SIMATIC TI560T/TI565T Technical Product Description: 2 TI560T, pages 34 to 43

Pages 34 to 43 of 122, from SIMATIC TI560T/TI565T Technical Product Description

The original document is the PDF (565 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Texas Instruments 500-5008 and Siemens 500-5008

Page 34

2.7

Remote Channel Controller Cards The TI560T or TI565T I/O system serves as the interface between field sensors and the logical control performed by the system processors. Remote Channel Controller (RCC) Cards, which reside in the TI560T or TI565T chassis (Figure 2-6), serve as the communication masters for the I/O system. These MC68000 microprocessor-based cards perform I/O reads and writes to gather information from remote I/O bases. Each remote I/O base is controlled by a Remote Base Controller (RBC) which communicates with its respective Remote Channel Controller through CATV cables, fittings, and taps. RS-485 media allows communication up to 3,300 ft. depending on the number of taps. Each Remote I/O Base contains a remote base power supply which supplies logic power to the RBC and TI500/TI505 I/O modules installed in the base. The TI500/TI505 controller family allows you to install any I/O module in any slot of any base: the I/O map is fully user-configurable. Any TI500/TI505 I/O base may be used with the TI560T or TI565T system. Some TI500 I/O bases require adapter bases. See the SIMATIC TI560T/TI565T System Manual (PPX:560/565–8105–x) for details.

RCC Card

Figure 2-6 TI560T/565T RCC Card

SIMATIC TI560T/TI565T Technical Product Description

TI560T

2-11

Page 35

Remote Channel Controller Cards (continued) Operation

The Remote Channel Controller (RCC) controls all communications between the TI560T or TI565T system and the Remote Base Controllers (RBC). The RCC sends and receives I/O updates to and from the RBCs located on the remote I/O base. The TI560T or TI565T system can accommodate up to four RCC cards, each card addressing up to 2048 I/O points for a system total of 8,192 I/O points. Each RCC can address 2 I/O channels; each I/O channel can consist of up to 1024 I/O points of any mix of analog or discrete. In addition, each RCC can address 2048 Control Relays (Cs) which are used as internal programming control elements. A system with 4 RCCs has 8,192 Control Relays available. The last 256 Cs on each RCC channel are retentive i.e., C769 – C1024 on channel 1; C1793 – C2048 on channel 2; etc. These 8192 control relays on the RCCs are in addition to the 49,152 local control relays provided on the TI560 CPU card. A system with all 4 RCCs installed then would have a total of 57,344 control relays. Using CATV media, the RCC can communicate with up to 16 RBCs on each channel and the RBCs can be located up to 15,000 ft. or further from the TI560T chassis. There should be less than 55 dB loss from the RCC card to any RBC. RS-485 media allows communication up to 3,300 ft. depending on the number of taps. Each RCC is controlled by a dedicated MC68000 microprocessor. All I/O channels (8 max.) are updated in parallel to minimize system I/O update times. The I/O communications channel operates at a data rate of 1 MBaud on a 35.75 MHz carrier frequency. A Miller encoding technique is utilized with FSK data transfer with an extended message preamble. Error checking includes CRCC–CCITT and field-length checks.

2-12

TI560T

SIMATIC TI560T/TI565T Technical Product Description

Page 36

2.8

Ladder Logic Instruction Set

Instruction Types

The Main CPU card executes an advanced ladder logic instruction set, which includes discretes, ladder logic subroutines, and high-level instructions. This instruction set is a superset of the TI520C and TI530C instruction sets. As a result, any program that operates on these models can be upgraded to a TI560T or TI565T.

Discrete Instructions Inputs Outputs

Control Relays

The input instruction (X) represents a discrete (on or off) input device. Up to 8192 inputs are available. The output instruction (Y) controls the status (on or off) of the output module point that corresponds to the instruction reference number. Up to 8192 outputs are available. Each channel of the RCC card provides 1024 control relays. The first 768 relays on each channel are nonretentive, the next 256 are retentive. A total of 8192 control relays are available on a full-up (4 RCCs) system.

Conditional/Unconditional Operations Jump

Master Control Relay

Skip Forward to LBL

Scan Sync Inhibit

The Jump instruction freezes all outputs in its field of control. The end jump instruction may be either conditional or unconditional. The MCR instruction turns off all outputs within the zone of control between the MCR instruction and the end MCR. The end MCR instruction may be either conditional or unconditional.

provide a means of selecting specific segments of a program to be executed during a scan. When the controller reads the Skip instruction, no ladder logic is executed until the Label instruction is found. The Scan Synchronization Inhibit instruction is used to control bringing a standby unit on-line to run in synchronization with the active unit in a hot backup configuration.

Bit Instructions Bit Clear Bit Pick Bit Set Bit Shift Register

The Bit Clear instruction clears a selected bit of a word to 0. The Bit Pick instruction tests a selected bit of a specified word to determine its status. The Bit Set instruction sets a selected bit of a word to 1. The Bit Shift Register instruction creates a bit shift register containing up to 1023 bits.

