Page 1
16_Sec (065-096).qxd
07/28/03
03:24 PM
Page 16/78
Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine
■ Selection and ordering data Design
Description
Order No.
Price
Pack
1 unit
Unit
SlimLine S22.5 with screw-type terminals 3RK1 200-0CE00-0AA2
3RK1 100-1CE00-0AA2
4 inputs Standard slaves
4I
• 2-wire PNP transistor
3RK1 200-0CE00-0AA2
1
• 2- and 3-wire PNP transistor
3RK1 200-0CE02-0AA2
1
• 115 V input (AC)
3RK1 200-0CE00-0AC2
1
• 230 V input (AC)
3RK1 200-0CE01-0AC2
1
2 inputs/2 outputs PNP transistor 2-wire Standard slaves
2I/2O
3RK1 400-0BE00-0AA2
1
2 inputs/2 outputs relay outputs
2I/2OR
3RK1 402-0BE00-0AA2
1
4 outputs PNP transistor Standard slaves
4O
3RK1 100-1CE00-0AA2
1
• 2-wire
3RK1 200-0CG00-0AA2
1
• 2- and 3-wire
3RK1 200-0CG02-0AA2
1
SlimLine S22.5 with Cage Clamp terminals 3RK1 200-0CG00-0AA2
4 inputs PNP transistor Standard slaves
4I
2 inputs/2 outputs 2-wire PNP transistor Standard slaves
2I/2O
3RK1 400-0BG00-0AA2
1
2 inputs/2 outputs relay outputs
2I/2OR
3RK1 402-0BG00-0AA2
1
4 outputs PNP transistor Standard slaves
4O
3RK1 100-1CG00-0AA2
1
•1A
3RK1 400-1CE00-0AA2
1
•2A
3RK1 400-1CE01-0AA2
1
• 1 A, floating I/Os
3RK1 402-3CE01-0AA2
1
• 230 V
3RK1 402-3CE00-0AA2
1
• 115 V input (AC)
3RK1 402-1CE00-0AC2
1
• 230 V input (AC)
3RK1 402-1CE01-0AC2
1
3RK2 400-1FE00-0AA2
1
SlimLine S45 with screw-type terminals 3RK1 400-1CE00-0AA2
4 inputs/4 outputs Standard slaves PNP transistor
4 inputs/4 outputs Relay output Standard slaves
4 inputs/ 3 outputs 2A PNP transistor A/B slaves
16/78
4I/4O
4I/4OR
4I/3O
Discount Code: AS-Interface
Siemens Energy & Automation, Inc. Industrial Controls Catalog
Page 2
16_Sec (065-096).qxd
07/28/03
03:24 PM
Page 16/79
Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine
■ Selection and ordering data Design
Description
Order No.
Price
Pack
1 unit
Unit
SlimLine S45 with Cage Clamp terminals 3RK1 400-1CG00-0AA2
4 inputs/4 outputs Standard slaves PNP transistor
4I/4O
•1A
3RK1 400-1CG00-0AA2
1
•2A
3RK1 400-1CG01-0AA2
1
• 1 A, floating I/Os
3RK1 402-3CG01-0AA2
1
4 inputs/4 outputs relay output 230 V
4E/4AR
3RK1 402-3CG00-0AA2
1
4 inputs/ 3 outputs A/B slaves
4E/3A
3RK2 400-1FG00-0AA2
1
Accessories 3RP1 902
Push-in lugs for screw mounting (1 packg. = 10 units)
3RP1 903
10
8WA2 807
1
5 1 packg.
SlimLine opening tool for all devices with Cage Clamp terminals up to max. 1.5 mm2 conductor cross-section partly insulated
Siemens Energy & Automation, Inc. Industrial Controls Catalog
1 packg.
