Page 31

S5-100U

Technical Description

Data Cycle Prior to a program scan, the external I/O bus transfers current information from the input modules to the process image input table (PII). At the same time, information contained in the process image output table (PIQ) is transferred to the output modules.

Shift data

Program scanning

Shift data

Data cycle

Time axis

Transfer data from the shift register to the output modules. Load data from the input modules into the shift register. Figure 2-6. Data Cycle

Interrupt Data Cycle, for CPU 103 version 8MA02 and higher There is an interrupt input data cycle prior to each time-controlled or interrupt-driven program scan. Before a time-controlled program scan, current information about the input modules is read into the interrupt PII. Before an interrupt-driven program scan, interrupt inputs on slots 0 and 1 only are read into the interrupt PII. Following a time-controlled program scan, there is not an interrupt output data cycle until data has been moved into the interrupt PIQ via a transfer operation (see section 6.6.2). Information is output from the interrupt PIQ to the output modules during an interrupt output data cycle. The PIQ is updated.

EWA 4NEB 812 6120-02b

2-7

Page 32

Technical Description

S5-100U

Length of the Shift Register The total length of the shift register is obtained from the sum of the data bits of all plugged-in modules and of the empty slots. The check bit is not counted. You must know the length of the shift register to be able to determine the data cycle time. Data cycle time is 25 µs x number of data bits.

Table 2-2. Number of Bits per Module in the Shift Register Plugged-in Module

Number of Data Bits

Diagnostic module or vacant slot

4

4-channel digital input and output modules

4

500 Hz comparator module, 500 Hz timer module, 500 Hz counter module

4

25 KHz counter module

32

8-channel digital input and output modules

8

Digital input and output module, 16 inputs/16 outputs

16

Simulator module

8

Analog modules for each activated channel

16*

CP 521, IP 262, IP 266, IP 267

64

Refer to the individual manuals for information on other modules. *

This does not apply to the 466-8MC11 analog input module (8 data bits).

The CPU specifies the maximum length of the shift register in a particular configuration. •

CPU 100:

256 data bits, 128 (max.) of these from analog modules

•

CPU 102:

480 data bits, 256 (max.) of these from analog modules

•

CPU 103:

704 data bits, 512 (max.) of these from analog modules

Note If the maximum expansion allowed is exceeded, the S5-100U goes into the STOP mode. The “PEU” bit (I/O not ready) is set in the ISTACK.

2-8

EWA 4NEB 812 6120-02b

Page 33

S5-100U

Technical Description

Examples: a) CPU 100:

This CPU lets you operate six digital modules (8-channel) and two analog modules (4-channel): [6 x 8+2 x (4 x 16)]=48+128<256 b) CPU 100:

This CPU does not let you use three digital modules (8-channel) with three analog modules (4-channel) because the maximum permissible number of analog data bits would be exceeded: [3 x 8+3 x (4 x 16)]=24+192<256 c) CPU 102:

This CPU lets you operate seven digital modules (8-channel) and four analog modules (4-channel): [7 x 8+4 x (4 x 16)]=56+256<480 d) CPU 102:

This CPU does not let you use 20 digital modules (8-channel) with 5 analog modules (4-channel) because the maximum permissible number of analog data bits would be exceeded: [20 x 8+5 x (4 x 16)]=160+320=480 e) CPU 103:

This CPU lets you operate 24 digital modules (8-channel) and eight analog modules (4-channel): [24 x 8+8 x (4 x 16)]=192+512=704 f)

CPU 103:

This CPU does not let you use 31 digital modules (8-channel) with four analog modules (2-channel) because the maximum permissible number of slots would be exceeded: [31 x 8+4 x (2 x 16)]=248+128<704

EWA 4NEB 812 6120-02b

2-9

Page 34

EWA 4NEB 812 6120-02b

Page 35

3

Installation Guidelines 3.1 3.1.1 3.1.2 3.1.3 3.1.4

Installing S5-100U Components . . . . . . . . . . . . . . . . . . . . . . . . . Assembling a Tier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Multi-Tier Expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cabinet Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Vertical Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3 3 3 3 3 -

3.2 3.2.1 3.2.2 3.2.3 3.2.4

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connection Methods: Screw-Type Terminals and Crimp Snap-in . . Connecting the Power Supply to the S5-100U . . . . . . . . . . . . . . . Connecting Digital Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting the Digital Input/Output Module . . . . . . . . . . . . . . . . .

