The text of a manual · part 18 of 27
SHARP Programmable Controller New Satellite W series: Network module JW-20CM, Remote I/O slave module JW-20RS User's Manual: Chapter 9: Data Link, pages 139 to 148
Pages 139 to 148 of 230, from SHARP Programmable Controller New Satellite W series: Network module JW-20CM, Remote I/O slave module JW-20RS User's Manual
The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Sharp ZW-1PU, Sharp ZW-32IO2 and Sharp ZW-32S2T
Page 139
From the previous page [Example for setting] The master station and slave station 01 and 02 are JW-20CM. It shows example for setting that slave station 01 is data link (standard function) and slave station 02 is data link (memory capacity save function : V5 ).
(Standard) Slave station 01
Master station
(Save memory) Slave station 02 Offset (4 bytes)
コ0200
コ 0210
コ 0210
8 bytes Relay 4 bytes link area
○ : Send ● : Receive
コ 0214 コ 0220 コ 0224
コ0223
コ1000
8 bytes
コ1004 コ 0233
4 bytes 8 bytes
コ1013
コ 0400
コ 0400
コ 0420
コ 0420
9000
コ 0430
9010
コ 0437
9017
Off set (8 bytes)
16 bytes Register link area
8 bytes
8 bytes コ 0430
8 bytes
8 bytes コ 0437 コ 0740
Flag 24 bytes area Station No. コ 0767 information
コ 0770
Flag 24 bytes
Flag 24 bytes
コ0740
19000 Station No. 19027 19030
Station No. ココ0767 0770 information
9 information
Maser station
Slave station 1 (standard)
Slave station 2 (save memory)
コ0210
コ0200
※ コ1000
–
–
4 bytes
Number of sending bytes of relay link
8 bytes
4 bytes
8 bytes
Number of receiving bytes of relay link
–
–
※ 4 bytes
コ0400
コ0400
※ 09000
–
–
8 bytes
Number of sending bytes of register link
16 bytes
8 bytes
8 bytes
Number of receiving bytes of register link
–
–
※ 8 bytes
Top address of flag area
コ0740
※ コ0740
※ 19000
Station number information output
Yes
※ Yes
※ Yes
Top address of relay link area Number of off set bytes of relay link area
Top address of register link area Number of off set bytes of register link area
No mark -- Setting by parameter of master station ※ ---------- Setting by parameter of slave station
To the next page
9·41
Page 140
From the previous page Data link function setting [HEX (hexadecimal), byte] • Set “01(H) (=001(8))” in parameter address 004002(8) and change to “relay/register link.” Screen display of JW-13PG
(Operation example of JW-13PG) Write 001(8) to 004002(8)
Set number of connecting stations
04000 04001 I PARAM. >04002
HEX HEX
880 00F
HEX
01
[DCM (decimal), byte]
• Set the number of connecting stations (02 to 64(D)) including the master station in the parameter address 004003(8) by octal. • If you try to set values other than 02 to 64(D), JW-20CM the displays 6F(H) error code. Screen display of JW-13PG
After converting into decimal notation in 004003(8), write “003.”
04001 04002 I PARAM. >04003
DCM DCM
000 001
DCM
003
Set top address of relay link area on slave station (01 to 77) (at standard function)/number of offset bytes (memory capacity save function) File address: OCT (octal), word File number/flag: HEX (hexadecimal), byte Set the "same" as or "different" from the master station: HEX (hexadecimal) , bytes.
9
• Set in parameter addresses 004004 to 004377(8). These top addresses should not overlap the register link area, flag area, or any area used by other option module. Slave station 01
004004(8) 004005(8) 004006(8) 004007(8)
〜 Slave station 77(8)
004374(8) 004375(8) 004376(8) 004377(8)
Lower Upper 00(H)
·
Lower Upper 00(H)
·
In case of standard function, set top address by file address(8). In case of save memory function, set number of offset bytes. 00(H): The top address is the same address of the master station regardless of the value set at of 004004 to 004005(8). 80(H): The top address is different from the address of the master station (Offset is valid). For the save memory function, set in 80(H).
00(H) 80(H)
• In case of setting コ0200 (file address 000200(8)) in parameter addresses 004004 to 004007(8) (slave station 01) and set 4 (number of off set bytes) in 004010(8) to 004013(8) (slave station 02). (Example for page 11·10.) To the next page
9·42
Page 141
From the previous page
( ) Word display
Slave station 01
Write 000200 (8) in parameter addresses 004004 to 004005(8). Convert to octal figures
Write 000(8) (=00(H)) in parameter address 004006(8).
