Page 72

4.7

Run-Time Diagnostics The following diagnostic routines are run during operation of the controller. •

ROM “Fletcher” Checksum Test

•

RAM Checksum

•

RAM Parity on each RAM Access

•

Watchdog Timer on Inter-Processor Communication and Acknowledgments, as well as major functions of controller timeline

•

Various Sanity Checks on the Loop, Analog Alarm, and SF Program Variables

•

Consistency checks on S memory Control Block Structures

•

Invalid Instruction and Spurious Interrupt Traps

•

CRC Checks on all Remote I/O Communication

•

Early Power-Fail Detection and Controlled Switchover to battery Backup

If a fatal error is encountered, the controller halts operation and the PC GOOD LED is turned off.

4-10

Hot Backup and System Diagnostics

SIMATIC TI560T/TI565T Technical Product Description

Page 73

4.8

User-Initiated Diagnostics User-Initiated Diagnostics are available via a programming device and are accessed through the Auxiliary Functions Menu. These user-initiated diagnostics are used for troubleshooting the TI560T and TI565T. The diagnostics routines available from the Auxiliary Functions Menu are outlined as follows.

Run controller Diagnostics

This routine runs a set of diagnostics on each of the cards installed in the system chassis. When the diagnostics are complete, the message “Diagnostics passed” is displayed if no errors were found. Otherwise, one or more of the following error messages is displayed for each slot with a board installed. Error Messages

-

Run Remote Base Diagnostics

This routine runs diagnostic checks on each remote base controller configured in the system. When the diagnostics are complete, one or more of the following messages is displayed. Remote Base Messages -

-

SIMATIC TI560T/TI565T Technical Product Description

Hot Backup and System Diagnostics

4-11

Page 74

User-Initiated Diagnostics (continued) Display Failed I/O

This routine initiates a status check of the configured I/O modules by the Main CPU. When the check is complete, the location of failed I/O modules is displayed in chart form on the programming device. The failures are identified by Channel, Base, and Slot.

Show Controller Diagnostics Cell

This routine calls a display which supplies information for the items shown in Figure 4-3.

TI560T OPERATIONAL STATUS

SCAN = (TIME, FIXED OR V)

BATTERY = (GOOD, LOW)

KEY = (LOCKED OR UNLOCKED)

DOWNLOAD = (ON OR OFF)

MODE = (RUN OR PROGRAM)

PROGRAM IN RAM

SF/LOOP MODE = (RUN OR PROGRAM) SF/LOOP FOLLOWS P/C TO PROGRAM MODE

FATAL ERROR

= (NONE OR ERROR TYPE)

NON FATAL ERROR

= (NONE OR ERROR TYPE)

LOOP FATAL ERROR

= (NONE OR ERROR TYPE)

LOOP NON FATAL ERROR

= (NONE OR ERROR TYPE)

Figure 4-3 TI560T Operational Status Screen If errors are encountered, they will be listed by classification as fatal or non-fatal as indicated above. The type of error appears in the space next to the fatal or non-fatal error prompt.

4-12

Hot Backup and System Diagnostics

SIMATIC TI560T/TI565T Technical Product Description

Page 75

4.9

Status Words Status words are available in the TI560T and TI565T to indicate system status. This status information words can be used in either ladder logic or Special Function programs to take corrective action when unfavorable conditions occur. These status words are useful in troubleshooting situations.

TI560T

For the TI560T, status words provide both system and I/O status information as outlined in the following table. TI560T Status Words

1

Specific bits provide information on power supply, battery, ports, scan time, move insts.

2-9

Bases on Channels 1-8

11-26

Modules on Channel 1

27-42

Modules on Channel 2

43-58

Modules on Channel 3

59-74

Modules on Channel 4

75-90

Modules on Channel 5

91-106

Modules on Channel 6

107-122 Modules on Channel 7 123-138 Modules on Channel 8

SIMATIC TI560T/TI565T Technical Product Description

Hot Backup and System Diagnostics

4-13

Page 76

Status Words (continued) TI565T

Status Words 161 and 162 enable you to read fatal and non-fatal error status in the TI565T. Access of the error data through status words provides a means for incorporating alarms into ladder logic programs to alert operators when an error occurs. The errors designated by the bits in the status words are given in the following tables. Status Word 161 Bits 1-8 set to 1 indicate errors as follows: 1...............

