Page 72
4.7
Run-Time Diagnostics The following diagnostic routines are run during operation of the controller. •
ROM “Fletcher” Checksum Test
•
RAM Checksum
•
RAM Parity on each RAM Access
•
Watchdog Timer on Inter-Processor Communication and Acknowledgments, as well as major functions of controller timeline
•
Various Sanity Checks on the Loop, Analog Alarm, and SF Program Variables
•
Consistency checks on S memory Control Block Structures
•
Invalid Instruction and Spurious Interrupt Traps
•
CRC Checks on all Remote I/O Communication
•
Early Power-Fail Detection and Controlled Switchover to battery Backup
If a fatal error is encountered, the controller halts operation and the PC GOOD LED is turned off.
4-10
Hot Backup and System Diagnostics
SIMATIC TI560T/TI565T Technical Product Description
Page 73
4.8
User-Initiated Diagnostics User-Initiated Diagnostics are available via a programming device and are accessed through the Auxiliary Functions Menu. These user-initiated diagnostics are used for troubleshooting the TI560T and TI565T. The diagnostics routines available from the Auxiliary Functions Menu are outlined as follows.
Run controller Diagnostics
This routine runs a set of diagnostics on each of the cards installed in the system chassis. When the diagnostics are complete, the message “Diagnostics passed” is displayed if no errors were found. Otherwise, one or more of the following error messages is displayed for each slot with a board installed. Error Messages
-
Run Remote Base Diagnostics
This routine runs diagnostic checks on each remote base controller configured in the system. When the diagnostics are complete, one or more of the following messages is displayed. Remote Base Messages -
-
SIMATIC TI560T/TI565T Technical Product Description
Hot Backup and System Diagnostics
4-11
Page 74
User-Initiated Diagnostics (continued) Display Failed I/O
This routine initiates a status check of the configured I/O modules by the Main CPU. When the check is complete, the location of failed I/O modules is displayed in chart form on the programming device. The failures are identified by Channel, Base, and Slot.
Show Controller Diagnostics Cell
This routine calls a display which supplies information for the items shown in Figure 4-3.
TI560T OPERATIONAL STATUS
SCAN = (TIME, FIXED OR V)
BATTERY = (GOOD, LOW)
KEY = (LOCKED OR UNLOCKED)
DOWNLOAD = (ON OR OFF)
MODE = (RUN OR PROGRAM)
PROGRAM IN RAM
SF/LOOP MODE = (RUN OR PROGRAM) SF/LOOP FOLLOWS P/C TO PROGRAM MODE
FATAL ERROR
= (NONE OR ERROR TYPE)
NON FATAL ERROR
= (NONE OR ERROR TYPE)
LOOP FATAL ERROR
= (NONE OR ERROR TYPE)
LOOP NON FATAL ERROR
= (NONE OR ERROR TYPE)
Figure 4-3 TI560T Operational Status Screen If errors are encountered, they will be listed by classification as fatal or non-fatal as indicated above. The type of error appears in the space next to the fatal or non-fatal error prompt.
4-12
Hot Backup and System Diagnostics
SIMATIC TI560T/TI565T Technical Product Description
Page 75
4.9
Status Words Status words are available in the TI560T and TI565T to indicate system status. This status information words can be used in either ladder logic or Special Function programs to take corrective action when unfavorable conditions occur. These status words are useful in troubleshooting situations.
TI560T
For the TI560T, status words provide both system and I/O status information as outlined in the following table. TI560T Status Words
1
Specific bits provide information on power supply, battery, ports, scan time, move insts.
2-9
Bases on Channels 1-8
11-26
Modules on Channel 1
27-42
Modules on Channel 2
43-58
Modules on Channel 3
59-74
Modules on Channel 4
75-90
Modules on Channel 5
91-106
Modules on Channel 6
107-122 Modules on Channel 7 123-138 Modules on Channel 8
SIMATIC TI560T/TI565T Technical Product Description
Hot Backup and System Diagnostics
4-13
Page 76
Status Words (continued) TI565T
Status Words 161 and 162 enable you to read fatal and non-fatal error status in the TI565T. Access of the error data through status words provides a means for incorporating alarms into ladder logic programs to alert operators when an error occurs. The errors designated by the bits in the status words are given in the following tables. Status Word 161 Bits 1-8 set to 1 indicate errors as follows: 1...............