Sealable cap for protection against unauthorized addressing (1 packg. = 5 units)
Discount Code: AS-Interface
16/79
Page 3
16_Sec (065-096).qxd
07/28/03
03:24 PM
Page 16/80
Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine
■ Technical data SlimLine S22.5 with screw-type terminals 4 inputs
Slave type
2-wire
2- and 3-wire
115 V input (AC)
230 V input (AC)
PNP transistor
PNP transistor
3RK1 200-0CE00-0AA2
3RK1 200-0CE02-0AA2
3RK1 200-0CE00-0AC2
3RK1 200-0CE01-0AC2
≤ 270
≤60
Standard slaves
Operational voltage in accordance with AS-Inter- 26.5 ... 31.6 face specification in V Total current input in mA
≤ 50
Input connection
PNP
Inputs • Sensor supply via AS-Interface
Short-circuit and overload-proof
–
• Voltage range in V
20 ... 30
–
• Load rating for sensor supply in mA
–
200
–
• Connection of sensors
2-wire system
2- and 3-wire system
2-wire system
• Switching level High in V
≥ 10
≥ 10
≥ 79 AC / ≤ 135 AC
• Input current Low/High in mA
≤1.5/≥ 5
I/O configuration
0
ID/ID2 code
0/F
≥ 164 AC / ≤ 255 AC
≤1.5/≥ 6 F/F
Assignment of data bits • Data bit D0
IN1
• Data bit D1
IN2
• Data bit D2
IN3
• Data bit D3
IN4
AS-Interface certificate yes
Approvals
UL, CSA, ship building
Protection
IP 20
Ambient temperature in °C
–25 ... +85
Storage temperature in °C
–40 ... +85
Weight in g
150 in preparation
–25 ... +60 140
Displays • Inputs/outputs yellow LED
• AS-Interface green LED
• FAULT red LED
Connection via screw terminal
Note
To supply the output circuit, an external supplementary supply (AUX POWER) of DC 20 to 30 V is necessary. The supplementary supply must comply with VDE 0106 (PELV), safety class III.
16/80
Siemens Energy & Automation, Inc. Industrial Controls Catalog
Page 4
16_Sec (065-096).qxd
07/28/03
03:24 PM
Page 16/81
Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine
■ Technical data 2 inputs/2 outputs 2-wire
Slave type
4 outputs
PNP transistor
Relay outputs
PNP transistor
3RK1 400-0BE00-0AA2
3RK1 402-0BE00-0AA2
3RK1 100-1CE00-0AA2
Standard slaves
Operational voltage in accordance with AS-Inter- 26.5 ... 31.6 face specification in V Total current input in mA
≤ 50
≤40
Input connection
PNP
–
• Sensor supply via AS-Interface
Short-circuit and overload-proof
–
• Voltage range in V
20 ... 30
–
• Load rating for sensor supply in mA
–
• Connection of sensors
2-wire system
–
• Switching level High in V
≥ 10
–
• Input current Low/High in mA
≤1.5/≥ 5
–
Inputs
Outputs • Type of output
PNP transistor
Relay
Electronics (PNP)
• Current carrying capacity in A
2
–
1
• Short-circuit protection built-in external back-up fuse built-in
• Inductive interference protection built-in not applicable built-in
• Polarity reversal protection not built-in not applicable built-in
• External voltage supply DC 24 V via screw terminal Terminal 7 = "+" Terminal 10 = "-" not applicable via screw terminal Terminal 7 = "+" Terminal 10 = M
• Ith
–
6
–
• AC-15
–
3
–
• DC 13 24 V
–
1
–
• DC 13 110 V
–
0.2
–
• DC 13 230 V
–
0,1
–
Watchdog built-in
I/O configuration
3
ID/ID2 code
0/F
8
Assignment of data bits • Data bit D0
IN1
OUT1
• Data bit D1
IN2
OUT2
• Data bit D2
OUT1
OUT3
• Data bit D3
OUT2
OUT4
AS-Interface certificate yes
Approvals
UL, CSA, ship building
Protection
IP 20
Ambient temperature in °C
–25 ... +70
Storage temperature in °C
–40 ... +85
Weight in g
150
160 approx. 150
Displays • Outputs yellow LED
• AS-Interface green LED
• Diagnostics
– red LED
• FAULT red LED
–
Connection
Screw terminals
Note
To supply the output circuit, an external supplementary supply (AUX POWER) of DC 20 to 30 V is necessary. The supplementary supply must comply with VDE 0106 (PELV), safety class III.
