical result. The SEND communication instruction (writing data) is not available with this setting. 3. You cannot program SEND/RECEIVE instructions in a ZW model PC. However, the ZW model PC will respond to SEND/RECEIVE instructions from a JW model PC. Ex.: When you want to enter 91(H) at both the master station and at slave station 01 (if the PC a JW model and the I/O is a ZW-20CM with a sticker indicating that it can be used with the JW model). After converting to hexadecimal, write the setting value.
Display the contents of address 007600(8)
To the next page
Screen display of JW-13PG 07577 07600 I PARAM. >07601
Write setting value in addrsee 007601(8)
9·26
HEX HEX
00 91
HEX
91
Page 125
From the previous page “When PC is JW model and the SEND/RECEIVE function is used”
V5
Select system in each channel in SEND/RECEIVE function Select the method of each channel (instruction or data memory starting) on the parameter address 007700 to 007703(8). 007700(8)
CH 0
007701(8)
CH 1
007702(8)
CH 2
007703(8)
CH 3
1. When using 1 channel alone Channel
CH 0 CH 1 CH 2 CH 3
Setting value (H)
System
00
Instruction system
80
Data memory starting system
00
Instruction system
81
Data memory starting system
00
Instruction system
82
Data memory starting system
00
Instruction system
83
Data memory starting system
2. When using connected channels (see page 10·2) In the SEND/RECEIVE function, the JW-22CM can transfer and receive a maximum of 256 bytes of data for each channel. For the data memory starting system, the amount of communication data can be increased by connecting channels. Set the data amount with 8X(H) (X is 0 to 3, determined depending on which channel is used for the connector.) When using connected channels, these should be consecutive channels. For example, channel 0 and 1, or channel 2 and 3 can be connected to each other, but channel 1 and 3 can not be connected to each other. [Example 1] When all channels are used for the data memory starting system (using 1 channel alone) CH 0 007700(8)
8 0 (H)
CH 1 007701(8)
8 1 (H)
CH 2 007702(8)
8 2 (H)
CH 3 007703(8)
8 3 (H)
[Example 2] When channel 0 is used for the instruction system, and channel 1 to 3 are the data memory starting system and used connected. (In this case, channel 2 and 3 can not be used.) CH 0 007700(8)
8 0 (H)
CH 1 007701(8)
8 1 (H)
CH 2 007702(8)
8 1 (H)
CH 3 007703(8)
8 1 (H)
If values other than “00(H), 80 to 83(H)” are set, they will be ignored. To the next page
9·27
9
Page 126
From the previous page “When PC is JW model and the SEND/RECEIVE function is used”
V5
V5
Set top address in communication information storage area when using data memory system of SEND/RECEIVE function · Set file address(8) in parameter addresses 007710 to 007713(8). Top address of communication information storage area (file address)
007710(8)
Lower
007711(8)
Upper
007712(8)
File number of communication information storage area
007713(8)
This setting is valid by 80(H)
“When PC is JW model and the memory capacity save function is used” Set the number of sending bytes of the relay link in save memory function [DCM (decimal), word] · Set the number of sending bytes in decimal on the parameter address 007720 to 007721(8). Lower Upper
007200(8) 007721(8)
· In case of setting 4 bytes using JW-13PG: Example for slave station 02 of page 9·41 Display the contents of parameter addresses 007720 to 007721(8) Write 00004(D) after converting to decimal Screen display of JW-13PG 07714 07716 I PARAM. >07720
V5
9
D D
00000 00000
D
00004
007720(8) 007721(8)
00004(D)
“When PC is JW model and the memory capacity save function is used” Set the number of receiving bytes of register link in save memory function Set the number of sending bytes in decimal on the parameter address 007722 to 007723(8). Lower Upper
007722(8) 007723(8)
· In case of setting 8 bytes for parameter addresses 007722 to 007723(8) using JW-13PG: Example for slave station 02 of page 9·41 Display the contents of parameter addresses 007722 to 007723(8) Write 00008(D) Screen display of JW-13PG 07716 07720 I PARAM. >07722
D D
00000 00004
D
00008
007722(8) 007723(8)
To the next page
9·28
00008(D)
Page 127
From the previous page
V5
“When PC is JW model and the memory capacity save function is used” File address: OCT (octal), word Set top address of relay link area. File number/flag: HEX (hexadecimal), byte · Set file address in parameter address 007730 to 007733(8). These top addresses should not overlap the register link area, flag area, or any area used by other option module. 007730(8)
Lower
007731(8)
Upper
007732(8)
00(H)
File address
007733(8)
In case of setting コ1000 (file address 001000(8)) using JW-13PG : Example for slave station 02 of page 9·41. アドレス ADRS
7
3 0
変 換 変 換 変 換 CONV CONV CONV STEP (+)
A
B
書 込 ENT
0
A
D
7
A
Display the contents of parameter address 007730 to 007731(8).