ROM Error.
.1..............
RAM Error.
..1.............
Operating System Error.
...1............
Invalid Control Block Encountered.
....1...........
Diagnostic Failure.
.....1..........
Memory Parity Error.
......1.........
S Memory is inconsistent.
.......1........
SF Program Number received from ladder logic is invalid.
Bits 9-11 are unused, and are always 0. ...........1....
Alarm Enabled. (If a word is selected for the analog flags, Bit 12 is written. If a discrete is selected for the analog flags, Bit 12 is not written.)
Bits 13-16 are unused, and are always 0.
4-14
Hot Backup and System Diagnostics
SIMATIC TI560T/TI565T Technical Product Description
Page 77
Status Word 162 1............... Port 1 Communications Error. This error is logged if the TI565T board has a character queued for printing to Port 1 for more than 30 seconds. .1.............. Port 2 Communications Error. This error is logged if the TI565T board has a character queued for printing to Port 2 for more than 30 seconds. ..1............. Loops are overrunning. ...1............ Analog Alarms are overrunning. ....1........... Cyclic SF Programs are overruning. .....1.......... Normal SF Program Queue is full. ......1......... Priority SF Program Queue is full. .......1........ Cyclic SF Program Queue is full ........1....... Error occurred during Loop calculations. .........1...... Error occurred during Analog Alarm calculations. ..........1..... A control block is disabled. ...........1.... Attempt to execute an undefined SF Program or SF Subroutine. ............1... Attempt to invoke a restricted SF Program from ladder logic. ................ Bit 14 is unused. ................ Bit 15 is unused. ................ Bit 16 is unused.
SIMATIC TI560T/TI565T Technical Product Description
Hot Backup and System Diagnostics
4-15
Page 78
4.10
LEDs
Using LEDs as Diagnostic Tools
LED displays on the cards are a simple means for beginning troubleshooting. Each card has LED indicators that supply information on the status of that particular card. Figure 4-4 illustrates the location of the LEDs on the cards. Power Supply
TI560
Ext. Mem.
RCC
TI565
TI560 HBU
ON OFF
POWER GOOD
P/C GOOD CPU GOOD
MEMORY PROTECT BATTERY GOOD
ACTIVE MEM GOOD
RCC GOOD
PROG RUN
CHANNEL
SF CPU GOOD
HBU GOOD
PROG RUN
STBY
COMGOOD
Figure 4-4 LED Locations The LEDs shown above provide status information at a glance for each of the cards. Troubleshooting is expedited by starting from the primary controller components and working through them to the I/O modules and wiring.
4-16
Hot Backup and System Diagnostics
SIMATIC TI560T/TI565T Technical Product Description
Page 79
Table 4-1 lists the indications provided by the LEDs on each card. Table 4-1 LED Indications LEDs
Indications
Power Good
Remains on as long as the power supply DC output voltage remains above the operating level..
Battery Good
Stays on as long as the memory back-up battery voltage remains above 2.4 volts, and system power is applied.
TI560T PC Good
When on, overall indicator of chassis operating integrity.
TI560T CPU Good
On indicates the CPU card is good.
TI560T PROG/RUN
LED on indicates the system is in the run mode.
TI565T CPU Good
On indicates the TI565 CPU card is good.
TI565T PROG/RUN
On indicates the system is executing Loops, Analog Alarms, and Special Function Programs.
RCC Good
On indicates the Remote Channel Controller has passed self-diagnostics.
Channel (top)
When on (may be flashing), indicates channel A is transmitting.
Channel (bottom)
When on (may be flashing), indicates channel B is transmitting.
MEM Good
On indicates the memory card is good.
HBU Good
On indicates integrity of card is good.
Active
On indicates this is Active Unit.
Standby
On indicates this is Standby Unit.
COMM Good
On indicates HBU Communications good.
SIMATIC TI560T/TI565T Technical Product Description
Hot Backup and System Diagnostics
4-17