The text of a spec sheet · part 2 of 2
Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20): SlimLine, pages 7 to 12
Pages 7 to 12 of 12
The original document is the PDF (764 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens 3RK1200-0CE02-0AA2
Page 7
16_Sec (065-096).qxd
07/28/03
03:24 PM
Page 16/84
Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine
■ Technical data SlimLine S45 with screw-type terminals 4 inputs/4 outputs PNP transistor 1A 3RK1 400-1CE00-0AA2 Slave type
Standard slaves
Operational voltage in accordance with AS-Interface specification in V
26.5 ... 31.6
Total current input in mA
≤ 270
Input connection
PNP
2A 3RK1 400-1CE01-0AA2
1 A, floating 3RK1 402-3CE01-0AA2
≤40
Inputs • Sensor supply via AS-Interface
Short-circuit and overload-proof
• Voltage range in V
20 ... 30
• Load rating for sensor supply in mA
200
• Connection of sensors
2- and 3-wire system
• Switching level High in V
≥ 10
• Input current Low/High in mA
≤1.5/ ≥ 5
Outputs • Type of output
Electronics
• Current carrying capacity in A DC 12 / DC 13 typ. (total current for all outputs 4 A)
1
• Ith
–
• AC-15
–
• DC 13 24 V
–
• DC 13 110 V
–
• DC 13 230 V
–
• Short-circuit protection built-in
• Inductive interference protection built-in
• Polarity reversal protection built-in
• External voltage supply DC 24 V
Terminal 13 = L24+ Terminal 19 = M24
Watchdog built-in
I/O configuration
7
ID/ID2 code
0/F
2
1
Sensor supply: Terminal 13 = U_s+ Terminal 19 = U_s– Actuator supply: Terminal 14 = L+ Terminals 20 to 24 = M
Assignment of data bits • Data bit D0
IN1/OUT1
• Data bit D1
IN2 /OUT2
• Data bit D2
IN3/OUT3
• Data bit D3
IN4/OUT4
AS-Interface certificate yes
Approvals
UL, CSA, ship building
Protection
IP 20
Ambient temperature in °C
–25 ... +70
Storage temperature in °C
–40 ... +85
Weight in g approx. 280
Displays • Inputs/outputs yellow LED
• AS-Interface green LED
• FAULT red LED
Connection via screw terminal
Note 1
–
Note 2
To supply the output circuit, an external supplementary supply (AUX POWER) of DC 20 to 30 V is necessary. The supplementary supply must comply with VDE 0106 (PELV), safety class III.
16/84
The module has four floating inputs and four floating switching outputs. For the input and output circuits, an external additional supply of 20 to 30 V according to VDE 0106 (PELV) safety class III is required.
Siemens Energy & Automation, Inc. Industrial Controls Catalog
Page 8
16_Sec (065-096).qxd
07/28/03
03:24 PM
Page 16/85
Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine
■ Technical data 4 inputs/4 outputs Relay output 230 V
115 V input (AC)
230 V input (AC)
3RK1 402-3CE00-0AA2
3RK1 402-1CE00-0AC2
3RK1 402-1CE01-0AC2
Slave type
Standard slaves
Operational voltage in accordance with AS-Interface specification in V
26.5 ... 31.6
Total current input in mA
≤ 270
Input connection
PNP
≤ 100
Inputs • Sensor supply via AS-Interface
Short-circuit and overload-proof
–
• Voltage range in V
20 ... 30
–
• Load rating for sensor supply in mA
200
–
• Connection of sensors
2- and 3-wire system
2-wire system
• Switching level High in V
≥ 10
≥ AC 79 / ≤ AC135
• Input current Low/High in mA
≤1.5/≥ 5
≤1.5/≥ 6
≥ AC 164 / ≤ AC 255
Outputs • Type of output
Relay
• Current carrying capacity in A DC 12 / DC 13 typ. (total current for all outputs 4 A)
–
• Ith
5
• AC-15
3
• DC 13 24 V
1
• DC 13 110 V
0.2
• DC 13 230 V
0,1
• Short-circuit protection external back-up fuse 6 A gL/gG
• Inductive interference protection not applicable
• Polarity reversal protection
–
• External voltage supply DC 24 V not applicable
Watchdog built-in
I/O configuration
7
ID/ID2 code
0/F
F/F
Assignment of data bits • Data bit D0
IN1/OUT1
• Data bit D1
IN2/OUT2
• Data bit D2
IN3/OUT3
• Data bit D3
IN4/OUT4
AS-Interface certificate yes
Approvals
UL, CSA, ship building
Protection
IP 20
Ambient temperature in °C
–25 ... +70
Storage temperature in °C
–40 ... +85
Weight in g approx. 290 in preparation
–25 ... +60
Displays • Inputs/outputs yellow LED
• AS-Interface green LED
• FAULT red LED
Connection via screw terminal
Note
To supply the output circuit, an external supplementary supply (AUX POWER) of DC 20 to 30 V is necessary. The supplementary supply must comply with VDE 0106 (PELV), safety class III.
