Page 7

16_Sec (065-096).qxd

07/28/03

03:24 PM

Page 16/84

Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine

■ Technical data SlimLine S45 with screw-type terminals 4 inputs/4 outputs PNP transistor 1A 3RK1 400-1CE00-0AA2 Slave type

Standard slaves

Operational voltage in accordance with AS-Interface specification in V

26.5 ... 31.6

Total current input in mA

≤ 270

Input connection

PNP

2A 3RK1 400-1CE01-0AA2

1 A, floating 3RK1 402-3CE01-0AA2

≤40

Inputs • Sensor supply via AS-Interface

Short-circuit and overload-proof

• Voltage range in V

20 ... 30

• Load rating for sensor supply in mA

200

• Connection of sensors

2- and 3-wire system

• Switching level High in V

≥ 10

• Input current Low/High in mA

≤1.5/ ≥ 5

Outputs • Type of output

Electronics

• Current carrying capacity in A DC 12 / DC 13 typ. (total current for all outputs 4 A)

1

• Ith

–

• AC-15

–

• DC 13 24 V

–

• DC 13 110 V

–

• DC 13 230 V

–

• Short-circuit protection built-in

• Inductive interference protection built-in

• Polarity reversal protection built-in

• External voltage supply DC 24 V

Terminal 13 = L24+ Terminal 19 = M24

Watchdog built-in

I/O configuration

7

ID/ID2 code

0/F

2

1

Sensor supply: Terminal 13 = U_s+ Terminal 19 = U_s– Actuator supply: Terminal 14 = L+ Terminals 20 to 24 = M

Assignment of data bits • Data bit D0

IN1/OUT1

• Data bit D1

IN2 /OUT2

• Data bit D2

IN3/OUT3

• Data bit D3

IN4/OUT4

AS-Interface certificate yes

Approvals

UL, CSA, ship building

Protection

IP 20

Ambient temperature in °C

–25 ... +70

Storage temperature in °C

–40 ... +85

Weight in g approx. 280

Displays • Inputs/outputs yellow LED

• AS-Interface green LED

• FAULT red LED

Connection via screw terminal

Note 1

–

Note 2

To supply the output circuit, an external supplementary supply (AUX POWER) of DC 20 to 30 V is necessary. The supplementary supply must comply with VDE 0106 (PELV), safety class III.

16/84

The module has four floating inputs and four floating switching outputs. For the input and output circuits, an external additional supply of 20 to 30 V according to VDE 0106 (PELV) safety class III is required.

Siemens Energy & Automation, Inc. Industrial Controls Catalog

Page 8

16_Sec (065-096).qxd

07/28/03

03:24 PM

Page 16/85

Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine

■ Technical data 4 inputs/4 outputs Relay output 230 V

115 V input (AC)

230 V input (AC)

3RK1 402-3CE00-0AA2

3RK1 402-1CE00-0AC2

3RK1 402-1CE01-0AC2

Slave type

Standard slaves

Operational voltage in accordance with AS-Interface specification in V

26.5 ... 31.6

Total current input in mA

≤ 270

Input connection

PNP

≤ 100

Inputs • Sensor supply via AS-Interface

Short-circuit and overload-proof

–

• Voltage range in V

20 ... 30

–

• Load rating for sensor supply in mA

200

–

• Connection of sensors

2- and 3-wire system

2-wire system

• Switching level High in V

≥ 10

≥ AC 79 / ≤ AC135

• Input current Low/High in mA

≤1.5/≥ 5

≤1.5/≥ 6

≥ AC 164 / ≤ AC 255

Outputs • Type of output

Relay

• Current carrying capacity in A DC 12 / DC 13 typ. (total current for all outputs 4 A)

–

• Ith

5

• AC-15

3

• DC 13 24 V

1

• DC 13 110 V

0.2

• DC 13 230 V

0,1

• Short-circuit protection external back-up fuse 6 A gL/gG

• Inductive interference protection not applicable

• Polarity reversal protection

–

• External voltage supply DC 24 V not applicable

Watchdog built-in

I/O configuration

7

ID/ID2 code

0/F

F/F

Assignment of data bits • Data bit D0

IN1/OUT1

• Data bit D1

IN2/OUT2

• Data bit D2

IN3/OUT3

• Data bit D3

IN4/OUT4

AS-Interface certificate yes

Approvals

UL, CSA, ship building

Protection

IP 20

Ambient temperature in °C

–25 ... +70

Storage temperature in °C

–40 ... +85

Weight in g approx. 290 in preparation

–25 ... +60

Displays • Inputs/outputs yellow LED

• AS-Interface green LED

• FAULT red LED

Connection via screw terminal

Note

To supply the output circuit, an external supplementary supply (AUX POWER) of DC 20 to 30 V is necessary. The supplementary supply must comply with VDE 0106 (PELV), safety class III.

