Manual · Siemens
SIMATIC TI560T/TI565T Technical Product Description
Manual122 pagesPDF 565 KB
Technical product description of the Siemens SIMATIC TI560T and TI565T programmable controllers, with their TI505 and TI500 I/O.
What this file really is
The old site listed this file as a manual for the Siemens 500-5008 and Texas Instruments 500-5008. This is the technical product description of the TI560T/TI565T controllers; the 500-5008 (a 14 VDC input module) appears only as one line in its TI500 I/O module table.
Filed with · 2 models
Also filed with these models on the old site
Summary
What is in it
Siemens Industrial Automation technical product description for the SIMATIC TI560T and TI565T programmable controller CPU models. It gives an overview of the system, programming with TISOFT and APT, networking and operator interfaces, then describes each controller's chassis, power supply, CPU cards, memory, ladder logic and special function programming, PID loops and analog alarms, hot backup and diagnostics, system configuration with TI505 and TI500 I/O modules, specifications and performance figures.
Its parts
- Overview
- TI560T
- TI565T
- Hot Backup and System Diagnostics
- System Configuration
- Performance
- Loop Operation
From the manual
Key facts from this manual
Each line names its page in the PDF.
Siemens technical product description, third edition of November 1993, for the SIMATIC TI560T and TI565T programmable controllers. It describes the chassis, power supplies, CPU, memory, remote channel controller and Hot Backup cards, diagnostics and specifications, and lists the TI500 and TI505 I/O modules used with these controllers, among them the 14 VDC Input module PPX:500-5008, which appears only in that list.
- 500-5008 module
- PPX:500-5008: TI500 14 VDC Input module for the TI560T/TI565T, 1.0 watt of +5 V p. 90
- Controllers
- SIMATIC TI560T and TI565T, MC68000-based, card-and-rack architecture p. 15
- I/O capacity
- TI560T: up to 8192 I/O points p. 25
- Memory
- 176K words on the Main CPU, up to 512K words with memory cards; 64K Word Memory Expansion Card PPX:560–2130 p. 25, 43
- TI565T additions
- SF CPU Card PPX:565–2120: up to 64 PID loops, 128 analog alarms, Special Function programs p. 15, 62
- Chassis
- 19-inch rack-mount, 8 card slots; power supply at far left, Main CPU in the first slot p. 26
- Power input
- 85 to 132 VAC, 170 to 260 VAC, or 20.4 to 30 VDC; 300 VA max.; 47 to 63 Hz; fuse 5 A/250 VAC p. 93
- Power output
- AC supply 112.5 watts; DC supply 147.5 watts p. 27
- Battery
- Lithium 1/2 gram, non-rechargeable; 6 months typical memory backup; 3 years typical shelf life p. 93
- Remote channel cards
- RF RCC: 2048 I/O points, 15000-ft channel; twisted pair RCC PPX:560–2127: 2048 I/O points, 3000-ft channel p. 43
- Hot Backup
- Hot Backup Card PPX:560–2128 (two needed) or upgrade kit PPX:560–2129; gives redundancy of CPU, memory, power supply and RCCs p. 15, 43
- Remote I/O bases
- PPX:500–5892 6-slot, PPX:500–5884 12-slot (19-inch rack), PPX:500–5848 14-slot; RBC PPX:500–2114; base power supply PPX:500–2151–A p. 84
- Environment
- 0 to 60°C operating; -40 to +85°C storage; 5% to 95% humidity, noncondensing p. 93
- CPU ports
- Local RS–232–C and RS–422 ports on the Main CPU card p. 28
What this manual walks you through
- System overview and layout p. 13, 14
- Choosing the components for a TI560T controller p. 43
- Choosing the components for a TI565T controller p. 62
- Fatal and non-fatal error messages p. 71
- Troubleshooting with the card LEDs p. 78, 79
- Remote I/O bases, base controllers and power supplies p. 84, 85
- TI505 I/O modules and their power use p. 87, 88
- TI500 I/O modules and their power use p. 90, 91
- Planning the CATV remote I/O cable p. 92
- Environmental and power supply specifications p. 93
Good to know
- This is a reference description, not an installation guide; setup and operation are in the TI560T/TI565T System Manual (PPX:560/565–8105–x). p. 11
- The Main CPU card must sit in the far left slot next to the power supply. p. 28
- Individual cards have no battery backup of their own. p. 27
- Signal loss between the RCC and any I/O base should be under 55 dB, and the CATV cable should carry no other traffic. p. 92
Questions this manual answers
What is the Siemens / TI 500-5008 module?
PPX:500-5008 is a 14 VDC Input module in the TI500 I/O line used with the TI560T/TI565T; it draws 1.0 watt of +5 V power. p. 90
What is the difference between the TI560T and TI565T?
The TI565T is a TI560T with a Special Function CPU card added, which runs PID loops, analog alarms and Special Function programs. p. 15
How far from the TI560T can remote I/O bases be?
Up to 15,000 ft over CATV cable; RS–485 media allows up to 3,300 ft, depending on the number of taps. p. 92
How much memory does a TI560T have?
176K words on the Main CPU, expandable to 512K words with memory cards. p. 25
What battery does the TI560T/TI565T power supply use?
A non-rechargeable 1/2 gram lithium battery, giving about 6 months of memory backup. p. 93
Contents
Chapters and sections
Each line opens the PDF at its page.
24 more lines, from page 70 on
The whole text · 14 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Title1-4
- Contents5-10
- Pages 11 to 2311-23
- 2 TI560T, pages 24 to 3324-33
- 2 TI560T, pages 34 to 4334-43
- 3 TI565T, pages 44 to 5344-53
- 3 TI565T, pages 54 to 6254-62
- 4 Hot Backup and System Diagnostics, pages 63 to 7163-71
- 4 Hot Backup and System Diagnostics, pages 72 to 7972-79
- 5 System Configuration80-93
- A Performance94-100
- B Loop Operation, pages 101 to 108101-108
- B Loop Operation, pages 109 to 116109-116
- B Loop Operation, pages 117 to 122117-122
The file