( ) Byte display
Write 80(H) (the top address is not same as the master station) in parameter address 004007(8). Convert to hexadecimal figures
Write 00004(D) (offset 4) in parameter addresses 004010 to 004011(8).
Slave station 02
Write 00(H) in parameter address 004012(8).
Write 80(H) (offset valid) in parameter address 004013(8). Screen display of JW-13PG 04011 04012 I PARAM. >04013
HEX HEX
00 00
HEX
80
Set top address of register link area on the master station File address: OCT (octal), word File number: HEX (hexadecimal) , bytes. Set on the parameter address (004400 to 004403(8)) in the file address(8). These top addresses should not overlap the register link area, flag area, or any area used by other option modules. 004400(8) 004401(8) 004402(8) 004403(8)
Lower Upper File number
File address
• In case of setting コ0400 (file address 000400(8)) in parameter addresses 004400 to 004403(8) and set 0 (file number) in 004402(8). (Example for page 9·41). Display the contents of parameter addresses 004400 to 004401(8) Write 000400(8) after converting to octal. Write file no 0 in parameter address 004402(8). Screen display of JW-13PG 04400 04401 I PARAM. >04402
To the next page
9·43
OCT OCT
000 001
OCT
000
9
Page 142
From the previous page Set top address of register link area on slave station 01 to 77(8) (at standard function)/ number of offset bytes (at memory capacity save function) File address: OCT (octal), word File number/flag: HEX (hexadecimal), byte Set the "same" as or "different" from the master station: HEX (hexadecimal) , bytes.
Set in parameter addresses 004404 to 004777(8). These top addresses should not overlap the register link area, flag area, or any area used by other option module. Slave station 01
004404(8) 004405(8) 004406(8) 004407(8)
〜 Slave station 77(8)
004774(8) 004775(8) 004776(8) 004777(8)
Lower Upper File number
·
〜 Lower Upper File number
·
In case of standard function, set top address by file address(8). In case of memory capacity save function, set number of offset bytes. 00(H): The top address is the same address of the master station regardless of the values set at of 004404 to 004405(8). 80(H): The top address is different from the address of the master station (Offset is valid). For the memory capacity save function, set in 80(H). 00(H) 80(H)
• In case of setting 0 (the top address is コ0440, the same as the address of the master station) in parameter addresses 004404 to 004407(8) (slave station 01) and the offset byte number 8 and “offset valid” on the parameter address 004410 to 004413(8) (slave station 02). (Example for 9·40)
9
Slave station 01
Write 0 in parameter 004004 to 004007(8) (same as master station). Write 00008(D) (offset 8) in parameter addresses 004410 to 004411(8).
Slave station 02
Write 00(H) (file 0) in parameter address 004412(8). Write 80(H) (offset valid) in parameter address 004413(8). Screen display of JW-13PG 04011 04012 I PARAM. >04013
To the next page
9·44
HEX HEX
00 00
HEX
80
Page 143
From the previous page Set the number of sending bytes of the master station relay link [DCM (decimal), word] • Set in parameter addresses 005000 to 005001(8). 005000(8) 005001(8)
Lower Upper
• These top addresses should not overlap the register link area, or the flag area, or exceed the setting range (0 to 256 bytes for each station, 256 bytes for all stations in total). In case of setting 8 bytes: Using JW-13PG example for page 9·41 Display the contents of parameter addresses 005000 to 005001(8) Screen display of JW-13PG Write 00008(D) after converting to decimal. 04774 D 00000 04776 I PARAM. >05000
D
00000
D
00008
Set the number of sending bytes of the slave station (01 to 77) relay link [DCM (decimal), word] • Set the number of sending bytes in decimal on the parameter addresses 005002 to 005177(8). (set in each station, 2 bytes for each station). These top addresses should not overlap the register link area, or the flag area, or exceed the setting range (0 to 256 bytes for each station, 256 bytes for all stations in total). Slave station 01(8) Slave station 77(8)
005002(8) 005003(8) to 005176(8) 005177(8)
Lower Upper to Lower Upper
}Enter by decimal }Enter by decimal
(In case of setting 4 bytes for slave station 01, and set 8 bytes for slave station 02: Example of page 9·41) Slave station 01
Write 00004(D) in parameter addresses 005002 to 005003(8).
