Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 10 of 14

SIMATIC TI560T/TI565T Technical Product Description: 5 System Configuration

Pages 80 to 93 of 122, from SIMATIC TI560T/TI565T Technical Product Description

The original document is the PDF (565 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Texas Instruments 500-5008 and Siemens 500-5008

Page 80

Chapter 5

System Configuration 5.1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-2

5.2

TI560T/TI565T Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-4

5.3

Remote I/O Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-5

Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remote Base Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Remote Base Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adapter Base Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-Slot I/O Base 14-Slot I/O Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-Slot I/O Base . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Redundant Base Controller Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-5 5-5 5-5 5-5 5-5 5-5 5-5

TI505 I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-8

I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-8

TI500 I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-11

I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-11

5.6

I/O Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-13

5.7

Specifications for TI560T/TI565T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-14

5.4

5.5

SIMATIC TI560T/TI565T Technical Product Description

System Configuration

5-1

Page 81

5.1

Overview In this chapter, you will find dimensional drawings and component listings for the TI560T/TI565T to help you in planning your installation. Figure 5-1 shows a typical layout of the TI560T/TI565T with the Hot Backup option. The TI560T/TI565T hardware is modular to make it more easily adapted to your specific needs. From the compact, 19-inch chassis that houses the power supply and cards to the I/O racks and modules, each component of a TI560T/TI565T system may be selected to conform to your particular application.

5-2

System Configuration

SIMATIC TI560T/TI565T Technical Product Description

Page 82

HBU Card SF CPU Global Memory Main CPU

Remote Channel Controller Standby Unit

Active Unit

1M Baud Fiber-Optic Cable 1M Baud Control Cable

Programmer – Connect to any dual port * module or RBC Comm port * Dual Comm Port Module

CRT Operator Interface

RS–232C R B C

RS–232C Micropanels R B C

PEERLINK Interlocking System (16 module max) P L

R B C

N I M

R B C

Any number up to 1 mile end-to-end

Loop Register and Data Display Modules

TIWAY Industrial LAN (254 PLC max)

Each Channel –

Up to 16 remote bases (max 1024 I/O) Up to 15,000’ end-to-end Max of 8 I/O channels

Figure 5-1 TI560T/TI565T with Hot Backup Option

SIMATIC TI560T/TI565T Technical Product Description

System Configuration

5-3

Page 83

5.2

TI560T/TI565T Chassis

19.25 (488.95)

17.75 (450.85)

12.5 (317.5) 6.75 (171.45)

1.5 (38.1) 16.875 (428.63)

18.031 (457.99) 18.875 (479.43)

14.0 (355.6)

1.0 (25.4)

0.125 (3.175)

13.0 (330.2)

2.0 (50.8)

14.9 (377.83) 15.0 (381.00)

Figure 5-2 Mounting Dimensions for TI560T/TI565T

5-4

System Configuration

SIMATIC TI560T/TI565T Technical Product Description

Page 84

5.3

Remote I/O Components

Components

Table 5-1 provides the part numbers for I/O components to assemble a TI565T remote I/O system to fit your application. Table 5-1 I/O Components Part Number

Description

PPX:500–2114

Remote Base Controller (RBC) with RS–232 Communication Port

PPX:500–2151–A

Remote Base Power Supply (110/220 VAC)

PPX:500–5840

Adapter Base Kit for using existing 8- and 16-slot SIMATIC TI520/TI530 Bases

PPX:500–5848

14-Slot I/O Base

PPX:500–5884

12-Slot I/O Base (mounts in 19-rack)

PPX:500–5892

6-Slot Base

Remote Base Controller

The RBC is an intelligent interface between a remote base and a Remote Channel Controller card in the TI560T/TI565T chassis.

Remote Base Power Supply

The remote base power supply converts user-supplied 110/220 VAC power into +5.1 and -5 VDC to power the base controller and I/O modules installed in the base.

Adapter Base Kit

The adapter base enables the 8- and 16-slot bases to be used with the TI560T/TI565T.

6-Slot I/O Base 14-Slot I/O Base

The 6- and 14-slot I/O bases contain a controller slot in addition to the I/O slots.

12-Slot I/O Base

The 12-slot base is sized for mounting in a standard 19-inch rack.

Redundant Base Controller Options

Table 5-2 shows the Redundant Base controller options. Table 5-2 I/O Components Part Number

Description

PPX:500–9914

Redundant RBC

PPX:500–9940

Redundant Adapter Base

PPX:500–5114

Twisted-pair RBC

PPX:500–6850

RF RBC

PPX:500–6851

Twisted-pair RBC

PPX:500–6660

P/S

PPX:500–6505, –6508, 6516

I/O Bases

SIMATIC TI560T/TI565T Technical Product Description

System Configuration

5-5

Page 85

Remote I/O Components (continued) Overall Mounting Height

10.44 (265.18) 6.750 (171.45)

2.200 (55.88)

0.750 (19.05) 2 pl.