モニタ MNTR A
A
0 0 0
1
書 込 ENT
Write 001000(8)
Write parameter address 007732 to 007733(8) for 000000(8). Screen display of JW-13PG 07726 07730 I PARAM. >07732
V5
0 0
000000 001000
0
000000
“When PC is JW model and the memory capacity save function is used” File address: OCT (octal), word Set register link area of register link area. File number/flag: HEX (hexadecimal), byte · Set file address in parameter address 007734 to 007737(8). These top addresses should not overlap the relay link area, flag area, or any area used by other option module. 007734(8)
Lower
007735(8)
Upper
007736(8)
File number
File address
007737(8)
In case of setting 09000 (file address 004000(8)) using JW-13PG : Example for slave station 02 of page 9·41. STEP (+) STEP (+)
E
4
A
0
A
Write parameter address 007734 to 007735(8) for 004000(8).
A
0
0
A
0
Write parameter address 007736(8) for file number 0. Screen display of JW-13PG 07716 07720 I PARAM. >07722
D D
00000 00004
D
00008
To the next page
9·29
9
Page 128
From the previous page V5
Set whether the station number information should be output or not · Set whether the station number information should be output or not on the parameter address 007763(8).
007763(8)
Whether the station number information should be output or not
00(H): Do not output 01(H): Output The station number information is output on the next byte of the flag area (24 bytes.)
V5
File address: OCT (octal), word File number/flag: HEX (hexadecimal), byte
Set top address of flag area
· Set the top address of the flag area (24 bytes) in order to monitor the communication condition and PC operation condition on the parameter address 007764 to 007767(8). · Flag area uses 24 bytes regardless number of connecting stations. 007764(8) 007765(8) 007766(8) 007767(8) D7
Contents
Initial value
Lower
E0(H)
Upper
01(H) 00(H)
File number 0
80(H)
Output flag
Output flag : ON Do not output flag : OFF
Remarks
· The PC's input/output relays, auxiliary relays, registers etc. are all allocated individual byte addresses for each item. However, the JW-20CM can assign these addresses with file addressees allocated throughout the memory.
コ00677 コ00700 コ00777 コ01000
General purpose relay 001577 001600 001777 002000
Register 005777 006000
19777 29000
015777
99777
コ01577 TMR/CNT time limited contact b0000
TMR/CNT/MD current value
003777 b17777
· The usable file numbers will vary with the memory module that is installed on the PC. Name of memory module
Usable file numbers
ZW-1MA, JW-1MAH
0 or 1※
ZW-2MA, JW-2MAH
0 or 1
ZW-3MA, JW-3MAH
0, 1, 2
ZW-4MA, JW-4MAH
0, 1, 2, 3, 4, 5, 6, 7
To the next page
9·30
※ If file number is 1, file address shall be within 000000 to 037777(8). (See page 13·20 and 21 for other cases.)
JW model PCs
Latch relay
09777 19000
004777 005000 JW model PCs
000677 000700 000777 001000
Auxiliary relay
Register コ00377 コ00400
ZW model PCs
I/O relay 000377 000400
Byte address 09000
File address 004000
Byte address コ0000
File address
ZW model PCs
9
File number
Byte address 01E0(H)→000740(8)→コ0740