Slave station 02
Write 00008(D) in parameter addresses 005004 to 005005(8). Screen display of JW-13PG 05000 05002 I PARAM. >05004
To the next page
9·45
D D
00008 00004
D
00008
9
Page 144
From the previous page Set the number of sending bytes of the master station register link [DCM (decimal), word] • Set the number of sending bytes in decimal on the parameter addresses 005200 to 005201(8). • These top addresses should not overlap the relay link area or the flag area, or exceed the setting value (0 to 2048 bytes for each station, 2048 bytes for all stations in total). 005200(8) 005201(8)
Lower Upper
}Enter by decimal
(In case of setting 16 bytes using JW-13PG: Example of page 9·41) Display the contents of parameter addresses 005200 to 005201(8) Screen display of JW-13PG Write 00016(D) in decimal notation. 05174 05176 I PARAM. >05200
D D
00000 00000
D
00016
Set the number of sending bytes of the slave station (01 to 77(8)) register link [DCM (decimal), word] • Set the number of sending bytes in decimal on the parameter addresses 005202 to 005377(8). (set in each station, 2 bytes for each station). These top addresses should not overlap the resister link area, or the flag area, or exceed the setting range (0 to 2048 bytes for each station, 2048 bytes for all stations in total). Slave station 01
Slave station 77(8)
9
005202(8) 005203(8) to 005376(8) 005377(8)
Lower Upper to Lower Upper
(In case of setting 8 bytes both for slave station 01 and 02: example of page 9·41) Slave station 01
Write 00008(D) in parameter addresses 005202 to 005203(8).
Slave station 02
Write 00008(D) in parameter addresses 005204 to 005205(8). Screen display of JW-13PG 05200 05202 I PARAM. >05204
To the next page
9·46
D D
00016 00008
D
00008
Page 145
From the previous page “When PC is JW model and the SEND/RECEIVE function is used” Set time-out time of SEND/RECEIVE function [DCM (decimal), byte] • When the own station uses the SEND/RECEIVE instructions, set the time-out time on each communication target station. • Setting range is 001 (0.1 sec.) to 255 (25.5 sec.) by decimal. 00(H) of initial value is 1 second. Station No. (8)
Address (8)
Station No. (8)
Address
(8)
―
―
007520
20
007501
01
007521
007502
02
007503
Address
Station No. (8)
Address (8)
Station No. (8)
007540
40
007560
60
21
007541
41
007561
61
007522
22
007542
42
007562
62
03
007523
23
007543
43
007563
63
007504
04
007524
24
007544
44
007564
64
007505
05
007525
25
007545
45
007565
65
007506
06
007526
26
007546
46
007566
66
007507
07
007527
27
007547
47
007567
67
007510
10
007530
30
007550
48
007570
70
007511
11
007531
31
007551
51
007571
71
007512
12
007532
32
007552
52
007572
72
007513
13
007533
33
007553
53
007573
73
007514
14
007534
34
007654
54
007574
74
007515
15
007535
35
007555
55
007575
75
007516
16
007536
36
007556
56
007576
76
007517
17
007537
37
007557
57
007577
77
(8)
9
Initial value: 00(H) in all address (1 second) (In case of setting 020(D) (2 sec.) both for slave station 01 and 02 using JW-13PG) Screen display of JW-13PG
Display the contents of address 007501(8)
Write setting value
Writs setting value in addrsee 007502(8)
To the next page
9·47
07500 07501 I PARAM. >07502
DCM DCM
000 020
DCM
020
Page 146
From the previous page “When PC is JW model and the SEND/RECEIVE function is used” Set PC model of each station [HEX (hexadecimal), byte] • Assign model type of the communication target station from ZW and JW PCs, ZW-20CM with JW applied or not, or JW-22CM (JW20/JW20H, JW30H) PC of target station Communication module of target station
ZW model
JW model
ZW-20CM (without JW applied sign)
00, 80
00, 80
ZW-20CM (with JW applied sign)
81
91
JW-20CM
81
91 91
JW-22CM
Address (8)
9
Set values(H)
Station number (8)
Address
Station number (8)
Address (8)
Station number (8)
Address
(8)
(8)
Station number (8)
007620
20
007640
40
007660
60
007601
01
007621
21
007641
41
007661
61
007602
02
007622
22
007642
42
007662
62
007603
03
007623
23
007643
43
007663
63
007604
04
007624
24
007644
44
007664
64
007605
05
007625
25
007645
45
007665
65
007606
06
007626
26
007646
46
007666
66
007607
07
007627
27
007647
47
007667
67
007610
10
007630
30
007650
48
007670
70
007611
11
007631
31
007651
51
007671
71
007612
12
007632
32
007652
52
007672
72
007613
13
007633
33
007653
53
007673
73
007614
14
007634
34
007654
54
007674
74
007615
15
007635
35
007655
55
007675
75
007616
16
007636
36
007656
56
007676
76
007617
17
007637
37
007657
57
007677
77
1. Initial value: 91(H) all address. 2. Entering both 00(H) and 88(H) will produce the identical result. The SEND communication instruction (writing data) is not available with this setting. 3. You cannot program SEND/RECEIVE instructions in a ZW model PC. However, the ZW model PC will respond to SEND/RECEIVE instructions from a JW model PC. Ex.: When you want to enter 91(H) at both the slave station 01 and 02 (if the PC a JW model and the I/O is a ZW-20CM with a sticker indicating that it can be used with the JW model or JW20CM).