8.635 (219.33)

0.250 (6.35)

3.34 (84.83)

14.200 (360.68)

12.7 (322.58)

14.700 (373.38)

0.750 (19.05) 2 pl. 6.750 (171.45)

PPX:500–5892

2.200 (55.88)

Use #10 (M5) mounting hardware – 4 pl) Overall Mounting Height

19.540 (496.32) 15.850 (402.59) 0.750 (19.05) 3 pl.

2.200 (55.88)

8.635 (219.33)

6.750 (171.45)

3.34 (84.83)

0.250 (6.35)

14.200 (360.68)

12.7 (322.58)

14.700 (373.38)

0.750 (19.05) 3 pl.

15.850 (402.59)

6.750 (171.45)

Use #10 (M5) mounting hardware – 6 pl) Notes: 1.in 2.Power supply occupies first two slots (mm)

2.200 (55.88)

PPX:500–5848

Figure 5-3 6-Slot and 14-Slot I/O Bases

5-6

System Configuration

SIMATIC TI560T/TI565T Technical Product Description

Page 86

4.7 (119.38) 1,35 (34.29)

0,75 (19.05)

14.2 (360.68)

14.7 (373.38)

0,75 (19.05) In (mm)

Front View

Figure 5-4 PPX:500–5840 Adapter Base

SIMATIC TI560T/TI565T Technical Product Description

System Configuration

5-7

Page 87

5.4

TI505 I/O

I/O Modules

The TI505 I/O modules are used with the TI560T/TI565T. Table 5-3 lists the I/O modules available and their part number and description. Table 5-3 TI505 I/O Modules Part Number

5-8

Description

DC Consumption (watts) +5 V –5 V

PPX:505-4008

24 VAC Input (8 point)

2.0

Ć

PPX:505-4016

24 VAC Input (16 point)

2.0

Ć

PPX:505-4032

24 VAC Input (32 point)

2.0

Ć

PPX:505-4108

LVDC/TTL (8 point)

2.0

Ć

PPX:505-4116

LVDC/TTL (16 point)

2.0

Ć

PPX:505-4132

LVDC/TTL (32 point)

2.0

Ć

PPX:505-4208

110 VAC Input (8 point)

2.0

Ć

PPX:505-4216

110 VAC Input (16 point)

2.0

Ć

PPX:505-4232

110 VAC Input (32 point)

2.0

Ć

PPX:505-4308

24 VDC Input (8 point)

2.0

Ć

PPX:505-4316

24 VDC Input (16 point)

2.0

Ć

PPX:505-4332

24 VDC Input (32 point)

2.0

Ć

PPX:505-4408

220 VAC Input (8 point)

2.0

Ć

PPX:505-4416

220 VAC Input (16 point)

2.0

Ć

PPX:505-4432

220 VAC Input (32 point)

2.0

Ć

PPX:505-4508

24 VDC Output (8 point)

2.5

Ć

PPX:505-4516

24 VDC Output (16 point)

2.5

Ć

PPX:505-4532

24 VDC Output (32 point)

2.5

Ć

PPX:505-4608

110 VAC Output (8 point)

2.5

Ć

PPX:505-4616

110 VAC Output (16 point)

2.5

Ć

PPX:505-4632

110 VAC Output (32 point)

2.5

Ć

PPX:505-4708

24 VDC Output (8 point)

5.0

Ć

PPX:505-4716

24 VDC Output (16 point)

5.0

Ć

PPX:505-4732

24 VDC Output (32 point)

5.0

Ć

PPX:505-4808

220 VAC Output (8 point)

5.0

Ć

PPX:505-4816

220 VAC Output (16 point)

5.0

Ć

PPX:505-4832

220 VAC Output (32 point)

5.0

Ć

PPX:505-4908

Relay Output Form C (8 point)

2.5

Ć

PPX:505-4916

Relay Output Form A (16Ć point)

2.5

Ć

System Configuration

SIMATIC TI560T/TI565T Technical Product Description

Page 88

Table 5-3 TI505 I/O Modules (continued) Part Number

Description

DC Consumption (watts) +5 V –5 V

PPX:505-4932

Relay Output Form A (32Ć point)

2.5

Ć

PPX:505-4932

Relay Output Form A (32Ć point)

