Page 117

Error Squared Control

When error squared control is selected, the error (en) is calculated as:

Since en =< e, a loop using the error squared is less responsive than a loop using just the error. In fact, the smaller the error, the less responsive the loop. Error squared control would typically be used in a PH control application.

Error Deadband Control

When error deadband control is selected and YDEV is the yellow deviation alarm limit, the error is calculated as:

-

With error deadband control, no control action is taken if the PV is within the yellow deadband area around the setpoint.

SIMATIC TI560T/TI565T Technical Product Description

Loop Operation

B-17

Page 118

Special Computations on Output, PV, or Error (continued) Derivative Gain

There are many applications where the process dynamics call for the stabilization and braking action of derivative control. The applications are prevented from using the derivative control because of noise on the process variable signal. If the process variable signal contains rapidly varying noise spikes of small amplitude, then the derivative term effectively amplifies those noise pulses and passes them directly to the output device. The Derivative Gain Limiting option on the TI565T addresses this problem and allows the use of derivative control action in many cases. This option allows the user to specify a filter coefficient Kd which is also known as the Derivative Gain Limiting coefficient. When derivative gain limiting is used, the TI565T loop calculation is modified as follows: Position PID Algorithm - -

-

-

Velocity PID Algorithm - -

-

- -

This effectively places a first-order filter on the derivative term, with a time constant of Kd sample times. The default value of Kd is 10, so then if the loop sample time were 0.5 sec., this would result in a net filter time constant of 5 seconds. Since this definition takes into account the loop sample time and only affects the derivative term the default value of Kd = 10 is probably good for almost all applications requiring derivative control.

B-18

Loop Operation

SIMATIC TI560T/TI565T Technical Product Description

Page 119

Ramp/Soak

For each loop, the TI565T allows the user to program a RAMP/SOAK table to indicate how the setpoint is to change with time. A RAMP/SOAK table consists of entries called steps: there are two types. In a RAMP step, the setpoint is changed from its current value to a user-specified final value at a user-specified rate. In a SOAK step, the setpoint is held constant for a user-specified period of time. For a SOAK step, the user may also specify that guaranteed soaking is desired by specifying a deadband around the setpoint. The Process Variable must be within this deadband limit of the setpoint in order for SOAK time to be measured.

SF Programming

At various points in the execution of a loop, the TI565T will allow the user to break out of the normal loop execution sequence to perform his own processing. The mechanism provided is through SF Programs. An SF Program is a sequence of BASIC-like statements that allow the user to manipulate TI560T or TI565T variables, including all of the parameters to a loop. The points in the execution of a loop in which an SF Program may be invoked 1.

After reading and performing any indicated conditioning on the Process Variable. This type of SF Program would typically be used to perform filtering on the Process Variable. (SF on PV).

2.

Before using the Setpoint to compute the error. This type of SF Program would typically be used in a ratio-control application. (SF on SP).

3.

Before storing the output. (SF on output).

SIMATIC TI560T/TI565T Technical Product Description

Loop Operation

B-19

Page 120

SIMATIC is a trademark of Siemens AG. APT, CVU, PM550C, Series 500, Series 505, 5TI, TISOFT, TISTAR, TIWAY, PEERLINK, and Unilink are trademarks of Siemens Industrial Automation, Inc. TI500, TI505, TI520, TI525, TI520C, TI530, TI530C, TI535, TI560, TI560T, TI565, and TI565T are trademarks of Texas Instruments. IBM, AT, and PS/2 are registered trademarks of International Business Machines Corporation. United Laboratories Inc. is a registered trademark of Underwriters Laboratories Inc. Honeywell is a registered trademark of Honeywell Inc.

Page 121

Customer Registration

We would like to know what you think about our user manuals so that we can serve you better. How would you rate the quality of our manuals? Excellent

Good

Fair

Poor

Accuracy Organization Clarity Completeness Overall design Size Index

Would you be interested in giving us more detailed comments about our manuals?

Yes! Please send me a questionnaire. No. Thanks anyway.

Your Name: Title: Telephone Number:

(

)

Company Name: Company Address:

Manual Name:

SIMATIC TI560T/TI565T Technical Product Description

Manual Assembly Number: 2597773–0033 Order Number:

PPX:560/565–8107–3

Edition:

Third

Date:

11/93

Page 122

FOLD NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES

BUSINESS REPLY MAIL FIRST CLASS

PERMIT NO.3

JOHNSON CITY, TN

POSTAGE WILL BE PAID BY ADDRESSEE

ATTN: Technical Communications M/S 3519 SIEMENS INDUSTRIAL AUTOMATION INC. 3000 BILL GARLAND RD P O BOX 1255 JOHNSON CITY TN 37605–1255

FOLD