Siemens Energy & Automation, Inc. Industrial Controls Catalog

16/85

Page 9

16_Sec (065-096).qxd

07/28/03

03:24 PM

Page 16/86

Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine

■ Technical data 4 inputs/ 3 outputs PNP transistor 2A 3RK2 400-1FE00-0AA2 Slave type

A/B slaves

Operational voltage in accordance with AS-Interface specification in V

26.5 ... 31.6

Total current input in mA

≤ 270

Input connection

PNP

Inputs • Sensor supply via AS-Interface

Short-circuit and overload-proof

• Voltage range in V

20 ... 30

• Load rating for sensor supply in mA

200

• Connection of sensors

2- and 3-wire system

• Switching level High in V

≥ 10

• Input current Low/High in mA

≤1.5/≥ 5

Outputs • Type of output

Electronics

• Current carrying capacity in A DC 12 / DC 13 typ. (total current for all outputs 4 A)

2

• Ith

–

• AC-15

–

• DC 13 24 V

–

• DC 13 110 V

–

• DC 13 230 V

–

• Short-circuit protection built-in

• Inductive interference protection built-in

• Polarity reversal protection built-in

• External voltage supply DC 24 V

Terminal 13 = L24+ Terminal 19 = M24

Watchdog built-in

I/O configuration

7

ID/ID2 code

A/0

Assignment of data bits • Data bit D0

IN1/OUT1

• Data bit D1

IN2/OUT2

• Data bit D2

IN3/OUT3

• Data bit D3

IN4

AS-Interface certificate in preparation

Approvals

UL, CSA, ship building

Protection

IP 20

Ambient temperature in °C

–25 ... +70

Storage temperature in °C

–40 ... +85

Weight in g approx. 280

Displays • Inputs/outputs yellow LED

• AS-Interface green LED

• FAULT red LED

Connection via screw terminal

Note

To supply the output circuit, an external supplementary supply (AUX POWER) of DC 20 to 30 V is necessary. The supplementary supply must comply with VDE 0106 (PELV), safety class III.

16/86

Siemens Energy & Automation, Inc. Industrial Controls Catalog

Page 10

16_Sec (065-096).qxd

07/28/03

03:24 PM

Page 16/87

Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine

■ Technical data SlimLine S45 with Cage Clamp terminals 4 inputs/4 outputs PNP transistor 1A

2A

1 A, floating I/Os

3RK1 400-1CG00-0AA2

3RK1 400-1CG01-0AA2

3RK1 402-3CG01-0AA2

Slave type Operational voltage in accordance with AS-Interface specification in V Total current input in mA Input connection Inputs • Sensor supply via AS-Interface • Voltage range in V • Load rating for sensor supply in mA • Connection of sensors • Switching level High in V • Input current Low/High in mA Outputs • Type of output • Current carrying capacity in A DC 12 / DC 13 typ. (total current for all outputs 4 A) • Ith • AC-15 • DC 13 24 V • DC 13 110 V • DC 13 230 V • Short-circuit protection • Inductive interference protection • Polarity reversal protection • External voltage supply DC 24 V

Standard slaves 26.5 ... 31.6

Watchdog I/O configuration ID/ID2 code Assignment of data bits • Data bit D0 • Data bit D1 • Data bit D2 • Data bit D3 AS-Interface certificate Approvals Protection Ambient temperature in °C Storage temperature in °C Weight in g Displays • Inputs/outputs • AS-Interface • FAULT Connection Conductor cross-sections in mm2 built-in 7 0/F

Note 1 Note 2

Note 3

Siemens Energy & Automation, Inc. Industrial Controls Catalog

≤ 270 PNP

≤40

Short-circuit and overload-proof 20 ... 30 200 2- and 3-wire system ≥ 10 ≤1.5/≥ 5 Electronics 1 – – – – – built-in – built-in Terminal 13 = L24+ Terminal 19 = M24

