Page 1 of Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20): SlimLine

Spec sheet · Siemens

Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20): SlimLine

Spec sheet12 pagesPDF 764 KB

Siemens catalog pages for SlimLine AS-Interface I/O modules for the control cabinet, including the 3RK1 200-0CE02-0AA2 4-input slave.

Download the PDF764 KB

Covers · 1 model

The models it covers

Summary

What is in it

Pages from the Siemens Energy & Automation Industrial Controls Catalog on SlimLine Actuator-Sensor-Interface (AS-Interface) I/O modules for use in the control cabinet (IP 20). It gives selection and ordering data for the S22.5 and S45 modules with screw-type or Cage Clamp terminals (4 inputs, 2 inputs/2 outputs, 4 outputs, 4 inputs/4 outputs and A/B slaves), accessories, technical data tables for each order number, and dimension drawings. The 3RK1 200-0CE02-0AA2 is the 4-input module for 2- and 3-wire PNP sensors.

Its parts

  1. Selection and ordering data
  2. Technical data
  3. Dimension drawings

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

Siemens Industrial Controls Catalog pages 16/78 to 16/89 on the AS-Interface SlimLine I/O modules for the control cabinet (IP 20), in S22.5 and S45 sizes with screw-type or Cage Clamp terminals. Besides the 3RK1 200-0CE02-0AA2 four-input module, it covers the other 3RK1 and 3RK2 input, output and mixed modules. It gives ordering data, technical data and dimension drawings.

What it is
3RK1200-0CE02-0AA2: AS-Interface SlimLine S22.5 standard slave, 4 PNP inputs for 2- and 3-wire sensors, screw-type terminals p. 1, 3
Operating voltage
26.5 ... 31.6 V, per the AS-Interface specification p. 3
Sensor supply
3RK1200-0CE02-0AA2: via AS-Interface, short-circuit and overload-proof, 20 ... 30 V, 200 mA load rating p. 3
Input levels
3RK1200-0CE02-0AA2: switching level High ≥ 10 V; input current Low/High ≤1.5/≥ 5 mA p. 3
Indicators
Yellow LED for inputs/outputs, green LED for AS-Interface, red LED for FAULT p. 3
Data bits
3RK1200-0CE02-0AA2: I/O configuration 0; data bits D0 to D3 carry IN1 to IN4 p. 3
Protection
IP 20, for operation in the control cabinet p. 3
Storage temperature
–40 ... +85 °C p. 3
Approvals
The document lists UL, CSA and ship building approvals p. 3
SlimLine family
4 inputs, 4 outputs, 2 inputs/2 outputs (transistor or relay), 4 inputs/4 outputs, and 4 inputs/3 outputs A/B slaves p. 1
Accessories
Push-in lugs for screw mounting, SlimLine opening tool for Cage Clamp terminals, sealable cap against unauthorized addressing; order numbers 3RP1 902, 3RP1 903, 8WA2 807 p. 2
Cage Clamp conductors
Cage Clamp versions: solid 2 × (0.25-1.5) mm2; AWG 2 × (24-16) p. 5
Relay output fuse
Relay output 4 inputs/4 outputs modules: external back-up fuse 6 A gL/gG p. 8

What this sheet walks you through

  • Choosing and ordering a SlimLine module by I/O mix and terminal type p. 1, 2
  • Technical data of each SlimLine module p. 3, 4, 5, 6, 7, 8, 9, 10
  • Wiring the external 24 V supply terminals of the S45 modules p. 7
  • Dimension drawings of the S22.5 and S45 housings p. 12

Good to know

  • The output circuit needs an external AUX POWER supply of DC 20 to 30 V complying with VDE 0106 (PELV), safety class III. p. 3
  • On the 4 inputs/4 outputs modules the total current for all outputs is 4 A. p. 7
  • For the 4 inputs/3 outputs A/B slave 3RK2 400-1FE00-0AA2, the AS-Interface certificate is listed as in preparation. p. 9

Questions this sheet answers

Can the 3RK1200-0CE02-0AA2 take 3-wire sensors?

Yes. It is the 2- and 3-wire PNP version of the four-input SlimLine module, with sensor supply through AS-Interface. p. 1, 3

What voltage does an AS-Interface SlimLine module run on?

26.5 to 31.6 V, in line with the AS-Interface specification. p. 3

What do the LEDs on the SlimLine module mean?

Yellow shows the inputs/outputs, green shows AS-Interface, red shows a FAULT. p. 3

Which data bits carry the four inputs of the 3RK1200-0CE02-0AA2?

Data bits D0 to D3 carry IN1 to IN4. p. 3

What tool opens the SlimLine Cage Clamp terminals?

The SlimLine opening tool, for devices with Cage Clamp terminals up to 1.5 mm2 conductors. p. 2

The whole text · 2 parts

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 61-6
  2. Pages 7 to 127-12

The file

Revision and size

RevisionIndustrial Controls Catalog, pages 16/78 to 16/89
PublisherSiemens Energy & Automation, Inc.
Pages12
PDF764 KB
TextText from the PDF itself.

The first pages · 4 of 12

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 12
Page 2
Page 2of 12
Page 3
Page 3of 12
Page 4
Page 4of 12