Spec sheet · Siemens
Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20): SlimLine
Spec sheet12 pagesPDF 764 KB
Siemens catalog pages for SlimLine AS-Interface I/O modules for the control cabinet, including the 3RK1 200-0CE02-0AA2 4-input slave.
Covers · 1 model
The models it covers
Summary
What is in it
Pages from the Siemens Energy & Automation Industrial Controls Catalog on SlimLine Actuator-Sensor-Interface (AS-Interface) I/O modules for use in the control cabinet (IP 20). It gives selection and ordering data for the S22.5 and S45 modules with screw-type or Cage Clamp terminals (4 inputs, 2 inputs/2 outputs, 4 outputs, 4 inputs/4 outputs and A/B slaves), accessories, technical data tables for each order number, and dimension drawings. The 3RK1 200-0CE02-0AA2 is the 4-input module for 2- and 3-wire PNP sensors.
Its parts
- Selection and ordering data
- Technical data
- Dimension drawings
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Siemens Industrial Controls Catalog pages 16/78 to 16/89 on the AS-Interface SlimLine I/O modules for the control cabinet (IP 20), in S22.5 and S45 sizes with screw-type or Cage Clamp terminals. Besides the 3RK1 200-0CE02-0AA2 four-input module, it covers the other 3RK1 and 3RK2 input, output and mixed modules. It gives ordering data, technical data and dimension drawings.
- What it is
- 3RK1200-0CE02-0AA2: AS-Interface SlimLine S22.5 standard slave, 4 PNP inputs for 2- and 3-wire sensors, screw-type terminals p. 1, 3
- Operating voltage
- 26.5 ... 31.6 V, per the AS-Interface specification p. 3
- Sensor supply
- 3RK1200-0CE02-0AA2: via AS-Interface, short-circuit and overload-proof, 20 ... 30 V, 200 mA load rating p. 3
- Input levels
- 3RK1200-0CE02-0AA2: switching level High ≥ 10 V; input current Low/High ≤1.5/≥ 5 mA p. 3
- Indicators
- Yellow LED for inputs/outputs, green LED for AS-Interface, red LED for FAULT p. 3
- Data bits
- 3RK1200-0CE02-0AA2: I/O configuration 0; data bits D0 to D3 carry IN1 to IN4 p. 3
- Protection
- IP 20, for operation in the control cabinet p. 3
- Storage temperature
- –40 ... +85 °C p. 3
- Approvals
- The document lists UL, CSA and ship building approvals p. 3
- SlimLine family
- 4 inputs, 4 outputs, 2 inputs/2 outputs (transistor or relay), 4 inputs/4 outputs, and 4 inputs/3 outputs A/B slaves p. 1
- Accessories
- Push-in lugs for screw mounting, SlimLine opening tool for Cage Clamp terminals, sealable cap against unauthorized addressing; order numbers 3RP1 902, 3RP1 903, 8WA2 807 p. 2
- Cage Clamp conductors
- Cage Clamp versions: solid 2 × (0.25-1.5) mm2; AWG 2 × (24-16) p. 5
- Relay output fuse
- Relay output 4 inputs/4 outputs modules: external back-up fuse 6 A gL/gG p. 8
What this sheet walks you through
- Choosing and ordering a SlimLine module by I/O mix and terminal type p. 1, 2
- Technical data of each SlimLine module p. 3, 4, 5, 6, 7, 8, 9, 10
- Wiring the external 24 V supply terminals of the S45 modules p. 7
- Dimension drawings of the S22.5 and S45 housings p. 12
Good to know
- The output circuit needs an external AUX POWER supply of DC 20 to 30 V complying with VDE 0106 (PELV), safety class III. p. 3
- On the 4 inputs/4 outputs modules the total current for all outputs is 4 A. p. 7
- For the 4 inputs/3 outputs A/B slave 3RK2 400-1FE00-0AA2, the AS-Interface certificate is listed as in preparation. p. 9
Questions this sheet answers
Can the 3RK1200-0CE02-0AA2 take 3-wire sensors?
Yes. It is the 2- and 3-wire PNP version of the four-input SlimLine module, with sensor supply through AS-Interface. p. 1, 3
What voltage does an AS-Interface SlimLine module run on?
26.5 to 31.6 V, in line with the AS-Interface specification. p. 3
What do the LEDs on the SlimLine module mean?
Yellow shows the inputs/outputs, green shows AS-Interface, red shows a FAULT. p. 3
Which data bits carry the four inputs of the 3RK1200-0CE02-0AA2?
Data bits D0 to D3 carry IN1 to IN4. p. 3
What tool opens the SlimLine Cage Clamp terminals?
The SlimLine opening tool, for devices with Cage Clamp terminals up to 1.5 mm2 conductors. p. 2
The whole text · 2 parts
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file