2

1 no (internal fusible link)

built-in built-in Sensor supply: Terminal 13 = U_s+ Terminal 19 = U_s– Actuator supply: Terminal 14 = L+ Terminals 20 ... 24 = M

IN1/OUT1 IN2/OUT2 IN3/OUT3 IN4/OUT4 yes UL, CSA, ship building IP 20 –25 ... +70 –40 ... +85 approx. 280 yellow LED green LED red LED Cage Clamp terminals solid: 2 × (0.25-1.5) finely stranded with end sleeve: 2 × (0.25-1) finely stranded without end sleeve: 2 × (0.25-1.5) AWG conductors, solid or stranded: AWG 2 × (24-16) Opening tool for Cage Clamp terminals: See accessories To supply the output circuit, an external supplementary supply (AUX POWER) of DC 20 to 30 V is necessary. The supplementary supply must comply with VDE 0106 (PELV), safety class III. – The module has four floating inputs and four floating switching outputs. For the input and output circuits, an external additional supply of 20 to 30 V according to VDE 0106 (PELV) safety class III is required.

16/87

Page 11

16_Sec (065-096).qxd

07/28/03

03:24 PM

Page 16/88

Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine

■ Technical data 4 inputs/4 outputs

4 inputs/ 3 outputs

Relay output 230 V 3RK1 402-3CG00-0AA2

3RK2 400-1FG00-0AA2

Slave type

Standard slaves

A/B slaves

Operational voltage in accordance with AS-Interface specification in V

26.5 ... 31.6

Total current input in mA

≤ 270

Input connection

PNP

Inputs • Sensor supply via AS-Interface

Short-circuit and overload-proof

• Voltage range in V

20 ... 30

• Load rating for sensor supply in mA

200

• Connection of sensors

2- and 3-wire system

• Switching level High in V

≥ 10

• Input current Low/High in mA

≤1.5/≥ 5

Outputs • Type of output

Relay

Electronics

• Current carrying capacity in A DC 12 / DC 13 typ. (total current for all outputs 4 A)

–

2

• Ith

5

–

• AC-15

3

–

• DC 13 24 V

1

–

• DC 13 110 V

0.2

–

• DC 13 230 V

0,1

–

• Short-circuit protection external back-up fuse 6 A gL/gG built-in

• Inductive interference protection not applicable built-in

• Polarity reversal protection built-in

• External voltage supply DC 24 V not applicable

Watchdog built-in

I/O configuration

7

ID/ID2 code

0/F

Terminal 13 = L24+ Terminal 19 = M24

A/E

Assignment of data bits • Data bit D0

IN1/OUT1

• Data bit D1

IN2/OUT2

• Data bit D2

IN3/OUT3

• Data bit D3

IN4/OUT4

IN4

AS-Interface certificate yes in preparation

Approvals

UL, CSA, ship building

Protection

IP 20

Ambient temperature in °C

–25 ... +70

Storage temperature in °C

–40 ... +85

–

Weight in g approx. 290 approx. 280

Displays • Inputs/outputs yellow LED

• AS-Interface green LED

• FAULT red LED

Connection

Cage Clamp terminals

Conductor cross-sections in mm2 solid: 2 × (0.25-1.5) finely stranded with end sleeve: 2 × (0.25-1) finely stranded without end sleeve: 2 × (0.25-1.5) AWG conductors, solid or stranded: AWG 2 × (24-16)

Note 1

Opening tool for Cage Clamp terminals: See accessories

Note 2

To supply the output circuit, an external supplementary supply (AUX POWER) of DC 20 to 30 V is necessary. The supplementary supply must comply with VDE 0106 (PELV), safety class III.

16/88

Siemens Energy & Automation, Inc. Industrial Controls Catalog

Page 12

16_Sec (065-096).qxd

07/28/03

03:24 PM

Page 16/89

Actuator-Sensor-Interface I/O Modules for Operation in the Control Cabinet (IP 20) SlimLine

■ Dimension drawings SlimLine S22.5 with screw-type terminals 22,5 15

5

30

60

SlimLine S22.5 with Cage Clamp terminals 86

8

110 120

22,5

5

Address socket

5

Designation plate

Siemens Energy & Automation, Inc. Industrial Controls Catalog

86,1

SlimLine S45 with Cage Clamp terminals

84,2 107,6

102

SlimLine S45 with screw-type terminals

45

Nameplate

Designation plate

NSA00071a

102 82 62

55,8 83,3

Address socket

92

45

Nameplate

5

86,4

16/89