Siemens Energy & Automation, Inc. Industrial Controls Catalog
16/85
Page 9
16_Sec (065-096).qxd
07/28/03
03:24 PM
Page 16/86
Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine
■ Technical data 4 inputs/ 3 outputs PNP transistor 2A 3RK2 400-1FE00-0AA2 Slave type
A/B slaves
Operational voltage in accordance with AS-Interface specification in V
26.5 ... 31.6
Total current input in mA
≤ 270
Input connection
PNP
Inputs • Sensor supply via AS-Interface
Short-circuit and overload-proof
• Voltage range in V
20 ... 30
• Load rating for sensor supply in mA
200
• Connection of sensors
2- and 3-wire system
• Switching level High in V
≥ 10
• Input current Low/High in mA
≤1.5/≥ 5
Outputs • Type of output
Electronics
• Current carrying capacity in A DC 12 / DC 13 typ. (total current for all outputs 4 A)
2
• Ith
–
• AC-15
–
• DC 13 24 V
–
• DC 13 110 V
–
• DC 13 230 V
–
• Short-circuit protection built-in
• Inductive interference protection built-in
• Polarity reversal protection built-in
• External voltage supply DC 24 V
Terminal 13 = L24+ Terminal 19 = M24
Watchdog built-in
I/O configuration
7
ID/ID2 code
A/0
Assignment of data bits • Data bit D0
IN1/OUT1
• Data bit D1
IN2/OUT2
• Data bit D2
IN3/OUT3
• Data bit D3
IN4
AS-Interface certificate in preparation
Approvals
UL, CSA, ship building
Protection
IP 20
Ambient temperature in °C
–25 ... +70
Storage temperature in °C
–40 ... +85
Weight in g approx. 280
Displays • Inputs/outputs yellow LED
• AS-Interface green LED
• FAULT red LED
Connection via screw terminal
Note
To supply the output circuit, an external supplementary supply (AUX POWER) of DC 20 to 30 V is necessary. The supplementary supply must comply with VDE 0106 (PELV), safety class III.
16/86
Siemens Energy & Automation, Inc. Industrial Controls Catalog
Page 10
16_Sec (065-096).qxd
07/28/03
03:24 PM
Page 16/87
Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine
■ Technical data SlimLine S45 with Cage Clamp terminals 4 inputs/4 outputs PNP transistor 1A
2A
1 A, floating I/Os
3RK1 400-1CG00-0AA2
3RK1 400-1CG01-0AA2
3RK1 402-3CG01-0AA2
Slave type Operational voltage in accordance with AS-Interface specification in V Total current input in mA Input connection Inputs • Sensor supply via AS-Interface • Voltage range in V • Load rating for sensor supply in mA • Connection of sensors • Switching level High in V • Input current Low/High in mA Outputs • Type of output • Current carrying capacity in A DC 12 / DC 13 typ. (total current for all outputs 4 A) • Ith • AC-15 • DC 13 24 V • DC 13 110 V • DC 13 230 V • Short-circuit protection • Inductive interference protection • Polarity reversal protection • External voltage supply DC 24 V
Standard slaves 26.5 ... 31.6
Watchdog I/O configuration ID/ID2 code Assignment of data bits • Data bit D0 • Data bit D1 • Data bit D2 • Data bit D3 AS-Interface certificate Approvals Protection Ambient temperature in °C Storage temperature in °C Weight in g Displays • Inputs/outputs • AS-Interface • FAULT Connection Conductor cross-sections in mm2 built-in 7 0/F
Note 1 Note 2
Note 3
Siemens Energy & Automation, Inc. Industrial Controls Catalog
≤ 270 PNP
≤40
Short-circuit and overload-proof 20 ... 30 200 2- and 3-wire system ≥ 10 ≤1.5/≥ 5 Electronics 1 – – – – – built-in – built-in Terminal 13 = L24+ Terminal 19 = M24
2
1 no (internal fusible link)
built-in built-in Sensor supply: Terminal 13 = U_s+ Terminal 19 = U_s– Actuator supply: Terminal 14 = L+ Terminals 20 ... 24 = M
IN1/OUT1 IN2/OUT2 IN3/OUT3 IN4/OUT4 yes UL, CSA, ship building IP 20 –25 ... +70 –40 ... +85 approx. 280 yellow LED green LED red LED Cage Clamp terminals solid: 2 × (0.25-1.5) finely stranded with end sleeve: 2 × (0.25-1) finely stranded without end sleeve: 2 × (0.25-1.5) AWG conductors, solid or stranded: AWG 2 × (24-16) Opening tool for Cage Clamp terminals: See accessories To supply the output circuit, an external supplementary supply (AUX POWER) of DC 20 to 30 V is necessary. The supplementary supply must comply with VDE 0106 (PELV), safety class III. – The module has four floating inputs and four floating switching outputs. For the input and output circuits, an external additional supply of 20 to 30 V according to VDE 0106 (PELV) safety class III is required.