Screen display of JW-13PG
After converting to hexadecimal, write the setting value.
Display the contents of address 007601(8)
To the next page
Write setting value in addrsee 007602(8)
9·48
07600 07601 I PARAM. >07602
HEX HEX
00 91
HEX
91
Page 147
From the previous page “When PC is JW model and the SEND/RECEIVE function is used” Select system in each channel in SEND/RECEIVE function • Select the method of each channel (instruction or data memory starting) on the parameter address 007700 to 007703(8). 007700(8)
CH 0
007701(8)
CH 1
007702(8)
CH 2
007703(8)
CH 3
1. When using 1 channel alone Channel
CH 0 CH 1 CH 2 CH 3
Setting value (H)
System
00
Instruction system
80
Data memory starting system
00
Instruction system
81
Data memory starting system
00
Instruction system
82
Data memory starting system
00
Instruction system
83
Data memory starting system
2. When using connected channels In the SEND/RECEIVE function, the JW-20CM can send and receive a maximum of 256 bytes of data for each channel. For the data memory starting system, the amount of communication data can be increased by connecting channels. Set the data amount with 8X(H) (X is 0 to 3, determined depending on which channel is used for the connector.) When using connected channels, these should be consecutive channels. For example, channel 0 and 1, or channel 2 and 3 can be connected to each other, but channel 1 and 3 can not be connected to each other. [Example 1] When all channels are used for the data memory starting system (using 1 channel alone) CH 0 007700(8)
8 0 (H)
CH 1 007701(8)
8 1 (H)
CH 2 007702(8)
8 2 (H)
CH 3 007703(8)
8 3 (H)
[Example 2] When channel 0 is used for the instruction system, and channel 1 to 3 are the data memory starting system and used connected. (In this case, channel 2 and 3 can not be used.) CH 0 007700(8)
8 0 (H)
CH 1 007701(8)
8 1 (H)
CH 2 007702(8)
8 1 (H)
CH 3 007703(8)
8 1 (H)
If you enter values other than “00(H), 81(H) to 83(H)” the JW-20CM ignores the entry. To the next page
9·49
9
Page 148
From the previous page “When PC is JW model and the SEND/RECEIVE function is used”
V5
Set top address in communication information storage area when using data memory starting system of SEND/RECEIVE functions Set address of communication information storage area in parameter addresses 007710 to 007713(8). Top address of communication information Lower 007710(8) storage area Upper (file address) 007711(8) 007712(8) 007713(8)
File number of communication information storage area
This setting is valid by 80(H)
Set connection status of slave station [bit pattern, byte] • In the initial settings of the data link function, the JW-20CM will not display errors (on the LEDs on the panel, or in the system memory) even if it detects a communication error in a slave station. In order to display the error when a slave station communication error is detected, set bit 0(E) at parameter address 007750(8) to ON. Each bit at addresses 00751 to 007757(8) corresponds to a slave station. Turn ON the respective bit if required. (See page 13·15.) With the setting above, the JW-20CM will display errors when a slave station whose corresponding bit is ON produces a communication error. 7 6 5 4 3 2 1 0 Ex.: Setting the bits to output errors for slave 007750(8) 0 0 0 0 0 1 1 1 stations 01 and 02 using the JW-13PG. Screen display of JW-13PG 07746 □□□□□□□□ 07747 □□□□□□□□ I PARAM. >07750 □□□□□■■■
9
· If a bit corresponding to a slave station is turned OFF, the module will not display an error code for a slave station which has an error.
V5
Set whether the station number information should be output or not • Set whether the station number information should be output or not on the parameter address 007763(8).
007763(8)
Whether the station number information should be output or not
00(H): Do not output 01(H): Output The station number information is output on the next byte of the flag area (24 bytes.)
To the next page
9·50