2.5

Ć

PPX:505-5100

TurboPlastic

7.0

0

PPX:505-5103

TurboParison

7.0

0

PPX:505-5184

MODNIM 〈Modbus NIM)

8.0

0

PPX:505-5190

6MTCC: TI505 to 6MT I/F

4.0

0

PPX:505-5417

16 Output Relay, 115 VDC

3.0

0

PPX:505-6010

Input Simulator

2.0

Ć

PPX:505-6011

Output Simulator

2.5

Ć

PPX:505-6108

Analog Input

4.0

Ć

PPX:505-6108-A

Analog Input

4.0

Ć

PPX:505-6202

Analog Output (2 point)

2.5

Ć

PPX:505-6204

Analog Output (4 point)

5.0

Ć

PPX:505-6208

Analog Output (8 point)

5.0

Ć

PPX:505-6208-A

Analog Output (8 point)

2.0

Ć

PPX:505-6308

Word Input

4.0

Ć

PPX:505-6408

Word Output

5.0

Ć

PPX:505-6851-A

Remote Base Controller

5.0

0.2

PPX:505-6830

IOCC

5.0

0.1

PPX:505-6840

Distributed Base Controller

5.0

0.1

PPX:505-7002

High Speed Counter & Encoder

2.5

Ć

PPX:505-7012

8 In/4 Out Analog

3.0

Ć

PPX:505-7016

Bipolar 8 In/4 Out Analog

6.5

Ć

PPX:505-7028

Thermocouple

6.5

0.01

PPX:505-7038

RTD

2.2

0

PPX:505-7101

BASIC Module

6.0

0.125

PPX:505-7339

NIM (Network Interface Module)

8.0

Ć

PPX:505-7340

Dual Media NIM

8.0

Ć

PPX:505-7354

Peerlink

8.0

Ć

SIMATIC TI560T/TI565T Technical Product Description

System Configuration

5-9

Page 89

TI505 I/O (continued) Table 5-3 TI505 I/O Modules (continued)

5-10

Part Number

Description

PPX:505-ATM

IBM AT Compatible Coprocessor

11.0

0.2

PPX:505-0220

IBM AT Compatible Coprocessor

11.0

0.2

PPX:505-0440

IBM AT Compatible Coprocessor

11.0

0.2

PPX:505-4120

IBM AT Compatible Coprocessor

11.0

0.2

System Configuration

DC Consumption (watts) +5 V –5 V

SIMATIC TI560T/TI565T Technical Product Description

Page 90

5.5

TI500 I/O

I/O Modules

The TI500 I/O modules are used with the TI560T/TI565T. Table 5-4 lists the I/O modules available, and gives the part number and description of each module. Table 5-4 TI500 I/O Modules Part Number