SIMATIC TI560T/TI565T Technical Product Description

TI560T

2-13

Page 37

Ladder Logic Instruction Set (continued)

Counter/Timer Instructions Counter Up/Down Counter

Timer Discrete Control Alarm Timer

Motor Control Alarm Timer

The Counter instruction counts recurring events up to 32,767. The Up-down Counter instruction counts the number of events (up or down) that have occurred between zero and 32,767. The Timer instruction decrements in .1-second or 1-millisecond steps for timing of events. The Discrete Control Alarm Timer is designed for use with a discrete control valve that provides feedback on whether the valve is open or closed. The output of the instruction should be the output to the valve or motor; the input should be from the logic that determines the state of the valve. The Motor Control Alarm Timer is similar to the Discrete Control Alarm, but provides additional functions to use with motor driven valves, driving in each direction or reversing motors.

Drum Instructions Drum

Event Drum

Maskable Event Drum-Discrete

Maskable Event Drum-Word

2-14

TI560T

The Drum instruction simulates operation of an electromechanical drum, and provides 15 output coils with 16 steps. The steps are indexed on multiples of the time base set up for the drum. The Event Drum instruction simulates operation of an electromechanical drum and provides 15 output coils with 16 steps. The steps can be indexed by a timer only, and event contact only, or a combination of an event contact and a timer. The Maskable Event Drum-Discrete functions in the same manner as the event drum with the addition of the capability of specifying a mask for each step to allow selection of the outputs to be controlled by the step. The Maskable Event Drum-Word functions just as the discrete drum, but gives the option of specifying a word rather than a set of discretes.

SIMATIC TI560T/TI565T Technical Product Description

Page 38

Matrix Instructions Scan Matrix Compare

Index Matrix Compare

- - 16 user-defined bit patterns against the current states of up to 15 I/O points. If a match is found, the step number is entered into the V-memory location specified. - - - bit pattern of a user-specified step to the current state of up to 15 I/O points. The instruction is indexed by loading a step number into the location specified.

Math Instructions Add

Subtract

Divide

Multiply

Compare

Square Root

The Add instruction adds a signed integer (positive or negative) in memory location A to a signed integer in memory location B and stores the result in memory location C. The signed integers on which the addition is performed are not affected by the operation and retain their values in the original locations. The Subtract instruction subtracts a signed integer (positive or negative) in memory location B from a signed integer in memory location A and stores the result in location C. The signed integers on which the subtraction is performed are not affected by the operation and retain their values in the original location. The Divide instruction divides a dividend in two memory locations, A and A+1, by a divisor in memory location B. The quotient and remainder are stored in two memory locations, C and C+1. The dividend and divisor values are not affected and retain their values in memory after the division is complete. The Multiply instruction multiplies a signed integer in memory location A by a signed integer in memory location B. The product is stored in two memory locations, C and C+1. The signed integer values in memory locations A and B are not affected by the multiplication and retain their values in the memory after multiplication is complete. The Compare instruction compares a number in memory location B to a number in memory location A. The comparison is made for equal to, less than, or greater than. Values in the A and B memory locations are not affected. The Square Root instruction takes the square root of a positive integer and stores the result in a specified memory location. The integer retains its original value.

SIMATIC TI560T/TI565T Technical Product Description

TI560T

2-15

Page 39

Ladder Logic Instruction Set (continued)

Move Instructions

2-16

TI560T

Load Data Constant

The Load Data Constant instruction loads the specified into the A memory location.

Move Discrete IR to Word

The Move Image Register to Word instruction shifts a specified number of bits from the discrete image register (X, Y, or C) to a specified word in memory.

Move Word to Discrete IR

The Move Word to Image Register instruction allows a specified number of bits to be shifted from a word memory location to specified discrete image register locations in a single memory scan.

Move Word (memory)

The Move Word instruction moves up to 256 words from a designated memory location to another designated location.

Move Word from Table

The Move Word from Table instruction moves words from one table location in VĆmemory to another location in VĆmemory, as specified by a table address pointer. one word is moved each memory scan.

Move Word to Table

The Move Word to table instruction moves words from a word source in VĆmemory to a table destination address specified by a pointer in VĆmemory. One word is moved during each scan.

Indirect Move Word

The Indirect Move Word instruction is actually a tableĆ toĆtable block move operation. In a single scan it move a block of up to 255 words from within a source table to within a destination table, then increments both tble pointers by the number of words moved. In batch appliations this instruction greatly simplifies the management of large tables of recipe parameters.

Move Image Register to/from Table

These instructions move blocks of image register bits (up to 255 words or 4080 bits per scan) into or out of tables in VĆmemory and increment the table pointers by the number of words moved. These instructions allow for efficient bitĆlevel interlocks across Peerlink networks, for example, or elegant machine diagnostics with the table search instructions described below.