ROM Error.

.1..............

RAM Error.

..1.............

Operating System Error.

...1............

Invalid Control Block Encountered.

....1...........

Diagnostic Failure.

.....1..........

Memory Parity Error.

......1.........

S Memory is inconsistent.

.......1........

SF Program Number received from ladder logic is invalid.

Bits 9-11 are unused, and are always 0. ...........1....

Alarm Enabled. (If a word is selected for the analog flags, Bit 12 is written. If a discrete is selected for the analog flags, Bit 12 is not written.)

Bits 13-16 are unused, and are always 0.

4-14

Hot Backup and System Diagnostics

SIMATIC TI560T/TI565T Technical Product Description

Page 77

Status Word 162 1............... Port 1 Communications Error. This error is logged if the TI565T board has a character queued for printing to Port 1 for more than 30 seconds. .1.............. Port 2 Communications Error. This error is logged if the TI565T board has a character queued for printing to Port 2 for more than 30 seconds. ..1............. Loops are overrunning. ...1............ Analog Alarms are overrunning. ....1........... Cyclic SF Programs are overruning. .....1.......... Normal SF Program Queue is full. ......1......... Priority SF Program Queue is full. .......1........ Cyclic SF Program Queue is full ........1....... Error occurred during Loop calculations. .........1...... Error occurred during Analog Alarm calculations. ..........1..... A control block is disabled. ...........1.... Attempt to execute an undefined SF Program or SF Subroutine. ............1... Attempt to invoke a restricted SF Program from ladder logic. ................ Bit 14 is unused. ................ Bit 15 is unused. ................ Bit 16 is unused.

SIMATIC TI560T/TI565T Technical Product Description

Hot Backup and System Diagnostics

4-15

Page 78

4.10

LEDs

Using LEDs as Diagnostic Tools

LED displays on the cards are a simple means for beginning troubleshooting. Each card has LED indicators that supply information on the status of that particular card. Figure 4-4 illustrates the location of the LEDs on the cards. Power Supply

TI560

Ext. Mem.

RCC

TI565

TI560 HBU

ON OFF

POWER GOOD

P/C GOOD CPU GOOD

MEMORY PROTECT BATTERY GOOD

ACTIVE MEM GOOD

RCC GOOD

PROG RUN

CHANNEL

SF CPU GOOD

HBU GOOD

PROG RUN

STBY

COMGOOD

Figure 4-4 LED Locations The LEDs shown above provide status information at a glance for each of the cards. Troubleshooting is expedited by starting from the primary controller components and working through them to the I/O modules and wiring.

4-16

Hot Backup and System Diagnostics

SIMATIC TI560T/TI565T Technical Product Description

Page 79

Table 4-1 lists the indications provided by the LEDs on each card. Table 4-1 LED Indications LEDs

Indications

Power Good

Remains on as long as the power supply DC output voltage remains above the operating level..

Battery Good

Stays on as long as the memory back-up battery voltage remains above 2.4 volts, and system power is applied.

TI560T PC Good

When on, overall indicator of chassis operating integrity.

TI560T CPU Good

On indicates the CPU card is good.

TI560T PROG/RUN

LED on indicates the system is in the run mode.

TI565T CPU Good

On indicates the TI565 CPU card is good.

TI565T PROG/RUN

On indicates the system is executing Loops, Analog Alarms, and Special Function Programs.

RCC Good

On indicates the Remote Channel Controller has passed self-diagnostics.

Channel (top)

When on (may be flashing), indicates channel A is transmitting.

Channel (bottom)

When on (may be flashing), indicates channel B is transmitting.

MEM Good

On indicates the memory card is good.

HBU Good

On indicates integrity of card is good.

Active

On indicates this is Active Unit.

Standby

On indicates this is Standby Unit.

COMM Good

On indicates HBU Communications good.

SIMATIC TI560T/TI565T Technical Product Description

Hot Backup and System Diagnostics

4-17