16/87
Page 11
16_Sec (065-096).qxd
07/28/03
03:24 PM
Page 16/88
Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine
■ Technical data 4 inputs/4 outputs
4 inputs/ 3 outputs
Relay output 230 V 3RK1 402-3CG00-0AA2
3RK2 400-1FG00-0AA2
Slave type
Standard slaves
A/B slaves
Operational voltage in accordance with AS-Interface specification in V
26.5 ... 31.6
Total current input in mA
≤ 270
Input connection
PNP
Inputs • Sensor supply via AS-Interface
Short-circuit and overload-proof
• Voltage range in V
20 ... 30
• Load rating for sensor supply in mA
200
• Connection of sensors
2- and 3-wire system
• Switching level High in V
≥ 10
• Input current Low/High in mA
≤1.5/≥ 5
Outputs • Type of output
Relay
Electronics
• Current carrying capacity in A DC 12 / DC 13 typ. (total current for all outputs 4 A)
–
2
• Ith
5
–
• AC-15
3
–
• DC 13 24 V
1
–
• DC 13 110 V
0.2
–
• DC 13 230 V
0,1
–
• Short-circuit protection external back-up fuse 6 A gL/gG built-in
• Inductive interference protection not applicable built-in
• Polarity reversal protection built-in
• External voltage supply DC 24 V not applicable
Watchdog built-in
I/O configuration
7
ID/ID2 code
0/F
Terminal 13 = L24+ Terminal 19 = M24
A/E
Assignment of data bits • Data bit D0
IN1/OUT1
• Data bit D1
IN2/OUT2
• Data bit D2
IN3/OUT3
• Data bit D3
IN4/OUT4
IN4
AS-Interface certificate yes in preparation
Approvals
UL, CSA, ship building
Protection
IP 20
Ambient temperature in °C
–25 ... +70
Storage temperature in °C
–40 ... +85
–
Weight in g approx. 290 approx. 280
Displays • Inputs/outputs yellow LED
• AS-Interface green LED
• FAULT red LED
Connection
Cage Clamp terminals
Conductor cross-sections in mm2 solid: 2 × (0.25-1.5) finely stranded with end sleeve: 2 × (0.25-1) finely stranded without end sleeve: 2 × (0.25-1.5) AWG conductors, solid or stranded: AWG 2 × (24-16)
Note 1
Opening tool for Cage Clamp terminals: See accessories
Note 2
To supply the output circuit, an external supplementary supply (AUX POWER) of DC 20 to 30 V is necessary. The supplementary supply must comply with VDE 0106 (PELV), safety class III.
16/88
Siemens Energy & Automation, Inc. Industrial Controls Catalog
Page 12
16_Sec (065-096).qxd
07/28/03
03:24 PM
Page 16/89
Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine
■ Dimension drawings SlimLine S22.5 with screw-type terminals 22,5 15
5
30
60
SlimLine S22.5 with Cage Clamp terminals 86
8
110 120
22,5
5
Address socket
5
Designation plate
Siemens Energy & Automation, Inc. Industrial Controls Catalog
86,1
SlimLine S45 with Cage Clamp terminals
84,2 107,6
102
SlimLine S45 with screw-type terminals
45
Nameplate
Designation plate
NSA00071a
102 82 62
55,8 83,3
Address socket
92
45
Nameplate
5
86,4
16/89