SIMATIC TI560T/TI565T Technical Product Description

Page 40

Word Instructions The Convert Binary to BCD instruction converts binary inputs to equivalent Binary Coded Decimal values. Binary integer values up to 32,767 are converted to equivalent BCD values. Convert BCD The Convert Decimal to Binary instruction converts to Binary BCD inputs to equivalent binary integer values. BCD inputs up to 9999 are converted to their binary integer equivalents. Word AND The Word AND instruction logically ANDs a word in memory location A with a word in memory location B. The WAND instruction then places the result in memory location C. Word OR The Word OR instruction logically ORs a word in memory location A with a word in memory location B. The result of the WOR instruction is placed in memory location C. Word Exclusive OR The Word Exclusive OR exclusively ORs a word in memory location A with a word in a second location B. The result of the WXOR instruction is placed in memory location The Word Rotate instruction rotates to the right 4-bit Word Rotate segments of the word location specified. Word Shift The Word Shift Register instruction shifts from 1 to Register 1023 words from memory location A to V-memory, beginning at location B. One Shot The One-Shot instruction provides an output for one memory scan. Convert Binary to BCD

Ladder Logic Subroutines Go to Subroutine

Subroutine

Return

The Go to Subroutine instruction enables you to write ladder logic programs preceded by a subroutine number and to call them as needed. The Subroutine instruction is placed before a set of ladder logic instructions that are to be executed only when called with the Go to Subroutine instruction. The Return instruction brings execution of the ladder logic program back to the network. The Return may be either conditional or unconditional.

SIMATIC TI560T/TI565T Technical Product Description

TI560T

2-17

Page 41

Ladder Logic Instruction Set (continued)

Table Instructions Table to Table AND Table to Table OR Table to Table EXCLUSIVE OR Table Complement Word to Table Table to Word Word to Table AND

Word to Table OR

Word to Table EXCLUSIVE OR

Table Search for Equal

Table Search for Not Equal

2-18

TI560T

The Table to Table AND instruction ANDs the corresponding bits in two tables and places the results in a specified third table. The Table to Table OR instruction ORs the corresponding bits in two tables and places the results in a specified third table. The Table Exclusive OR instruction exclusively ORs the corresponding bits in two tables and places the results in a designated third table. The Table Complement instruction inverts the status of each bit in the first table and places the results in the second table. The complement of 0 is 1; of 1, 0. The Word to Table instruction places a duplicate of a word at the address specified in the destination table. The Table to Word instruction duplicates a specified word in a table to another word location. The Word to Table AND instruction compares each bit in a source word to the corresponding bit of a designated word in a table. The results are placed in a destination table. The Word to Table OR instruction logically ORs the corresponding bits of a source word with a designated word in a source table. The results are placed in a destination table. The Word to Table EXCLUSIVE OR instruction exclusively ORs the corresponding bits in a specified word and a word from a source table. The resultant word is placed in a destination table. The Table Search for Equal instruction locates the next occurrence of the word in a table that is equal to the source word. The address of the match is shown by a pointer. The Table Search for not Equal instruction locates the next occurrence of the word in a table that is not equal to the source word. The mismatch is shown by a pointer, and the value is copied to another specified word.

SIMATIC TI560T/TI565T Technical Product Description

Page 42

Clock Instructions Date Compare

Time Compare

Time Set

Date Set

The Date Compare instruction compares the current date of the real-time clock with the value contained in the designated V locations. The Time Compare instruction compares the time of the real-time clock with the values contained in the designated V-memory locations. The Time Set instruction sets the time portion of the real-time clock to the values contained in designated V-memory locations. The Date Set instruction sets the date portion of the real-time clock to the values contained in designated V-memory locations.

SIMATIC TI560T/TI565T Technical Product Description

TI560T

2-19

Page 43

2.9

TI560T Controller Component List The following listing provides the part numbers for components required to assemble a TI560T controller to fit your application.

PPX:560T–1101

Basic TI560T System, 120/240 VAC Includes: 1–Power Supply, 120/240 VAC (PPX:560T–2122) 1–Main CPU (PPX:560T–2820) w/176K Words of Memory 1–Chassis, 120/240 VAC (PPX:560T–2124)

PPX:560T–1102

Basic TI560T System, 24 VDC Includes: 1–Power Supply, 24 VDC (500–2123) 1–Main CPU (PPX:560T–2820) w/176K Words of Memory 1–RCC (PPX:560T–2126) (2048 I/O Capacity) 1–Chassis,-24 VDC (560T–2125)

PPX:560–2120

Main CPU w/48K Words of Memory

PPX:560–2122

120/240 VAC Power Supply

PPX:560–2123

24 VDC Power Supply

PPX:560–2124

Chassis, 120/240 VAC

PPX:560–2125

Chassis, 24 VDC

PPX:560–2126A

RF Remote Channel Controller (RCC) Card 2048 I/O Point Capacity per Card 2048 Control Relays per Card 15000-ft Channel Distance

PPX:560–2127

Twisted Pair Remote Channel Controller (RCC) Card 2048 I/O Point Capacity per Card 2048 Control Relays per Card 3000-ft Channel Distance

2-20

TI560T

PPX:560–2128

Hot Backup Card (Need Qty. of 2)

PPX:560–2129

Hot Backup Upgrade Kit (contains 2 PPX:560–2128 cards)

PPX:560–2130

64K Word Memory Expansion Card

SIMATIC TI560T/TI565T Technical Product Description