Page 24

Chapter 2

TI560T 2.1

TI560T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-2

Advantages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-2 2-2

2.2

Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-3

2.3

Chassis Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-4

2.4

Main CPU Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-5

2.5

CPU Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-6

TI560T CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I/O Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ladder Logic Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Intelligent Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communication Port Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Hot Backup Unit Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-6 2-6 2-7 2-7 2-7 2-7

Memory Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-8

Memory Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-9

Remote Channel Controller Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-11

Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-12

Ladder Logic Instruction Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-13

Instruction Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-13

TI560T Controller Component List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2-20

2.6

2.7

2.8

2.9

SIMATIC TI560T/TI565T Technical Product Description

TI560T

2-1

Page 25

2.1

TI560T

Advantages

The TI560T satisfies your application requirements for a high number of I/O points (8192) with quick, reliable performance. Additionally, the TI560T is compatible with Siemens’ other TI500/TI505 products, which enables you to select from a full product line to customize your application.

Features

The TI560T offers high-level instruction boxes, such as multiplication and division, timers and counters, and word moves. Using the instruction boxes for these functions both eliminates the unnecessary use of memory to program individual steps and saves valuable programming time. You can select the memory size you need, from the 176K words resident on the CPU to a total of 512K words, with the addition of memory cards. The remote I/O provides a connect distance of up to 15,000 feet from the controller. The Hot Backup option is available for critical operations requiring minimum unscheduled process down time. The TI560T or TI565T chassis is a 19-inch, rack-mountable housing which can accommodate up to eight cards. The chassis contains a backplane to which the system cards are physically connected. The system power supply is mounted in the far left side of the chassis and does not occupy any of the 8 slots available for cards. The first slot next to the power supply is reserved for the Main CPU card. The remaining slots can be used for memory expansion, I/O expansion, SF CPU option, and the Hot Backup option.

2-2

TI560T

SIMATIC TI560T/TI565T Technical Product Description

Page 26

2.2

Chassis The TI560T or TI565T chassis (Figure 2-1) is a 19-inch, rack-mountable housing which can accommodate up to eight cards. The chassis contains a backplane to which the system cards are physically connected. The system power supply is mounted in the far left side of the chassis and does not occupy any of the 8 slots available for cards. The first slot next to the power supply is reserved for the Main CPU card. The remaining slots can be used for memory expansion, I/O expansion, SF CPU option, and the Hot Backup option.

Figure 2-1 TI560T/TI565T Chassis

SIMATIC TI560T/TI565T Technical Product Description

TI560T

2-3

Page 27

2.3

Chassis Power Supply The TI560T or TI565T chassis power supply is a plug-in module which resides in the left side of the chassis. (See Figure 2-2.) You may select either a 110/220 VAC or a 24 VDC power supply. This module supplies power to all the cards in the chassis. Use the PPX:560T–2125 chassis with the 24 volt power supply and the PPX:560T–2124 chassis with the 110/220 volt power supply. The AC power supply provides 112.5 watts of total power to the system and up to 1 amp of battery backup power. Individual cards do not have battery backup. The DC power supply affords 147.5 watts of total power to the system. A memory-protect lock, power LED, and battery status LED are located on the front panel of the power supply. The battery on/off switch, battery, AC power connection, and fuse are also accessible through the front panel. Selection of 110 VAC or 220 VAC is done via an internal switch.

Power Supply

Figure 2-2 TI560T/TI565T Power Supply Location

2-4

TI560T

SIMATIC TI560T/TI565T Technical Product Description

Page 28

2.4

Main CPU Card The Main CPU card is MC68000 microprocessor-based and contains 176K words of system memory along with 49,152 local control relay bits. This CPU acts as the central coordinator for the system. It executes relay ladder logic (RLL), schedules I/O updates, processes intelligent I/O module requests, SF CPU card communications, Hot Backup card communications, and the local RS–232–C and RS–422 port communications. The CPU card must be placed in the far left slot adjacent to the power supply (Figure 2-3). The edge connectors are reverse-keyed to prevent the card from being inserted into another slot.

Main CPU

Figure 2-3 TI560T Main CPU Card Placement

SIMATIC TI560T/TI565T Technical Product Description

TI560T

2-5

Page 29

2.5

CPU Functions Figure 2-4 shows the relationship of the sequence of operations performed during a scan.

Cycle

I/O Update

Ladder Execution

Main CPU

RCC Start Update

Diagnostics

Update Complete

I/O Update

HBU Start Update Update Complete

Continuously Communicating with other unit

RLL

Start Access

Intelligent I/O Service

Intel Module Access

Request/ Response

Intel Module Access

Memory Updates from Intelligent Modules Intel Module Complete

Communication Port Service

Comm Port Access

Communication Updates from Operator Interfaces & Programmers Scan Time Check & Acknowledge

Figure 2-4 CPU Scan TI560T CPU

The TI560T CPU requires approximately 11 ms for overhead tasks. This time is distributed throughout each scan.