3 - 9 3 - 9 3 - 12 3 - 13 3 - 18

3.3 3.3.1 3.3.2 3.3.3

Electrical Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Configuration for the S5-100U . . . . . . . . . . . . . . . . . . . . Electrical Configuration with External I/Os . . . . . . . . . . . . . . . . . . . Non-Floating and Floating Configurations . . . . . . . . . . . . . . . . . . .

3 - 20 3 - 20 3 - 21 3 - 25

3.4

Wiring Arrangement, Shielding, and Measures to . . . . . . . . . . . . . Guard against Electromagnetic Interference Running Cables Inside and Outside a Cabinet . . . . . . . . . . . . . . . Running Cables Outside Buildings . . . . . . . . . . . . . . . . . . . . . . . . Equipotential Bonding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Shielding Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Special Measures for Interference-Free Operation . . . . . . . . . . . . .

3 - 29

3.4.1 3.4.2 3.4.3 3.4.4 3.4.5

EWA 4NEB 812 6120-02b

1 1 5 7 8

3 - 29 3 - 30 3 - 31 3 - 32 3 - 33

Page 36

Figures 3-1 3-2 3-3 3-4 3-5 3-6 3-7 3-8 3-9 3-10 3-11 3-12 3-13 3-14 3-15 3-16 3-17 3-18 3-19

3-20 3-21 3-22 3-23 3-24 3-25 3-26 3-27 3-28

Mounting the PS 930 Power Supply Module . . . . . . . . . . . . . . . . . . . . . . . Removing Bus Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Coding System to Prevent an Inadvertent Interchange of Modules . . . . . . . . Interconnecting Tiers with Interface Modules (6ES5 316-8MA12) ........ Multi-Tier Configuration in a Cabinet with the IM 316 Interface Module (6ES5 316-8MA12) . . . . . . . . . . . . . . . . . . . . . . . Cabinet Mounting with a Series of Devices . . . . . . . . . . . . . . . . . . . . . . . . Vertically Mounting a Programmable Controller . . . . . . . . . . . . . . . . . . . . . . SIGUT/Screw-Type Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . Mounting the Crimp Snap-in Terminal ........................... Disconnecting a Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting a Power Supply Module and a CPU . . . . . . . . . . . . . . . . . . . . . Two-Wire Connection of a Sensor to Channel 2 . . . . . . . . . . . . . . . . . . . . . Two-Wire Connection of a Lamp to Channel 3 . . . . . . . . . . . . . . . . . . . . . . Connecting a Sensor to Channel 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Connecting a Lamp to Channel 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Front View of the Digital I/O Module with a Crimp Snap-In Connector (simplified view and not true to scale) ........................... Connecting a Sensor and a Load to Digital Input/Output Module 482 . . . . . . Configuration Possibility: S5-100U with 115/230 V AC Power Supply for Programmable Controller, Sensors, and Actuators . . . . . . . . . . . . . . . . . Configuration Possibility: S5-100U with 24 V DC Power Supply (with Safe Electrical Isolation According to DIN VDE 0160) for Programmable Controller, Sensors, and Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Non-Grounded Operation; 24 V DC Power Supply (with Safe Electrical Isolation According to DIN VDE 0160) for Programmable Controller and I/Os . . . Example: Non-Floating Connection of I/Os to the S5-100U . . . . . . . . . . . . . Simplified Representation of a Non-Floating I/O Connection . . . . . . . . . . . . Simplified Representation of a Galvanically Isolated Connection of the I/Os to the S5-100U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A Simplified Representation of a Floating I/O Connection . . . . . . . . . . . . . . Laying Equipotential Bonding Conductor and Signal Label . . . . . . . . . . . . . . Fixing Shielded Cables with Various Types of Cable Clamps . . . . . . . . . . . . Wiring Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Measures for Suppressing Interference from Fluorescent Lamps in the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3 3 3 3 -

2 3 4 5

3 - 7 3 - 8 3 - 8 3 - 9 3 - 10 3 - 11 3 - 12 3 - 14 3 - 15 3 - 16 3 - 17 3 - 18 3 - 19 3 - 22

3 - 23 3 - 24 3 - 25 3 - 26 3 - 27 3 - 28 3 - 31 3 - 33 3 - 33 3 - 34

Tables 3-1 3-2 3-3

Installing, Removing, and Changing S5-100U Components . . . . . . . . . . . . Connecting the Load Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Rules for Common Running of Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3 - 1 3 - 13 3 - 29