Siemens Energy & Automation, Inc. Industrial Controls Catalog
16/81
Page 5
16_Sec (065-096).qxd
07/28/03
03:24 PM
Page 16/82
Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine
■ Technical data SlimLine S22.5 with Cage Clamp terminals 4 inputs
Slave type
2 inputs/2 outputs
2-wire
2- and 3-wire
2-wire
PNP transistor
PNP transistor
PNP transistor
3RK1 200-0CG00-0AA2
3RK1 200-0CG02-0AA2
3RK1 400-0BG00-0AA2
≤ 270
≤ 50
Relay outputs
3RK1 402-0BG00-0AA2
Standard slaves
Operational voltage in accordance with AS-Inter- 26.5 ... 31.6 face specification in V Total current input in mA
≤ 50
Input connection
PNP
Inputs • Sensor supply via AS-Interface
Short-circuit and overload-proof
• Voltage range in V
20 ... 30
• Load rating for sensor supply in mA
–
200
–
• Connection of sensors
2-wire system
2- and 3-wire system
2-wire system
• Switching level High in V
≥ 10
• Input current Low/High in mA
≤1.5/≥ 5
Outputs • Type of output
–
PNP transistor
Relay floating changeover contact
• Current carrying capacity in A DC 12 / DC 13 typ. (total current for all outputs 4 A)
–
2
–
• Ith
–
6
• AC-15
–
3
• DC 13 24 V
–
1
• DC 13 110 V
–
0.2
• DC 13 230 V
–
• Short-circuit protection
– built-in external back-up fuse necessary
• Inductive interference protection
– built-in not applicable
• Polarity reversal protection
– not built-in not applicable
• External voltage supply DC 24 V
– via terminals: Terminal 7 = "+" Terminal 10 = "-" not applicable
0,1
• Watchdog
– built-in
I/O configuration
0
3
ID/ID2 code
0/F
Assignment of data bits • Data bit D0
IN1
• Data bit D1
IN2
• Data bit D2
IN3
OUT1
• Data bit D3
IN4
OUT2
AS-Interface certificate yes
Approvals
UL, CSA, ship building
Protection
IP 20
Ambient temperature in °C
–25 ... +85
Storage temperature in °C
–40 ... +85
Weight in g
150
–25 ... +70 160
Displays • Inputs/outputs yellow LED
• AS-Interface green LED
• FAULT red LED
Connection
Cage Clamp terminals
Conductor cross-sections in mm2 solid: 2 × (0.25-1.5) finely stranded with end sleeve:2 × (0.25-1) finely stranded without end sleeve: 2 × (0.25-1.5) AWG conductors, solid or stranded: AWG 2 × (24-16)
Note 1
Opening tool for Cage Clamp terminals: See accessories
Note 2
To supply the output circuit, an external supplementary supply (AUX POWER) of DC 20 to 30 V is necessary. The supplementary supply must comply with VDE 0106 (PELV), safety class III.
16/82
Siemens Energy & Automation, Inc. Industrial Controls Catalog
Page 6
16_Sec (065-096).qxd
07/28/03
03:24 PM
Page 16/83
Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine
■ Technical data 4 outputs PNP transistor 3RK1 100-1CG00-0AA2 Slave type
Standard slaves
Operational voltage in accordance with AS-Interface specification in V
26.5 ... 31.6
Total current input in mA
≤40
Outputs • Type of output
Electronics (PNP)
• Current carrying capacity in A DC 12 / DC 13 typ. (max. 2 A per module)
1
• Short-circuit protection built-in
• Polarity reversal protection built-in
• Inductive interference protection built-in
• External voltage supply DC 24 V via screw terminal (terminal 7 = "+", terminal 10 = M)
Watchdog built-in
I/O configuration
8
ID/ID2 code
0/F
Assignment of data bits • Data bit D0
OUT1
• Data bit D1
OUT2
• Data bit D2
OUT3
• Data bit D3
OUT4
AS-Interface certificate yes
Approvals
UL, CSA, ship building
Protection
IP 20
Ambient temperature in °C
–25 ... +70
Storage temperature in °C
–40 ... +85
Weight in g approx. 150
Displays • Outputs yellow LED
• AS-Interface green LED
• Diagnostics red LED
Connection
Cage Clamp terminals
Conductor cross-sections in mm2 solid: 2 × (0.25-1.5) finely stranded with end sleeve: 2 × (0.25-1) finely stranded without end sleeve: 2 × (0.25-1.5) AWG conductors, solid or stranded: AWG 2 × (24-16)
Note 1
Opening tool for Cage Clamp terminals: See accessories
Note 2
To supply the output circuit, an external supplementary supply (AUX POWER) of DC 20 to 30 V is necessary. The supplementary supply must comply with VDE 0106 (PELV), safety class III.
Siemens Energy & Automation, Inc. Industrial Controls Catalog
16/83