I/O Cycle

During the I/O cycle update, the Main CPU card runs board-level diagnostics. The RCC card(s) update all output points (discrete, word, and analog) with new values from the last program scan. All input modules are read and transferred to the image register for the next RLL execution. The length of the I/O update cycle corresponds to the RCC card that requires the longest update time. This is primarily dependent upon the number of bases and types of modules (analog, discrete or intelligent) on each channel. Each RCC has two channels which update in parallel. All I/O points are fully updated each scan.

2-6

TI560T

SIMATIC TI560T/TI565T Technical Product Description

Page 30

Ladder Logic Cycle

Upon completion of the I/O update, the Main CPU card starts the execution of the relay ladder logic program. While the program is being executed, the RCCs run background tasks (polling for unconfigured bases and servicing operator interfaces connected at the I/O bases if that RBC has requested service). The Main CPU executes typical relay ladder logic programs in 1.5 milliseconds per K words of program instructions. The entire ladder logic program is fully executed each scan. Execution times for the full range of instructions are given with the Instruction Set listed in Appendix A.

Intelligent Module

Upon completion of the ladder logic scan, the intelligent module communications begin. The Main CPU executes task codes gathered from the intelligent modules by the RCC. This information is made available to the RCCs for transfer back to the intelligent modules in the I/O bases. The RCCs start diagnostics when the transfer of SF module information is complete. Each intelligent module that requires service during this period adds scan time according to the type of module and the type of task. Each type of module is allowed a certain number of task code requests, block transfers, or store-and-forward operations per scan. Once these are completed, the SF cycle is terminated by the RCC card.

Communication Port Service

The communication period consists of three 2-millisecond time slots to service the two communications ports on the Main CPU and all communication ports located on all RBCs. Each time slot is allocated approximately 2 milliseconds, with a maximum of 6.0 milliseconds available. Four communication tasks are serviced in the three time slots such that at any given time two of the four communication tasks being performed are from the local ports. The other two tasks being performed are from the remote ports on a time-share basis. If only one port has activity, then all three time slots will be allocated to that port.

Hot Backup Unit Communications

During all of the above periods, the HBU transmits messages between the TI560T or TI565T systems (with standby unit on-line). The HBU adds approximately 9.0 milliseconds for TI560T operation and approximately 1 to 4 ms additional for TI565T updates.

SIMATIC TI560T/TI565T Technical Product Description

TI560T

2-7

Page 31

2.6

Memory Cards The TI560T system comes with 176K words of memory resident on the Main CPU card. Additional memory cards can be installed. (See Figure 2-5.) Memory cards may be placed anywhere in the TI560T or TI565T chassis, excluding the slot adjacent to the power supply where the Main CPU must be positioned. The TI560T or TI565T system is capable of storing 512K words of user memory. Additional memory can be purchased in card sizes of 64K or 256K words.

Memory Card

Figure 2-5 TI560T/TI565T with Additional Memory Card

2-8

TI560T

SIMATIC TI560T/TI565T Technical Product Description

Page 32

Memory Types

L-memory is used for ladder logic, V-memory is used for variable memory (changeable from ladder logic), K-memory is used for constant memory (changeable only from task codes), and S-memory is used with the SF CPU for PID loops, analog alarms, special function programs, and special function subroutines. Memory Allocation

System memory is user-configurable. L-, V-, K-, and S-memory allocations can be set or altered with a TISOFT programming device. This allows an optimum memory configuration for any application. And, the user can expand memory type capacities without affecting program integrity. Additional memory space is allocated without damage to existing programs. Ladder logic program code is stored in both source code and compiled code. For this reason, the total amount of L-memory required will be 3X the amount of ladder logic program code. Also note in the tables that memory allocation is displayed in K bytes rather than words (2K bytes = 1K word).

SIMATIC TI560T/TI565T Technical Product Description

TI560T

2-9

Page 33

Memory Cards (continued) Table 2-1 lists the minimum and maximum memory configuration for the TI560T/TI565T controllers. Table 2-1 CPU Card Memory Configuration Memory Type

Allocation Size

Required per Block

Minimum Size

Maximum Size

Required for Maximum

Ladder (L)

4K bytes

12K bytes

16K bytes

256K bytes

768K bytes

Variable (V)

2K bytes

2K bytes

4K bytes

958K bytes

958K bytes

Constant (K)

2K bytes

2K bytes

0K bytes

954K bytes

954K bytes

Special (S)

2K bytes

2K bytes

0K bytes

954K bytes

954K bytes

TMR/CTR/ DCATS/MCAT

1024*

5K bytes

1024

20480

100K bytes

DRUM/EDRUMS/ MDRMW/MDRMD

128*

6K bytes

128

2304

108K bytes

Shift Registers

2048*

2K bytes

2048

16384

16K bytes

MOVE TO/FROM Tables

1024*

2K bytes

1024

14336

28K bytes

One Shots

2048*

2K bytes

2048

32768

32K bytes

* Number per block

2-10

TI560T

SIMATIC TI560T/TI565T Technical Product Description