EWA 4NEB 812 6120-02b

Page 37

S5-100U

Installation Guidelines

3

Installation Guidelines

3.1

Installing S5-100U Components

Except for the I/O module, all of the S5-100U components are mounted on standard mounting rails in accordance with DIN EN 50022-35x15. Mount the rails on a metal plate to obtain the same reference potential. Bus units with a SIGUT/screw-type, or crimp snap-in connection method have different heights. If you install, remove, or change any parts of your S5-100U system, your system must be in the state indicated in Table 3-1. Table 3-1. Installing, Removing, and Changing S5-100U Components Installing, Removing, and Changing:

S5-100U Power Status

S5-100U Operating Mode

Load Voltage

I/O modules

X

STOP

OFF

Bus units Interface modules

Power OFF

X

X

CPU power supply

Power supply voltage OFF

X

X

X=not relevant

3.1.1

Assembling a Tier

You need the following components to configure the S5-100U: • • • •

Power supply module Central processing unit Bus units I/O modules

If you do not have a 24 V DC power supply, you must have a power supply module. Mount the first module on the extreme left end of the standard mounting rail. Add other modules to the right of the first module.

EWA 4NEB 812 6120-02b

3-1

Page 38 read from a scan by OCR; it may hold reading errors

Installation Guidelines S5-100U

Mounting the PS 930 Power Supply Module The backplane design makes it easy to attach this module to the standard mounting rail.

1. Hook the module onto the standard mounting rail. 2. Swing the module back until the slide snaps into place (see Figure 3-1).

Figure 3-1. Mounting the PS 930 Power Supply Module

Removing the PS 930 Power Supply Module

Turn off the 115 V/230 V AC power supply.

Remove the connections between the CPU and the power supply module. Use a screwdriver to press down on the slide on the bottom of the module. Swing the module up and out of the standard mounting rail.

PONS

Mounting the Central Processing Unit

Follow the same procedure you used to mount the PS 930 power supply module (see Figure 3-1). 1. Hook the CPU onto the rail and to the right of the power supply module. 2. Swing the CPU back until the slide snaps into place.

3-2 EWA 4NEB 812 6120-02b

Page 39 read from a scan by OCR; it may hold reading errors

S5-100U Installation Guidelines

Removing the CPU

1. Remove the I/O module located at slot “0”.

2. Pull the connection (ribbon cable) between the CPU and the first bus unit. 3. Pull the connections between the CPU and the power supply module.

4. Use a screwdriver to press down on the slide on the bottom of the module. 5. Swing the module up and out of the standard mounting rail.

Mounting Bus Units

Use the same procedures to mount the bus unit that you used to mount both the power supply module and the CPU. Hooks are located on the sides of each bus unit. These hooks are used to connect bus units to each other and to connect bus units to the CPU.

Connecting Bus Units to Each Other or to the CPU

1. Pull the ribbon cable connector located on the top left of the bus unit out of its holder. 2. Plug the connector either into the receptacle located on the right side of the CPU or into the receptacle of the adjacent bus unit located on the left (see Figure 3-2).

Removing Bus Units

1. Pull the connections to the neighboring bus units or to the CPU. 2. Use a screwdriver to press down on the slide. 3. Swing the module up and out of the standard mounting rail.

EWA 0183

Figure 3-2. Removing Bus Units

EWA 4NEB 812 6120-02b 3-3

Page 40 read from a scan by OCR; it may hold reading errors

Installation Guidelines S5-100U

Plugging Input and Output Modules into the Bus Units

Before you plug in an input or output module, you must set the bus unit’s coding element to match the module type.

Setting the Coding Element

An identification number is printed on the front plate of every I/O module. Depending on the particular module type, the number is between two and eight. There is a white mechanical coding key located on the back of each module. The position of the coding key is determined by the module type and cannot be changed. The bus unit has a mating component for each key, a white rotating coding element or “lock” (see Figure 3-3).

Use a screwdriver to set the “lock” on the bus unit to the corresponding I/O module code number.

Figure 3-3. Coding System to Prevent an Inadvertent Interchange of Modules

The 6ES5 788-8MA11 simulator module does not have a coding key. You can plug in this simulator module in place of any module.

Attaching I/O Modules

Hook the module onto the top of the bus unit.

Swing the module down onto the bus unit.

Press the module down firmly.

Tighten the hold-down screw on the front of the module to attach the module to the bus unit.

PONs

Removing I/O Modules Remove the hold-down screw and swing the module up and out of the bus unit.

3-4 EWA 4NEB 812 6120-02b