Description

DC Consumption (watts) +5 V –5 V

PPX:500-2108

IOCC

5.0

0.1

PPX:500-2109

Distributed Base Controller

5.0

0.1

PPX:500-5002

220 VAC

1.0

Ć

PPX:500-5003

110 VDC Input

1.0

Ć

PPX:500-5004

220 VDC Input

1.0

Ć

PPX:500-5005

24V AC/DC Input

1.0

Ć

PPX:500-5006

48V AC/DC Input

1.0

Ć

PPX:500-5007

TTL Input

1.0

Ć

PPX:500-5008

14 VDC Input

1.0

Ć

PPX:500-5009

Analog Input

3.0

Ć

PPX:500-5010

24/48 VAC Output

1.4

Ć

PPX:500-5011

110 VAC Output

1.4

Ć

PPX:500-5012

220 VAC Output

1.4

Ć

PPX:500-5013

24/48 VDC Output

1.4

Ć

PPX:500-5016

Analog Output

3.0

Ć

PPX:500-5018

Word Input

2.0

Ć

PPX:500-5019

Word Output

2.0

Ć

PPX:500-5020

Input Simulator

1.0

Ć

PPX:500-5021

Output Simulator

1.4

Ć

PPX:500-5022

ASCII Module

8.5

0.125

PPX:500-5023

High Speed Pulse Input

6.0

0.050

PPX:500-5024

Servo Axis Controller

7.5

0.150

PPX:500-5026

24 VDC Latching Input Rapid Response Output

2.0

Ć

PPX:500-5027

110 VAC Latching Input Rapid Response Output

2.0

Ć

PPX:500-5029

Dual Communication Port

8.5

0.125

PPX:500-5030

32Ćpoint 15-30 VDC Input

3.0

Ć

PPX:500-5031

32Ćpoint 20-30 VDC Output

3.0

Ć

PPX:500-5032

6Ćpoint Isolated Input, 85-132 VAC

1.0

Ć

SIMATIC TI560T/TI565T Technical Product Description

System Configuration

5-11

Page 91

TI500 I/O (continued) Table 5-4 TI500 I/O Modules (continued) Part Number

Description

DC Consumption (watts) +5 V –5 V

PPX:500-5033

4Ćpoint Isolated output, 85-132 VAC

1.4

Ć

PPX:500-5035

BASIC Module

8.5

0.125

PPX:500-5037-A 8 In, Analog

2

Ć

PPX:500-5038

Network Interface RS-232 & LLP

8.0

0.625

PPX:500-5039

Network Interface Dual LLP

8.0

1.250

PPX:500-5040

Network Interface Dual RS-232

8.0

0.050

PPX:500-5114

Remote Base Controller

6.0

0.200

PPX:500-5041

110 VAC Redundant Output

2.5

Ć

PPX:500-5047

8-Channel Analog Output

2.0

Ć

PPX:500-5047-A

8 Out, Analog

2.0

Ć

PPX:500-5048

24 VDC Isolated Input

1.0

Ć

PPX:500-5049

24 VDC Isolated Output

1.4

Ć

PPX:500-5051

Thermocouple

4.0

Ć

PPX:500-5052

Resistance Temp. Detector (RTD)

3.5

Ć

PPX:500-5053

TIWAY Peerlink

6.5

Ć

PPX:500-5054

Redundant TIWAY PEERLINK

6.9

1.25

PPX:500-5055

32Ćpoint, 110 VAC Input

3.0

Ć

PPX:500-5056

32Ćpoint,110 VAC Output

3.0 *

Ć

PPX:500-5061

HighĆcurrent Relay

3.0

Ć

PPX:500-5062

LowĆcurrent Relay

3.0

Ć

PPX:500-5192

48 VDC Input

3.0

Ć

PPX:500-9912

Redundant Remote Base Controller

6.0

0.200

* Some versions of the PPX:500-5056 consume 3.3 watts of +5 VDC power and are identified with a label.

5-12

System Configuration

SIMATIC TI560T/TI565T Technical Product Description

Page 92

5.6

I/O Installation Considerations CATV cable is the medium used to transmit I/O updates. The CATV cable, taps and fittings are user-supplied; consult the manufacturer for detailed specifications. The TI560T or TI565T I/O system allows remote I/O bases to be located as much as 15,000 ft. away from the main system processor. The bases are distributed in a multidrop configuration, and there should be less than 55 dB signal loss @25_C between the RCC and any I/O base. RS–485 media allows communication up to 3,300 ft. depending on the number of taps. Siemens recommends no less than quad-shield RG-6 for all drop lines. The CATV should not have any other communications traffic on it.

SIMATIC TI560T/TI565T Technical Product Description

System Configuration

5-13

Page 93

5.7

Specifications for TI560T/TI565T Table 5-5 Environmental Specifications

Operating temperature

0 to 60°C (32 to 140°F)

Storage temperature

–40 to +85°C (–40 to 185°F)

Relative humidity

5% to 95% noncondensing

Vibration

Random profile based on NAVMAT P–9492

Noise immunity, conducted

MIL STD 461A CS01, CS02 and CS06 IEEE472 Transient Surge NEMA ICS 2–230.45 Showering Arc

Noise immunity, radiated

MIL STD 461A RS01, RS02 and RS03 FCC Docket 20780 (Class A)

Agency Approvals

UL Listed CSA Certified FM Approved (Class I, Div. 2, Haz. Loc.)

Corrosion Protection

All parts of corrosion-resistant material or plated or painted as corrosion protection

Table 5-6 Electrical Specifications for Power Supply Input voltage selection

110 VAC/220 VAC, or 24 VDC

Voltage Range

85 to 132 VAC (110 VAC) 170 to 260 VAC (220 VAC) 20.4 to 30 VDC (24 VDC)

Maximum Power

300 VA

Frequency Range

47 to 63 Hz

Fuse

5 A/250 VAC

Output

5.1 V at 23 A for 110 VAC/220 VAC, 30 A for 24 VDC 12.0 V at 1 A -12.0 V at 1 A

Battery Shelf Life

3 years typical storage –40°C to +80°C

Battery Type

Lithium 1/2 gram (non-rechargeable)

Battery

6 months typical memory backup 0°C to 60°C

Backup Features

Memory Backup Displays: POWER GOOD and BATTERY GOOD LEDs Memory Protect Keylock

Agency Approvals

UL Listed CSA Certified FM Approved (Class I, Div. 2, Haz. Loc.)

5-14

System Configuration

SIMATIC TI560T/TI565T Technical Product Description